251934-YTG-G-0708
Johnson Controls Unitary Products
73
300
(25)
208-3-60 23.0
160
31.5
3.7
28.0
10.0
None
-
-
-
151.8
175
E18
13.5
1
37.5
151.8
175
E36
27.0
2
74.9
151.8
175
E54
40.6
2
112.7
188.4
200
E72
54.1
2
150.2
197.7
200
230-3-60 23.0
160
31.5
3.7
26.0
10.0
None
-
-
-
149.3
175
E18
18.0
1
43.3
149.3
175
E36
36.0
2
86.6
153.3
175
E54
54.0
2
129.9
174.9
175
E72
72.0
2
173.2
218.2
225
460-3-60 12.2
87
17.1
1.9
13.0
5.0
None
-
-
-
77.7
90
E18
18.0
1
21.7
77.7
90
E36
36.0
2
43.3
77.7
90
E54
54.0
2
65.0
87.5
90
E72
72.0
2
86.6
109.1
110
575-3-60 8.7
62
13.5
1.5
10.3
4.0
None
-
-
-
57.7
60
E18
18.0
1
17.3
57.7
60
E36
36.0
2
34.6
61.2
70
E54
54.0
2
52.0
69.8
70
E72
72.0
2
69.3
87.2
90
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZJ180-300 - Standard Drive With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages Amps