The procedure for blocking the current sensors is available from
version 2.00 of the Service Code onwards; in the event of lower
Service Codes, contact technical support.
Enter Pwd!
0001
Back
Increase
number
Decrease
number
Forward or
confirm
1.Advanced settings
9.CT Direction
“Password 0001”
Power read by CT
CT info
NOTE
: info for writing the password
To perform the freezing operation, follow the instructions below:
To supply DC voltage to the hybrid inverter, turn
the circuit breaker to the ON position
12.2 INITIAL SET UP PROCEDURE - FREEZING OF CURRENT SENSOR
12.3 INITIAL SET-UP PROCEDURE - PHOTOVOLTAIC START UP
Direction of power flow:
•
IMPORT → from grid to utility
•
EXPORT → from utility to grid
Phase shift between the voltage (V) and current (I)
expressed as a percentage → P/ (V x I) = cosϕ
Indicates the status of the current sensors:
•
UNFREEZE → direction not blocked (at each system start, the direction depends on the direction of the first current flow).
•
FREEZE → direction blocked (sensors keep the same direction at each start up).
After checking for the presence of a power flow towards the utility, freeze the CTs by pressing the arrow
so that the word
FREEZE
appears at the bottom and then confirm with the fourth button
To unfreeze, press the third button to display the
UNFREEZE
message and then press the third key.
Confirm. By switching the system off and on in this way, the sensor can once again be directed.