SILENT KNIGHT SK-6324 Installation And Operation Manual Download Page 1

Fire Control Panel

Part Number 151117C, 03/01

SK-6324

Installation and
Operation Manual

firealarmresources.com

Summary of Contents for SK-6324

Page 1: ...Fire Control Panel Part Number 151117C 03 01 SK 6324 Installation and Operation Manual firealarmresources com...

Page 2: ...tions 3 4 3 6 Mounting the SK 6324 3 5 3 7 Assembly 3 6 3 8 Wiring Specifications 3 7 3 9 Calculating Current Draw and Standby Battery 3 8 3 9 1 Worksheet Requirements 3 8 Filling in the Current Draw...

Page 3: ...o the Control Panel 4 13 4 9 3 Setting the SK 2880 Address 4 13 4 9 4 Open Collector Outputs P1 P2 and P3 4 15 4 9 5 Wiring SK 2880 Open Collector Outputs 4 17 4 9 6 SK 2880 Input Switches and Relay W...

Page 4: ...pecial applications such as door holders Enhanced Verification Mode a built in feature that distinguishes two wire smoke detectors from pull stations Housed in a 12 75 W x 15 H x 3 25 D metal cabinet...

Page 5: ...Model SK 6324 Fire Control Panel Installation Operation Manual 1 2 151117 firealarmresources com...

Page 6: ...eral requirements are described in this section When installing an individual device refer to the specific section of the manual for additional requirements 1 All field wiring must be installed in acc...

Page 7: ...Model Fire Control Panel Installation Operation Manual 2 2 firealarmresources com...

Page 8: ...er Part Quantity Item 1 Cabinet 122509 Panel Bag 1 Control Board 063240 1 Installation Manual 151117 Hardware Bag P N 7648 2 8 Screws 119152 2 8 Nuts 119538 3 Self tapping Screws 119296 1 Earth Ground...

Page 9: ...Name Description SK 2880 Input Output I O Module Used to drive customized annunciators and interface devices SK 2866 LED Annunciator Remote LED annunciator with Silence and Reset keyswitch inputs SK...

Page 10: ...of terminals connectors dip switches and LEDs Figure 3 1 Model SK 6324 Layout Zone Inputs 3 Notification Appliance Circuits Trouble Alarm Relays Auxiliary Power Output Backup Battery Connector AC Powe...

Page 11: ...er system inspection ports Do not mount in areas with humidity generating equipment such as dryers production machinery Table 3 3 Electrical Specifications Circuit Rating Primary AC 120 Vrms at 60 Hz...

Page 12: ...on concrete especially when moisture is expected attach a piece of 3 4 inch plywood to the concrete surface and then attach the cabinet to the plywood Also mount any other modules to the plywood Follo...

Page 13: ...Snap the bezel into the opening in the front of the cabinet See Figure 3 3 Figure 3 3 Assembly Diagram for the SK 6324 Note The bezel will fit in only one way 5 With the two 8 Screws and the two 8 nut...

Page 14: ...rom different groups through the same conduit If you must run them together do so for as short a distance as possible or use shielded cable Connect the shield to circuit ground at the panel You must r...

Page 15: ...s and record in the table at Line C 4 Any additional devices should be recorded at Line D 5 Make sure that the alarm current without the panel Lines B D does not exceed 2 5 A The total alarm current i...

Page 16: ...device manual for current ratings See Appendix to this manual for max per loop Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Al...

Page 17: ...Model SK 6324 Fire Control Panel Installation Operation Manual 3 10 151117 firealarmresources com...

Page 18: ...ssary for a professional electrician to make this connection The AC inputs are rated as 120 VAC 60 Hz for transformer P N 115061 or 230 VAC 50 Hz for transformer P N 115031 See Table 3 1 for more info...

Page 19: ...ng Determine the correct AH rating as per your current load calculation see Table 3 6 Wire batteries in series to produce a 24 volt equivalent Do not parallel batteries to increase the AH rating Note...

Page 20: ...Smoke Detector Wiring Figure 4 4 shows how to connect two wire smoke detectors to the SK 6324 loops The figure uses Silent Knight s SLK 24F with HSB 224 base as an example You can use any detector th...

Page 21: ...ectors to the SK 6324 loops The figure uses Silent Knight s SLK 24F with HSC 4R base as an example You can use any UL listed device Refer to the Appendix for a list of compatible devices Information o...

