Manual of 07/06/2019 Rev. 2.1 “User Manual for 3K-6KTLM LITE
The maximum open-circuit voltage of the photovoltaic string must be less than 600 V.
The 3K-6K TLM-L series has two Maximum Power Point Trackers (MPPT); all the
photovoltaic modules connected to it must be of the same model so as to have the
same rated electrical characteristics (Isc, Voc, Im, Vm, Pm and temperature
coefficients) and be positioned in the same orientation (solar azimuth and inclination
angle).
Note
4.1.
Electrical connections
Figure 13 – Steps for connecting the cables
4.2.
Connecting PNGD cables (grounding)
Connect the 3K-6K TLM-L inverter to the ground electrode using ground protection cables (PGND).
The inverter does not have a transformer, therefore the positive pole and
negative pole of the photovoltaic string does NOT need to be grounded.
Otherwise, the inverter may fail. All non-current-carrying metal parts (such as
the PV module frame, PV rack, housing of the combiner box, and housing of the
inverter) in the PV power system must be connected to the ground.
Attention
Procedure:
1)
Remove an adequate length of the external insulation layers using a wire stripper, as shown in figure
14.
Note:
L2 is approximately 2-3 mm longer than L1
Figure 14 – Preparing the ground cable (1)
2)
Insert the exposed wires in the OT terminal and crimp them using a crimping tool, as shown in figure
15.