251934-YTG-G-0708
26
Johnson Controls Unitary Products
115°F
125°F
5000
77
252.8
22.8
102.8
92.0
69.2
-
-
-
239.3
25.2
98.0
86.4
64.9
-
-
-
72
227.6
22.7
147.6 124.9 102.2
79.5
-
-
212.7
25.0
142.0 119.4
96.7
74.1
-
-
67
202.4
22.5
192.4 157.8 135.1 112.4
89.7
-
186.1
24.8
186.1 151.2 128.6 105.9
83.3
-
62
195.2
22.4
195.2 195.2 160.7 138.0 115.3
92.5
180.9
24.7
180.9 180.9 150.8 128.1 105.5
82.8
6000
77
258.7
22.8
128.0 102.1
76.1
-
-
-
244.6
25.2
127.2
97.6
71.5
-
-
-
72
232.9
22.7
164.2 138.3 112.3
86.3
-
-
217.4
25.0
158.7 132.6 106.6
80.5
-
-
67
207.1
22.6
200.4 174.5 148.5 122.5
96.6
-
190.2
24.8
190.2 167.7 141.6 115.6
89.5
-
62
199.8
22.4
199.8 199.8 176.6 150.6 124.6
98.7
184.8
24.7
184.8 184.8 166.1 140.0 114.0
87.9
57
198.9
22.5
198.9 198.9 175.3 149.3 123.3
97.3
185.2
24.8
185.2 185.2 162.8 136.7 110.7
84.6
7000
77
264.7
22.9
153.2 112.2
83.0
-
-
-
249.8
25.2
156.5 108.7
78.1
-
-
-
72
238.3
22.7
180.9 151.7 122.4
93.2
-
-
222.0
25.0
175.3 145.9 116.4
86.9
-
-
67
211.9
22.6
208.5 191.1 161.9 132.6 103.4
-
194.2
24.8
194.2 184.2 154.7 125.2
95.8
-
62
204.4
22.5
204.4 204.4 192.5 163.2 134.0 104.8
188.8
24.8
188.8 188.8 181.4 151.9 122.5
93.0
57
203.5
22.5
203.5 203.5 191.1 161.8 132.6 103.3
189.2
24.8
189.2 189.2 177.8 148.3 118.9
89.4
8000
77
270.6
22.9
178.5 122.3
89.8
-
-
-
255.1
25.2
185.7 119.9
84.7
-
-
-
72
243.6
22.8
197.5 165.0 132.5 100.0
-
-
226.7
25.0
192.0 159.1 126.2
93.3
-
-
67
216.6
22.6
216.6 207.8 175.3 142.8 110.3
-
198.3
24.8
198.3 198.3 167.8 134.9 102.0
-
62
209.0
22.5
209.0 209.0 208.4 175.9 143.4 110.9
192.7
24.8
192.7 192.7 192.7 163.9 131.0
98.1
57
208.1
22.5
208.1 208.1 206.8 174.3 141.8 109.3
193.2
24.8
193.2 193.2 192.9 160.0 127.1
94.2
8700
72
250.7
22.7
208.7 174.1 139.5 104.9
-
-
232.8
25.0
202.9 168.0 133.1
98.2
-
-
67
222.9
22.6
222.9 218.5 184.5 149.9 115.3
-
203.7
24.8
203.7 203.7 176.9 142.0 107.1
-
62
215.1
22.5
215.1 215.1 214.8 180.2 145.6 111.0
198.0
24.7
198.0 198.0 198.0 165.7 130.8
95.9
57
214.1
22.5
214.1 214.1 213.5 178.9 144.3 109.7
198.4
24.8
198.4 198.4 198.3 163.4 128.5
93.6
9400
72
257.8
22.7
219.9 183.2 146.5 109.8
-
-
239.0
25.0
213.8 176.9 140.0 103.1
-
-
67
229.2
22.6
229.2 229.2 193.7 157.0 120.3
-
209.0
24.8
209.0 209.0 186.1 149.2 112.2
-
62
221.1
22.4
221.1 221.1 221.1 184.5 147.8 111.1
203.2
24.7
203.2 203.2 203.2 167.6 130.7
93.8
57
220.2
22.5
220.2 220.2 220.2 183.5 146.8 110.1
203.7
24.8
203.7 203.7 203.7 166.8 129.9
92.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZJ240 (20 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65