251934-YTG-G-0708
Johnson Controls Unitary Products
65
RPM Selection
Size
(Tons)
Model
HP
Max
BHP
Motor
Sheave
Blower
Sheave
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Fully
Closed
180
(15)
ZJ/ZF
5
5.75
1VP65
BK110
815
850
885
920
950
985
N/A
5
5.75
1VP65
BK090
1010
1055
1095
1135
1180
1220
N/A
210
(17.5)
ZJ/ZF
5
5.75
1VP60
BK110
730
765
800
835
870
905
N/A
7.5
8.63
1VP60
BK090
905
950
990
1035
1075
1120
N/A
240
(20)
ZJ/ZF
5
5.75
1VP60
BK110
730
765
800
835
870
905
N/A
7.5
8.63
1VP60
BK090
905
950
990
1035
1075
1120
N/A
300
(25)
ZJ/ZF
7.5
8.63
1VP60
1B5V94
810
850
885
920
960
1000
N/A
10
11.50
1VP75X
1B5V110
975
1005
1040
1070
1100
1135
1165
15
17.25
1VP75X
1B5V94
1140
1180
1215
1255
1290
1330
1365
180
(15)
ZR
5
5.75
1VP65
BK110
815
850
885
920
950
985
N/A
7.5
8.63
1VP65
BK090
1010
1055
1095
1135
1180
1220
N/A
240
(20)
ZR
7.5
8.63
1VP60
BK110
730
765
800
835
870
905
N/A
10
11.50
1VP60
BK090
905
950
990
1035
1075
1120
N/A
300
(25)
ZR
7.5
8.63
1VP60
1B5V94
810
850
885
920
960
1000
N/A
10
11.50
1VP75X
1B5V110
975
1005
1040
1070
1100
1135
1165
15
17.25
1VP75X
1B5V94
1140
1180
1215
1255
1290
1330
1365
Additional Static Resistance
Size
(Tons)
Model
CFM
Cooling Only
1
1. Add these values to the available static resistance in the respective Blower Performance Tables.
Economizer
2
3
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the
return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Electric Heat kW
2
18
36
54
72
180
(15)
ZJ
ZR
ZF
4500
0.10
0.10
0.10
0.10
0.20
0.20
6000
0.10
0.10
0.10
0.20
0.30
0.40
7500
0.10
0.10
0.10
0.30
0.40
0.60
210 (17.5)
240 (20)
300 (25)
ZJ
ZR
ZF
6000
0.10
0.10
0.10
0.10
0.20
0.20
7500
0.10
0.10
0.10
0.20
0.30
0.40
9000
0.15
0.15
0.10
0.30
0.40
0.60
10500
0.15
0.15
0.20
0.40
0.60
0.80
12000
0.20
0.20
0.30
0.50
0.70
0.90