33
16
0
~
20mA (installed I4
module in MIO)
35
0
~
10V
17
K (0
~
300.00
℃
) *
36
2
~
10V
18
J (0
~
300.00
℃
) *
37
0
~
20V
dPt
Display
Resolution
Four formats (0, 0.0, 0.00, 0.000) are selectable
Note 1: For thermocouples or RTD input, only 0 or 0.0 is selectable, and the internal
resolution is 0.1. When S type thermocouple is used, dPt is recommended to be 0. If
Inp= 17,18 or 22, resolution will support display 0.0 or 0.00
0 / 0.0 /
0.00 /
0.000
ScL
Signal scale
low limit
Define scale low limit of input. It is also the low limit of transmitter output (CtrL=POP
or SOP) and light bar display.
-9990
~
+32000
units
ScH
Signal scale
high limit
Define scale high limit of input. It is also the high limit of retransmission output
(CtrL=POP or SOP) and light bar display.
Scb
Input Shift
Adjustment
Scb is used to shift input to compensate the error caused by transducer, input signal,
or auto cold junction compensation of thermocouple.
PV after compensation=PV before compen Scb
It is generally set to 0. The incorrect setting will cause measurement inaccurate.
-1999
~
+4000
units