40 - EN
Error
code
Description code
Cause
Result /
Action
E21
Port 1 no
communication
Com port 1 failure
No communication with connected equipment
Check settings in parameter M08, connections and connected
devices
E22
Port 2 no
communication
Com port 2 failure
E23
Port 3 no
communication
Com port 3 failure
E24
Port 4 no
communication
Com port 4 failure
E25
Port 5 no
communication
Com port 5 failure
E26
FIRE FIRE
The assigned input contact “Fire Alert”
(FIRE) is activated
�
The supply and extract fans run at the values programmed
in parameters M02-19 and M02-20 or in parameters M02-21
and M02-22;
�
The bypass opens;
�
The cooling and heating closes.
E3110
Failure supply fan
Supply fan malfunctioning.
Check fan, cabling, both PCBs.
E3210
Failure exhaust fan
Extract fan malfunctioning.
Check fan, cabling, both PCBs.
E33
n/a
Parameter M12-01 programmed
incorrectly.
Set M12-01 to 0.
E34
Failure overall
The assigned input contact “General
failure” is activated.
�
The supply or extract fans switch off;
�
The bypass closes.;
�
The cooling and heating valves close.
E35
n/a
Parameter M12-01 programmed
incorrectly.
Set M12-01 to 0
E36
Failure supply air
pressure nozzle
Supply fan pressure nozzle not
registering pressure difference.
Corresponding fan still running at 50%
Check air volumes, pressure hose, pressure nozzle.
E37
Failure exhaust air
pressure nozzle
Extract fan pressure nozzle not
registering pressure difference.
E3811
Failure cooling
Cooling battery failure.
No Delta T across the battery.
Check the corresponding battery.
E3911
Failure heating
Heating battery failure.
E41
Frost contact closed
Frost risk! The assigned digital/
temperature input contact “Frost
protection” is activated.
�
Summer night cooling stops;
�
The supply fan is switched off;
�
The heating valve is set at a minimum of 50%;
�
The cooling/heating pump is switched on.
E4211,12
PreHeat frost extract
max power
Output preheater extract is more than
95% for at least 5 minutes.
No actions necessary
E4311,12
Frost recuperating
unit
Heat exchanger frost protection has
become active. (T4 < M12-02).
The supply fan is powered down or switched off in accordance
with M12-02 and M12-03 settings.
This message will automatically disappear if the measured
value T4 exceeds M12-02 settings again.
E4411
Filter Exhaust
Excessive pressure drop across extract
filter for at least 24 hours.
Replace extract filter.
E4511
Filter Supply
Excessive pressure drop across supply
filter for at least 24 hours.
Replace supply filter.
E46
Min supply temp
alarm
Required supply temperature too low. (T2
≤ M10-29).
Supply fan is deactivated and only reactivated 30 minutes after
T2 measures a higher value than M10-29.
E4711,12
Max Filter Exhaust
Pressure across exhaust air filter is higher
than set in M70-13.
The exhaust fan is powered down.
This message will automatically disappear if the pressure
across the exhaust air filter is lower than set in M70-13.
E4811,12
Max Filter Supply
Pressure across supply air filter is higher
than set in M70-13.
The supply fan is powered down.
This message will automatically disappear if the pressure
across the supply air filter is lower than set in M70-13.
10 This failure code can be activated by a digital input or the communication line of the fan itself
11 The Alarm relay stays deactivated. The ComfoAir XL active relay stays active.
12 This failure code does not need to be reset.