23
English
Integrated energy meter
PARAMETER
TEST CONDITION
MIN
TYP
MAX
UNIT
Accuracy
Line voltage, current, and power factor
+/-3
%
Integrated RDC-DD
PARAMETER
SYMBOL
MIN
TYP
MAX
UNIT
Residual DC operating current
IΔ
dc
0.006
A
Operating characteristics
RDC-DD according to IEC 62955
Making and breaking capacity
Im
500
A
Residual making and breaking
capacity
IΔm
500
A
Rated conditional short- circuit
current
Inc
3
kA
Rated conditional residual
short-circuit current
IΔc
3
kA
Upstream circuit breaker and RCD
PARAMETER
SYMBOL
MIN
TYP
MAX
UNIT
Residual operating current
IΔn
0.03
A
Rated current
In
40
A
Operating characteristics
Type A according
to IEC/EN 61008-1 / 61009-1