Page 22: ...d at the factory See Section 5 for information on changing the pattern Figure 4 6 Notification Circuit Installation 4 4 Alarm and Trouble Relays The SK 6324 has built in relays for alarm and trouble T...

Page 23: ...l Installation Operation Manual 4 6 151117 4 6 Door Release Wiring Figure 4 7 shows how to configure a door release using an ESL DH series door holder Figure 4 7 Door Release Wiring Unsupervised Power...

Page 24: ...the expansion devices to the control panel as follows Model Number Name Description SK 2866 Remote LED Annuncaitor Remote LED annunciator with system reset and silence key switch inputs See Section 4...

Page 25: ...ion and wiring of this device must be done in accordance with NFPA 72 and local ordinances Follow these steps to properly wire the SK 2866 to the SK 6324 Control Panel 1 Remove AC power from the panel...

Page 26: ...Follow these steps to mount the SK 2866 1 Make sure that the SK 2866 is properly wired to the control panel See Figure 4 8 2 Slide the printed annunciator label into place on the SK 2866 The label fit...

Page 27: ...the SK 2866 and align the holes See Figure 4 9 5 Insert the four cover plate screws into the four screw holes on the standard 3 gang electri cal box 6 Screw the four cover plate screws into the cover...

Page 28: ...Reset and Silence See Figure 4 13 Figure 4 10 Components of the SK 2880 I O Module 4 9 1 SK 2880 Specifications Table 4 5 Specifications Circuit Rating Max Loop Resistance Data 25 25 25 Max Current Al...

Page 29: ...gure 4 11 I O Module Wiring 4 9 3 Setting the SK 2880 Address The range of valid addresses is 0 3 Each device requires a unique address Set the dip switches as shown in Table 4 6 See Figure 4 11 for d...

Page 30: ...visory Outputs when there is an alarm or supervisory on Zone 4 Pin 11 Zone 4 Trouble Outputs when a trouble condition exists on Zone 4 Pin 12 Zone 4 Clean Me Trouble Outputs when a Clean Me type detec...

Page 31: ...as been silenced Pin 7 Low AC Outputs if the control panel looses AC power or AC power drops below the control panels low AC threshold Pin 8 Low Battery Outputs when the backup battery voltage drops b...

Page 32: ...Figure 4 13 illustrates how to configure the inputs switches and the Form C Relays Figure 4 13 Wiring Examples for Input Switches and Form C Relays Note Reset and Silence switches must be UL recogniz...

Page 33: ...utward on the base retain ing tabs and lift the circuit board out See Figure 4 14 Figure 4 14 Circuit Board and Plastic Base Components 3 Mount the plastic base in a UL listed enclosure using any of t...

Page 34: ...ns Dip Switch Number Feature Switch Number Comments Zone 1 1 Enhanced Mode On 1 On Enhanced mode Use when both pull stations and detectors will be used in the same zone Enhanced Mode Off 1 Off Normal...

Page 35: ...th Delay 7 On Refer to General Options to program the Water Flow delay time 8 On Zone 3 2 Enhanced Mode On 1 On Enhanced mode Use when both pull stations and detectors will be used in the same zone En...

Page 36: ...o General Options to program the Water Flow delay time 8 On Zone 5 3 Enhanced Mode On 1 On Enhanced mode Use when both pull stations and detectors will be used in the same zone Enhanced Mode Off 1 Off...

Page 37: ...n NAC 1 Non Silencing 1 Off NAC 1 ANSI 2 On NAC 1 Steady 2 Off NAC 2 Silence 3 On NAC 2 Non Silencing 3 Off NAC 2 ANSI 4 On NAC 2 Steady 4 Off NAC 3 Silence 5 On NAC 3 Non Silencing 5 Off NAC 3 ANSI 6...

Page 38: ...od AC OFF Low AC trouble condition and it was acknowledged FLASHING Unacknowledged AC Low trouble condition If flashing press the ACK button to acknowledged the condition GENERAL TROUBLE yellow ON Sys...

Page 39: ...shing press the ACK button to acknowledged the condition SUPERVISORY yellow ON Zone has a supervisory condition which has been acknowledged self restoring condition OFF No supervisory condition exists...

Page 40: ...ilable during an alarm or supervisory condition To re enable a zone Press the appropriate ZONE DISABLE again Begin Walk Test Press WALK TEST Walk Test LED turns on Note Walk test will not activate if...

Page 41: ...Model SK 6324 Fire Control Panel Installation Operation Manual 6 4 151117 firealarmresources com...

Page 42: ...se alarms could occur Do not mix different models of detectors on any zone false alarms could occur A 1 1 Enhanced Mode Enhanced mode allows the installer to use pull stations on a loop that has been...

Page 43: ...op 55000 250 45681 200 55000 250 45681 200 24 loop Detection Systems DS250 MB2W or MB2WL B A 18 loop DS250HD MB2W or MB2WL B A 18 loop DS250TH MB2W or MB2WL B A 18 loop ESL 429C S10A N A S10A 30 loop...

Page 44: ...loop Table A 2 Compatible Four Wire Smoke Detectors Manufacturer Model Silent Knight SD P24F with SD B4 base Detection Systems DS200 DS200HD MB200 ESL 445 Series 449 Series Gentex 624 824 2040 24 Powe...

Page 45: ...DC Multi Tone Horn Strobe ceiling Faraday 5343B 0 14 24 DC Single Tone Horn Strobe flush Faraday 5344B 0 14 24 DC Single Tone Horn Strobe surface Faraday 5345B 0 4 24 DC Single Tone Horn Strobe ceili...

Page 46: ...robe Strobe ceiling Faraday 6320B 0 14 24 DC Sync Mini Horn Strobe 1 gang Faraday 6321B 0 14 24 DC Sync Mini Horn Strobe 1 2 gang Faraday 6322B 14 24 DC Mini Horn Sync Strobe 1 2 gang 4SQ Federal Sign...

Page 47: ...AES DL1 WS 24 VF R Multitone Horn Wheelock AES EL1 WS 24 VF R Multitone Horn Wheelock AES DL1 WH 24 VF R Multitone Horn Wheelock AES EL1 WH 24 VF R Multitone Horn Wheelock AES DL1 WM 24 VF R Multitone...

Page 48: ...F1 Chime Wheelock CH DF1 R Chime Wheelock CH BF1 WS 24 HF R Strobe Chime Wheelock CH CF1 LS 24 Strobe Chime Wheelock CH CF1 MS 24 Strobe Chime Wheelock CH CF1 IS 24 Strobe Chime Wheelock CH CF1 LS 24...

Page 49: ...ote Strobe Wheelock IS3 24 VFR Remote Strobe Wheelock ISP 24 HFR Remote Strobe Wheelock LS 24 VFR Remote Strobe Wheelock LS1 24 VFR Remote Strobe Wheelock LS3 24 VFR Remote Strobe Wheelock LSP 24 HFR...

Page 50: ...MT 24 WM Strobe Wheelock MT 24 WM VF R Horn Wheelock MT 24 WM VFR Strobe Horn Wheelock NH 12 24 R Horn Wheelock NS 2415W FR Strobe Horn Wheelock NS 241575W FR Strobe Horn Wheelock NS 2430W FR Strobe...

Page 51: ...FR Synchronized Remote Strobe Wheelock SL3 24 VFR Synchronized Remote Strobe Wheelock SLP 24 VFR Synchronized Remote Strobe Wheelock SLM 24 VFR Synchronized Remote Strobe Wheelock SL1M 24 VFR Synchron...

Page 52: ...12 24 W FR Strobe Horn Wheelock WM3T 24 FR Remote Strobe Wheelock WM3T 24 VFR Remote Strobe Wheelock WS1T 24 FR Strobe Wheelock WS3T 24 FR Strobe Wheelock WST 24 FR Strobe Table A 3 Compatible Notifi...

Page 53: ...Model SK 6324 Fire Control Panel Installation Operation Manual A 12 151117 firealarmresources com...

Page 54: ...roducts that are returned in cabinets will be charged an additional 20 to cover the extra shipping and handling costs over board only returns Do not return batteries Silent Knight has the authority to...

Page 55: ...ver Upon return of the defective product Silent Knight will at its sole discretion either repair or replace at no cost such goods as may be of defective material or workmanship Customers outside the U...

Page 56: ...he ACK button to acknowledged the condition TROUBLE yellow ON Zone has a trouble condition which has been acknowledged OFF No zone trouble FLASHING Zone has a trouble condition not yet acknowledged DO...

Page 57: ...Cut Along the Dotted Line firealarmresources com...

Page 58: ...2001 Silent Knight Part Number 151117C 03 01 7550 Meridian Circle Maple Grove MN 55369 4927 763 493 6455 1 800 328 0103 Fax 763 493 6475 firealarmresources com...