48
Jump:
The program can jump to any other steps in the range of 1 to 30 automatically as you programmed in the program
Step, and realize cycle control.
Run/Hold:
When program is in the running status, timer works, and set point value changes according to the preset curve. When
program is in the holding status, timer stops, and set point remains to make temperature hold also. The holding
operation can be programmed into the program step.
Stop:
When the stop operation is activated, the program will stop, running time will be clear, event output switch will reset
and the output control will stop output. If run operation is activated when instrument is in the stop status, the program
will start-up and run again from the set step no. The stop function can be programmed into the program Step. The stop
operation can also be performed manually at any time. (After stop operation is done, the step no. will be set to 1, but
user can modify it again). If the program ran the last step of “Pno”, program will stop automatically.
Power cut/resume event handling:
There are 5 events handling method selectable for power resume after power cut off. Please refer to parameter PonP.