ETS PARAMETERISATION
To begin with the parameterisation process of the IRSC controller it is necessary, once
the data base of the product (
IRSC Plus
application program) has been imported to
ETS, to add the device to the project where desired. After that, one right-click on the
device will permit selecting "Edit parameters", in order to start the configuration.
In the following sections a detailed explanation can be found about the different
functionalities of IRSC Plus in ETS.
3.1
DEFAULT CONFIGURATION
This section shows the default configuration the device parameterisation starts from for
the first time.
Figure 4.
IRSC Plus. Default Topology
The following communication objects are available by default:
ON/OFF
, aimed to receive orders from the bus to switch on or off the A/C
unit.
Temperature
, which will receive setpoint temperatures (in ºC) to be sent to
the machine. Moreover, this object can work as a status object, as the
“R”
(read) flag is active by default.
Fan [1 byte]
, aimed to receive orders from the bus to switch the A/C machine
from one fan speed to another (automatic, minimum, medium or maximum,
depending on the range the received value belongs to).