background image

 

 

 

                   IRSC Plus

 

http://www.zennio.com

 

                 

Technical Support:

 

http://support.zennio.com

 

 

10 

 

Disable Device

: binary object that will set IRSC into a standby mode on the 

reception of the value 

“1” from the bus. This prevents IRSC from reacting to 

control orders received from the bus 

–only read requests will be processed– 

and  from  sending  IR  orders  to  the  A/C  unit 

until  the  value  “0”  is  received. 

Therefore,  once  a  certain  state  has  been  set  to  the  A/C  unit,  sending  the 

value 

“1”  to  this  object  will  lock  that  state,  preventing  bus  orders  from 

changing  it.  This  function  makes  sense,  for  example,  when  a  centralised 

control system sends orders simultaneously to several IRSC controllers, and 

therefore  to  different  A/C  units.  At  a  certain  time  (for  power  saving  reasons, 

for  instance),  it  may  be  required  that  any  of  them  stops  reacting  to  the 

centralised  control  orders,  which  can  be  done  by  sending  a  “1”  to  its 

corresponding 

IRSC  controller  (through  the  address  of  the  “Disable  device” 

object). 

On  the  other  hand,  when  IRSC  Plus  is  parameterised  for  the  first  time,  the  following 

window will be shown: 

 

Figure 5. 

Configuration Screen by default 

As shown in Figure 5, the configuration screen is divided into the following main tabs: 

 

General  Parameters

:  general  features  of  the  air  conditioning  system  being 

controlled. 

 

Status

: allows enabling and disabling a set of 

status

 objects over which it will 

be  possible  to  send  read  requests  from  externally.  These  objects  will  report 

information  about  the  current  state  of  the  machine  and  will  also  work  as  an 

acknowledgement  signal  of  any  changes  made  over  this  state  whenever  a 

control order is received from the bus. 

 

Reset

:

 

allows  customising  the  status  of  the  A/C  system  after  a  bus  power 

failure  or  after  an  application  program  or  parameter  download,  as  well  as 

selecting whether to send or not the updated status objects to the KNX bus. 

Summary of Contents for IRSC Plus

Page 1: ...IRSC Plus Air Conditioning Controller ZN1CL IRSC USER MANUAL Application program version 6 12 8 0 User manual edition 8 0 _a www zennio com...

Page 2: ...4 1 3 The IRSC Plus Application Program 6 2 Configuration 7 3 ETS Parameterisation 8 3 1 Default Configuration 8 3 2 General Parameters 11 3 3 Status 12 3 4 Reset Initial Configuration 13 3 5 Reset Da...

Page 3: ...Open Window function 20 6 11 _a Changes in the application program Additional split models available for control 6 10 _a Changes in the application program Additional split models available for contr...

Page 4: ...ctions into the same device Control of the main functionalities of A C units On Off temperature mode fan speed etc Compatibility with most air conditioning manufacturers please refer to the correspond...

Page 5: ...ing the associated LED 2 light in red If this button is held while plugging the device into the KNX bus IRSC goes into safe mode IR emitter 5 infrared flashing diode to send commands to the air condit...

Page 6: ...common air conditioning systems via IR commands This application allows sending control orders to the A C system through infrared commands with IRSC acting as a KNX IR interface as explained in Secti...

Page 7: ...ver the following functionalities of the A C system can be configured ON OFF control of the A C system Status Objects which also work as acknowledgement objects for the orders sent to the system Worki...

Page 8: ...nt functionalities of IRSC Plus in ETS 3 1 DEFAULT CONFIGURATION This section shows the default configuration the device parameterisation starts from for the first time Figure 4 IRSC Plus Default Topo...

Page 9: ...iving a 1 through this object will make the slats swing i e perform a progressive sweep while one 0 will make them stop In the case of machines that permit multiple still positions for the slats the a...

Page 10: ...sed control orders which can be done by sending a 1 to its corresponding IRSC controller through the address of the Disable device object On the other hand when IRSC Plus is parameterised for the firs...

Page 11: ...to be controlled These are the following Split Model sets a code between 0 and 255 associated to the model of the IR remote of the system to be controlled please refer to the correspondence table at h...

Page 12: ...meterised temperature limitation effectively applied in such case the system will always keep the setpoint over the lower limit for Cool mode and under the upper limit for Heat mode truncating it when...

Page 13: ...tain integer value according to the currently active mode according to Table 2 Fan enables the Fan status 1 byte object which shows the current fan speed in percentage of the A C system according to T...

Page 14: ...wever after a download or a device reset from ETS the previous status will be lost during the download or the device reset in such case IRSC Plus will assume ON OFF Off Temperature 25 C Mode Cool Fan...

Page 15: ...or a device reset the status of the slats can be set to Last saved status1 Swing or Stopped Note that for both a default and for a custom configuration the Send Reset Configuration to the Split when r...

Page 16: ...the state sent to or assumed in the A C system after a bus interruption a download or a device reset This is done from the Reset Data Update screen Figure 8 Reset Data Update It is possible to select...

Page 17: ...cts should have been enabled see section 3 3 in order to have these values effectively sent to the bus Important if this sending is not enabled the KNX bus will definitively not be informed about the...

Page 18: ...mosphere to be generated Scene Number the numeric value 1 to 64 on whose arrival from the bus through the Scenes 1 byte object decreased by one 0 to 63 the air conditioning system will execute the sce...

Page 19: ...n and off can be independently enabled and configured After activating the Automatic OFF the Fixed Auto OFF 1 bit object will appear and the following parameters will also be shown in ETS Automatic OF...

Page 20: ...igured waiting period and then it will send a switch off order to the A C system When the window is closed again Window sensor 0 the A C system will be automatically switched on it will not be necessa...

Page 21: ...the time period in minutes that IRSC Plus should wait after receiving the value 0 empty room through the detection object before switching the A C unit off As soon as the Presence detection object rec...

Page 22: ...1IR ZAS and ZN1IRZ38 of any of the various Zennio devices capable of receiving IR signals ZAS InZennio Z38i ACTinBOX Hybrid ACTinBOX MAX6 or ACTinBOX QUATRO One of these devices will be therefore requ...

Page 23: ...er device ZAS InZennio Z38i ACTinBOX Hybrid ACTinBOX MAX6 or ACTinBOX QUATRO of the signals generated by the emitter and therefore whether IRSC Plus is behaving anomalously or not Important it is high...

Page 24: ...T W U DPST 1 1 DPST 1 10 0 1 Swing 1 Swing 0 Stop Step 7 1 Bit O C T R DPST 1 1 DPST 1 10 0 1 Swing status Swing state 0 Stopped 1 Swing 8 1 Bit I C T W U DPT_Switch 0 1 Heat Mode 1 Set mode 0 Nothing...

Page 25: ...Auto OFF 1bit 1 Sw OFF after param value 23 1 Bit I O C R W U DPT_Start 0 1 Fixed Auto ON 1bit 1 Sw ON after param value 24 1 Bit I C W U DPT_Bool 0 1 Presence Detection 0 Empty Room 1 Presence 25 1...

Page 26: ...d us your inquiries about Zennio devices http suppot zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 Fax 34 925 337 310 www zennio com info...

Reviews: