28
CtrL
Control mode
onoF: on-off control. For situation not requiring high precision
APId: advanced artificial intelligence PID control. (Recommended)
nPId: standard PID algorithm with anti integral-saturation function (no integral when
PV-SV > proportional band)
POP: Transmit PV. The instrument works as a temperature re-transmitter.
SOP: Transmit SV. The instrument works program generator.
onoF
APId
nPId
POP
SOP
Srun
Running Status
run: Control or program was running, “RUN” led light on
StoP
:
Control or program was stopped. Lower display keep flashing “StoP” and
“RUN” led light off.
HoLd: This only functioned on AI-526P, this will keeping temperature when this HoLd
was appeared. If the parameter Pno=0(Non timing limitation mode), controller will
functioning same at AI-526, if Pno>0 (in program mode),and Srun was set as “HoLd”,
means the timer stops and the temperature remains; user can resume the timer by
pressing the “
Hold”
from panel.
StoP /
run /
HoLd