28 - EN
M7 – Analog output settings
Parameter
Description
Unit
M07-01
Analog output 14 (main PCB)
n/a
M07-02
Analog output 24 (main PCB)
n/a
M07-03
Analog output 34 (I/O PCB)
n/a
M07-04
Analog output 44 (I/O PCB)
n/a
M07-05
Analog output 54 (I/O PCB)
n/a
M07-11
Analog output 1 control (main PCB)
n/a
M07-12
Analog output 2 control (main PCB)
n/a
M07-13
Analog output 3 control (I/O PCB)
n/a
M07-14
Analog output 4 control (I/O PCB)
n/a
M07-15
Analog output 5 control (I/O PCB)
n/a
4 The analogue outputs can be set as
follows:
�
3: n/a;
�
7: Modulated bypass valve;
�
0: No function;
�
4: Post-Heater valve;
�
8: PreHeater ODA (= suppy air) valve;
�
1: Supply fan;
�
5: Post-Cooler valve;
�
9: PreHeater ETA (= extract air) valve.
�
2: Exhaust fan;
�
6: Post-Cooler/Heater valve;
M8 – Communication settings
Parameter
Description
Unit
M08-01
Comport 15
Do not change.
n/a
M08-02
Comport 25
Do not change.
n/a
M08-03
Comport 35
Do not change.
n/a
M08-04
Comport 45
Do not change.
n/a
M08-05
Comport 55
Do not change.
M80-11
Comport 1 control
%
M80-12
Comport 2 control
%
M80-13
Comport 3 control
%
M80-14
Comport 4 control
%
M80-15
Comport 5 control
%
5 The comports can be set as follows:
�
2: Exhaust fan (EBM bus);
�
4: Exhaust fan (EBM Modbus);
�
0: No function;
�
3: Supply fan (EBM Modbus);
�
5: n/a.
�
1: Supply fan (EBM bus);
M9 – Analog input settings
Parameter
Description
Unit
M09-01
Analog Input 16 (I/O PCB)
n/a
M09-02
Analog Input 26 (I/O PCB)
n/a
M09-03
Analog Input 36 (I/O PCB)
n/a
M09-11
Analog Input 1 reading (I/O PCB)
%
M09-12
Analog Input 2 reading (I/O PCB)
%
M09-13
Analog Input 3 reading (I/O PCB)
%
6 The analogue inputs can be set as
follows:
�
3: Proportional ventilation;
�
7: Exhaust air pressure (0..300Pa);
�
0: No function;
�
4: Supply air pressure (0..500Pa);
�
8: Supply air 0..10V input;
�
1: No function;
�
5: Exhaust air pressure (0..500Pa);
�
9: Exhaust air 0..10V input.
�
2: No function;
�
6: Supply air pressure (0..300Pa);
Summary of Contents for ComfoAir 1500