Depth of Discharge
80%
EPS Depth of Discharge
85%
EPS Safety Buffer
10%
1. Depth of Discharge in ON-Grid mode
e.g.
Max charge value 100%
Min discharge value 20%
2. Depth of Discharge in EPS (or OFF-Grid) mode, beyond
which the inverter stops supplying power to the connected
loads.
SOC% < (100 - Depth of Discharge in EPS)
e.g. Max charge value = 100%
Min discharge value = 15%
3. After reaching the minimum EPS discharge value, the
inverter resumes supplying power to the loads in EPS (or
OFF-Grid) mode once the set threshold has been exceeded
SOC%> 100 – Depth of Discharge in EPS+ safety buffer)
e.g. LOAD output re-supplying value = 26%
7.1 Check inverter settings
If the photovoltaic production is normal, but the
LOAD consumption = 0, or if the
SOC% < 100% - EPS
DOD
the excess energy will be
stored in the battery.
If PV production > LOAD consumption (
Δ
P >
100W) the HYD-ES inverter will charge the
battery.
If PV production < LOAD consumption (ΔP
>
100W) the HYD-ES inverter will discharge
the battery.
Charge
Discharge
If PV production = LOAD consumption, the
HYD-ES inverter will not charge or
discharge the battery.
Standby
19.6 EPS OPERATING MODE (OFF GRID)