16
English
10. Install multiple chargers (continued)
Maximum total current 32A
Circuit breaker and RCD
type A.
Must be equal in value
on installations with
several Zaptec Go.
One circuit breaker
and RCD Type A per
Zaptec Go.
Phase rotation for
better load distribution
during 1 phase charging.
Integrated residual current
protection RDC-DD (6mA DC)
according to IEC 62955
40A
40A
40A
3 phase installation
3 phase for the chargers
N, L1, L2. L3
N, L3, L1. L2
N, L2, L3. L1
When rotating phases on a 3-phase installation, you must use the Zaptec app
to specify which incoming phase (L1, L2 or L3) is connected to the phase 1 terminal
on the charger. This can only be done via the Install Zaptec Go journey in the Zaptec app.