Make sure that the AC circuit breaker of the
hybrid inverter is open and that no voltage is
present on the inverter's terminal block.
OFF
HYD 3-6
GRID
8888
> 200W
Check that the DC circuit breaker of the inverter is in
the OFF position.
Make sure there is a domestic load of at least 200 W by using a current
clamp to measure under the import/export meter.
Current flow
Loads
Import/Export meter
Turn on the batteries:
In case of
WeCo
batteries, press the POWER
button of each battery for 1 second, the RUN LED
will turn on and the internal contactor will close
automatically.
To turn on the
Pylontech
batteries:
bring the switch on
the front of
all the
batteries
to the ON
position.
Press the red SW button of
a single
battery for one
second, the internal
contactor will close
automatically.
12.1 INITIAL SET UP PROCEDURE
Turn ON the AC circuit breaker located between
the inverter and AC grid.
Hybrid Inverter
GRID
ON
Summary of Contents for Azzurro HYD 3000 ES
Page 1: ...QUICK INSTALLATION GUIDE HYBRID INVERTER ...
Page 24: ...23 DATASHEET ...