background image

2 Requirements | 2.1 Environmental Requirements

ZEISS

Value

Temperature range for operation with indi-
cated performance (24 h per day, regardless
of whether the microscope is in operation or
switched off)

22 ± 3 °C

Temperature for reduced performance opera-
tion

15 to 35 °C

Recommended best temperature stability

± 0.5 °C/h

Long-term recommended stability

± 0.5 °C/h not more than ± 1.5 °C/h/12h

Relative humidity

< 65 %

Pollution degree [

}

 6]

2

To ensure sufficient clean air circulation through the cooling systems, do not operate the system
above the allowed altitude listed under 

Location Requirements [

}

 7]

.

Dust can cause erratic errors or possibly irreversible damage to electronic devices. Care should be
taken that the site is as dust free as possible.

2.1.2.1 Pollution Degrees

IEC 61010-1 specifies different types of pollution environments.

Pollution De-
gree

Description

1

No pollution or only dry, nonconductive pollution occurs. The pollution has
no influence. Example: A circuit in a hermetically sealed box (such as an IC
chip). No air can come into the box to bring condensation or conductive
particles.

2

Only nonconductive pollution occurs. Occasionally, temporary conductivity
caused by condensation is to be expected. Example: A circuit used in an of-
fice environment. The circuitry inside a computer would fall in this cate-
gory.

3

Conductive pollution occurs, or dry nonconductive pollution occurs that
becomes conductive due to condensation that is to be expected. Example:
Circuitry that is exposed to outside air, but will not be in contact with pre-
cipitation. A garage door opener would fall under this category. Note: Al-
though the IEC has defined this pollution degree in other documents,
IEC 61010-1 does not cover Pollution Degree 3.

4

The pollution generates persistent conductivity caused by conductive dust
or by rain or snow. Example: An exposed outdoor control box for a water
pump. Note: Although the IEC has defined this pollution degree in other
documents, IEC 61010-1 does not cover Pollution Degree 4.

2.1.3 Electromagnetic Compatibility

The Microscope System is suitable for laboratory and industrial premises but less suitable for do-
mestic premises where the EMC could interfere with nearby domestic appliances such as land line
phones and radios. The system can cause minimal electrical and radio interference as detailed by
its classification as a CISPR 11 / DIN EN 55011 / class A system according to DIN EN 61326-1.

6

Installation Requirements ZEISS LSM 900 | en-US | Rev. 2 | 349500-8183-000

Summary of Contents for LSM 900

Page 1: ...Installation Requirements ZEISS LSM 900 Laser Scanning Microscope...

Page 2: ...archiving purposes shall remain unaffected thereby Any viola tions may be prosecuted as copyright infringements The use of general descriptive names registered names trademarks etc in this document d...

Page 3: ...rvoltage Category 10 2 3 2 UPS Requirements 12 2 4 Network Connectivity 12 2 4 1 ZEISS Predictive Service 13 2 5 Safety and Radiation Information 14 2 5 1 Laser Safety 14 2 5 2 Biosafety Level of the...

Page 4: ...oom temperature Air quality The customer is responsible for ensuring that the conditions specified in this document are met and that the required equipment is available before delivery and installatio...

Page 5: ...than 50 dB Z class 200 to 500 Hz less than 55 dB Z class 2 1 2 Air Conditioning and Quality The following nominal power usage for the Microscope System and possible accessories is shown in Watts To m...

Page 6: ...porary conductivity caused by condensation is to be expected Example A circuit used in an of fice environment The circuitry inside a computer would fall in this cate gory 3 Conductive pollution occurs...

Page 7: ...d in closed rooms It is recommended to install the Microscope System in a dimmed room where artificial illumination sunlight or other light sources cannot interfere with image acquisition The Microsco...

Page 8: ...depending on the options purchased with the system For possible changes in preferential layout please dis cuss with your ZEISS representative The placing of the user table can vary depending on avail...

Page 9: ...ds and supplied socket with protective ground contact securely connected The provided electrical connection must be in accordance with the applicable electrical codes for the country of installation I...

Page 10: ...eferred to as Installation Category to address transient voltages Category IV devices can handle the largest transients relative to the normal working voltage Category I devices can handle only small...

Page 11: ...oltage levels of these loads must be rated at this overvoltage category III In fixed installations and for cases where the reliability and the availability of the equipment is subject to special requi...

Page 12: ...til normal mains is restored Please ensure to switch off the Microscope System be fore the batteries run low in a blackout In areas where the mains supply is very unstable or not very clean the most s...

Page 13: ...re the above network connectivity and predictive service will oper ate under the parameters shown in the table below Ports 443 Protocols HTTPS secure websocket URL of ZEISS server predictive service z...

Page 14: ...s the responsible body the operator is responsible for complying with laser safety regula tions The following types of lasers are currently intended for use Using other lasers than indicated be low re...

Page 15: ...ever some do exist in a small number of places in the US and around the world As the highest level of biological safety a BSL 4 lab consists of work with highly dangerous and exotic mi crobes Infectio...

Page 16: ...e user if the air supplied is from the building facilities or from gas bottles Due to acoustic noise and vibrations where possible the compressor should be installed in a sep arate room close to the w...

Page 17: ...f the system where necessary Some components such as the tables are large heavy or bulky and may require extra assis tance to get the units into the allocated site Maximum shock resistance Do not drop...

Page 18: ...s used not possi ble for Airyscan Anti vibration plate for Axio Imager 320 300 45 7 Anti vibration plate for Axio Observer 800 525 45 7 Microscope Axio Examiner Z1 700 390 820 24 Axio Imager Z2 560 39...

Page 19: ...EU RoHS and 2012 19 EU WEEE as applicable for the product In addition to the European and international guidelines and standards the 21 CFR 1040 10 Performance Standards for light emitting products la...

Page 20: ...ch requirements are yet to be completed ZEISS can be requested to assist with the checking of the environmental conditions Environmental conditions in and around a system can change with time due to v...

Page 21: ...adiation Information X Ray Laser Safety Biosafety Level of the Laboratory Cooling Water Supply Cooling liquid and or chemicals Exhaust Line Gas Supplies Compressed Air Nitrogen Additional Gas Transpor...

Page 22: ...l Zeiss Promenade 10 07745 Jena Germany phone 49 1803 33 63 34 fax 49 3641 64 3439 info microscopy de zeiss com www zeiss com microscopy Installation Requirements ZEISS LSM 900 en US Rev 2 Modificatio...

Reviews: