background image

 

 

 

                   IRSC Plus

 

http://www.zennio.com

 

                 

Technical Support:

 

http://support.zennio.com

 

 

13 

 

Figure 6. 

Status Window 

It is possible to activate status objects for the following actions: 

 

ON/OFF

:

 

enables the "ON/OFF (status)" binary object, which shows the A/C 

system  operation  status:  value  "1"  indicates  that  the  system  is  active, 

whereas the value "0" indicates the system is inactive.  

 

Mode

:  enables  one  status  object  per  available  mode  ("Heat  Mode  (status)", 

"Cool  Mode  (status)",  "Dry  Mode  (status)",  "Fan  Mode  (status)"  and  "Auto 

Mode  (status)")  as  well  as  the  "Mode  [1  byte]  (status)"  object.  The  first  five 

objects (1-bit) are set to "1" when their corresponding modes are active, while 

"0" indicates that the mode is not active. The 1-byte object is set to a certain 

integer value according to the currently active mode (according to Table 2)

 

Fan

:  enables  the  "Fan  (status)"  1-byte  object,  which  shows  the  current  fan 

speed, in percentage, of the A/C system (according to Table 1). 

 

Swing

:

 

enables  the  "Swing  (status)"  1-bit  object,  which  shows  the  current 

status  of the  slats  of  the  A/C  system  (if  available): the  value  "1"  means that 

the  swing  is  active,  while  "0"  indicates  that  the  slats  are  still.  Note  that  the 

swing function may differ slightly depending on the A/C system model. Please 

refer to section 3.1 for more details.  

3.4

 

RESET - INITIAL CONFIGURATION 

From  the  “Reset  (initial  configuration)”  and  the  “Reset  (data  update)”  tabs,  the 

integrator will be able to set the desired response to be performed by IRSC Plus upon 

KNX power losses as well as the initial status after a download or a device reset from 

ETS.  On  the  one  hand,  the  former  permits  defining  the  desired  status  in  the  air 

Summary of Contents for IRSC Plus

Page 1: ...IRSC Plus Air Conditioning Controller ZN1CL IRSC USER MANUAL Application program version 6 12 8 0 User manual edition 8 0 _a www zennio com...

Page 2: ...4 1 3 The IRSC Plus Application Program 6 2 Configuration 7 3 ETS Parameterisation 8 3 1 Default Configuration 8 3 2 General Parameters 11 3 3 Status 12 3 4 Reset Initial Configuration 13 3 5 Reset Da...

Page 3: ...Open Window function 20 6 11 _a Changes in the application program Additional split models available for control 6 10 _a Changes in the application program Additional split models available for contr...

Page 4: ...ctions into the same device Control of the main functionalities of A C units On Off temperature mode fan speed etc Compatibility with most air conditioning manufacturers please refer to the correspond...

Page 5: ...ing the associated LED 2 light in red If this button is held while plugging the device into the KNX bus IRSC goes into safe mode IR emitter 5 infrared flashing diode to send commands to the air condit...

Page 6: ...common air conditioning systems via IR commands This application allows sending control orders to the A C system through infrared commands with IRSC acting as a KNX IR interface as explained in Secti...

Page 7: ...ver the following functionalities of the A C system can be configured ON OFF control of the A C system Status Objects which also work as acknowledgement objects for the orders sent to the system Worki...

Page 8: ...nt functionalities of IRSC Plus in ETS 3 1 DEFAULT CONFIGURATION This section shows the default configuration the device parameterisation starts from for the first time Figure 4 IRSC Plus Default Topo...

Page 9: ...iving a 1 through this object will make the slats swing i e perform a progressive sweep while one 0 will make them stop In the case of machines that permit multiple still positions for the slats the a...

Page 10: ...sed control orders which can be done by sending a 1 to its corresponding IRSC controller through the address of the Disable device object On the other hand when IRSC Plus is parameterised for the firs...

Page 11: ...to be controlled These are the following Split Model sets a code between 0 and 255 associated to the model of the IR remote of the system to be controlled please refer to the correspondence table at h...

Page 12: ...meterised temperature limitation effectively applied in such case the system will always keep the setpoint over the lower limit for Cool mode and under the upper limit for Heat mode truncating it when...

Page 13: ...tain integer value according to the currently active mode according to Table 2 Fan enables the Fan status 1 byte object which shows the current fan speed in percentage of the A C system according to T...

Page 14: ...wever after a download or a device reset from ETS the previous status will be lost during the download or the device reset in such case IRSC Plus will assume ON OFF Off Temperature 25 C Mode Cool Fan...

Page 15: ...or a device reset the status of the slats can be set to Last saved status1 Swing or Stopped Note that for both a default and for a custom configuration the Send Reset Configuration to the Split when r...

Page 16: ...the state sent to or assumed in the A C system after a bus interruption a download or a device reset This is done from the Reset Data Update screen Figure 8 Reset Data Update It is possible to select...

Page 17: ...cts should have been enabled see section 3 3 in order to have these values effectively sent to the bus Important if this sending is not enabled the KNX bus will definitively not be informed about the...

Page 18: ...mosphere to be generated Scene Number the numeric value 1 to 64 on whose arrival from the bus through the Scenes 1 byte object decreased by one 0 to 63 the air conditioning system will execute the sce...

Page 19: ...n and off can be independently enabled and configured After activating the Automatic OFF the Fixed Auto OFF 1 bit object will appear and the following parameters will also be shown in ETS Automatic OF...

Page 20: ...igured waiting period and then it will send a switch off order to the A C system When the window is closed again Window sensor 0 the A C system will be automatically switched on it will not be necessa...

Page 21: ...the time period in minutes that IRSC Plus should wait after receiving the value 0 empty room through the detection object before switching the A C unit off As soon as the Presence detection object rec...

Page 22: ...1IR ZAS and ZN1IRZ38 of any of the various Zennio devices capable of receiving IR signals ZAS InZennio Z38i ACTinBOX Hybrid ACTinBOX MAX6 or ACTinBOX QUATRO One of these devices will be therefore requ...

Page 23: ...er device ZAS InZennio Z38i ACTinBOX Hybrid ACTinBOX MAX6 or ACTinBOX QUATRO of the signals generated by the emitter and therefore whether IRSC Plus is behaving anomalously or not Important it is high...

Page 24: ...T W U DPST 1 1 DPST 1 10 0 1 Swing 1 Swing 0 Stop Step 7 1 Bit O C T R DPST 1 1 DPST 1 10 0 1 Swing status Swing state 0 Stopped 1 Swing 8 1 Bit I C T W U DPT_Switch 0 1 Heat Mode 1 Set mode 0 Nothing...

Page 25: ...Auto OFF 1bit 1 Sw OFF after param value 23 1 Bit I O C R W U DPT_Start 0 1 Fixed Auto ON 1bit 1 Sw ON after param value 24 1 Bit I C W U DPT_Bool 0 1 Presence Detection 0 Empty Room 1 Presence 25 1...

Page 26: ...d us your inquiries about Zennio devices http suppot zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 Fax 34 925 337 310 www zennio com info...

Reviews: