251934-YTG-G-0708
70
Johnson Controls Unitary Products
Electrical Data
ZJ180 - 300
ZJ180-300 - Standard Drive Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
180
(15)
208-3-60 14.7
115
23.0
2.1
15.4
0.0
None
-
-
-
86.5
100
E18
13.5
1
37.5
86.5
100
E36
27.0
2
74.9
112.9
125
E54
40.6
2
112.7
160.1
175
E72
54.1
2
150.2
169.4
200
230-3-60 14.7
115
23.0
2.1
14.4
0.0
None
-
-
-
85.3
90
E18
18.0
1
43.3
85.3
90
E36
36.0
2
86.6
126.3
150
E54
54.0
2
129.9
147.9
175
E72
72.0
2
173.2
191.2
225
460-3-60 7.7
50
12.0
1.1
7.2
0.0
None
-
-
-
44.3
50
E18
18.0
1
21.7
44.3
50
E36
36.0
2
43.3
63.1
70
E54
54.0
2
65.0
74.0
90
E72
72.0
2
86.6
95.6
110
575-3-60 6.4
40
10.0
0.9
5.9
0.0
None
-
-
-
36.7
40
E18
18.0
1
17.3
36.7
40
E36
36.0
2
34.6
50.7
60
E54
54.0
2
52.0
59.3
70
E72
72.0
2
69.3
76.7
90
210
(17.5)
208-3-60 16.7
120
26.0
2.1
15.4
0.0
None
-
-
-
94.8
110
E18
13.5
1
37.5
94.8
110
E36
27.0
2
74.9
112.9
125
E54
40.6
2
112.7
160.1
175
E72
54.1
2
150.2
169.4
200
230-3-60 16.7
120
26.0
2.1
14.4
0.0
None
-
-
-
93.8
110
E18
18.0
1
43.3
93.8
110
E36
36.0
2
86.6
126.3
150
E54
54.0
2
129.9
147.9
175
E72
72.0
2
173.2
191.2
225
460-3-60 8.7
60
15.5
1.1
7.2
0.0
None
-
-
-
48.6
50
E18
18.0
1
21.7
48.6
50
E36
36.0
2
43.3
63.1
70
E54
54.0
2
65.0
74.0
90
E72
72.0
2
86.6
95.6
110
575-3-60 6.7
42
10.5
0.9
5.9
0.0
None
-
-
-
38.0
40
E18
18.0
1
17.3
38.0
40
E36
36.0
2
34.6
50.7
60
E54
54.0
2
52.0
59.3
70
E72
72.0
2
69.3
76.7
90