251934-YTG-G-0708
24
Johnson Controls Unitary Products
115°F
125°F
5500
77
230.9
19.1
108.4
87.7
63.4
-
-
-
222.4
21.1
112.0
81.5
59.3
-
-
-
72
207.5
19.0
146.2 121.9
97.6
73.3
-
-
197.6
20.9
142.4 117.7
93.1
68.4
-
-
67
184.1
18.9
184.1 156.1 131.8 107.5
83.2
-
172.9
20.8
172.9 151.5 126.8 102.1
77.4
-
62
181.9
18.8
181.9 181.9 154.2 129.9 105.6
81.3
173.3
20.8
173.3 173.3 144.2 119.6
94.9
70.2
6000
77
232.5
19.1
124.7
92.9
67.0
-
-
-
222.3
21.1
128.9
88.9
62.6
-
-
-
72
209.0
19.0
155.1 129.1 103.1
77.1
-
-
197.5
21.0
150.8 124.5
98.2
72.0
-
-
67
185.4
18.9
185.4 165.2 139.2 113.2
87.3
-
172.7
20.8
172.7 160.1 133.8 107.6
81.3
-
62
183.3
18.9
183.3 183.3 162.8 136.9 110.9
84.9
173.2
20.8
173.2 173.2 152.3 126.0
99.7
73.4
57
181.7
18.9
181.7 181.7 163.1 137.2 111.2
85.2
173.9
20.8
173.9 173.9 154.3 128.0 101.7
75.5
6500
77
234.2
19.2
141.1
98.2
70.5
-
-
-
222.3
21.1
145.8
96.3
65.9
-
-
-
72
210.5
19.1
163.9 136.2 108.6
80.9
-
-
197.4
21.0
159.2 131.3 103.4
75.5
-
-
67
186.7
18.9
186.7 174.3 146.6 119.0
91.3
-
172.6
20.9
172.6 168.8 140.9 113.0
85.1
-
62
184.6
18.9
184.6 184.6 171.5 143.8 116.2
88.5
173.1
20.9
173.1 173.1 160.3 132.4 104.5
76.6
57
183.0
18.9
183.0 183.0 171.8 144.1 116.5
88.8
173.8
20.9
173.8 173.8 162.4 134.5 106.7
78.8
7000
77
235.9
19.2
157.4 103.4
74.1
-
-
-
222.2
21.2
162.7 103.7
69.2
-
-
-
72
212.0
19.1
172.7 143.4 114.0
84.7
-
-
197.4
21.0
167.6 138.1 108.6
79.1
-
-
67
188.1
19.0
188.1 183.4 154.0 124.7
95.3
-
172.5
20.9
172.5 172.5 147.9 118.5
89.0
-
62
185.9
19.0
185.9 185.9 180.1 150.8 121.5
92.1
173.0
20.9
173.0 173.0 168.3 138.8 109.3
79.8
57
184.3
18.9
184.3 184.3 180.5 151.1 121.8
92.4
173.8
20.9
173.8 173.8 170.6 141.1 111.6
82.1
7875
72
217.1
19.1
186.2 154.2 122.3
90.3
-
-
202.0
21.0
180.5 148.5 116.5
84.5
-
-
67
192.6
19.0
192.6 190.3 165.2 133.2 101.2
-
176.6
20.9
176.6 176.6 158.7 126.7
94.6
-
62
190.4
18.9
190.4 190.4 187.5 155.6 123.6
91.7
177.1
20.9
177.1 177.1 174.8 142.8 110.7
78.7
57
188.8
18.9
188.8 188.8 186.9 154.9 123.0
91.0
177.9
20.9
177.9 177.9 176.3 144.3 112.3
80.2
8750
72
222.3
19.1
199.7 165.1 130.5
96.0
-
-
206.7
21.0
193.5 158.9 124.4
89.8
-
-
67
197.2
19.0
197.2 197.2 176.3 141.7 107.1
-
180.6
20.9
180.6 180.6 169.4 134.9 100.3
-
62
194.9
18.9
194.9 194.9 194.9 160.4 125.8
91.2
181.2
20.9
181.2 181.2 181.2 146.7 112.1
77.6
57
193.3
18.9
193.3 193.3 193.3 158.7 124.1
89.6
182.0
20.9
182.0 182.0 182.0 147.5 112.9
78.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZJ210 (17.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65