251934-YTG-G-0708
78
Johnson Controls Unitary Products
ZJ300 - Low Static Drive Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
300
(25)
208-3-60 23.0
160
31.5
3.7
20.0
0.0
None
-
-
-
132.6
150
E18
13.5
1
37.5
132.6
150
E36
27.0
2
74.9
132.6
150
E54
40.6
2
112.7
165.9
175
E72
54.1
2
150.2
175.2
200
230-3-60 23.0
160
31.5
3.7
20.0
0.0
None
-
-
-
132.6
150
E18
18.0
1
43.3
132.6
150
E36
36.0
2
86.6
133.3
150
E54
54.0
2
129.9
154.9
175
E72
72.0
2
173.2
198.2
225
460-3-60 12.2
87
17.1
1.9
10.0
0.0
None
-
-
-
69.5
80
E18
18.0
1
21.7
69.5
80
E36
36.0
2
43.3
69.5
80
E54
54.0
2
65.0
77.5
90
E72
72.0
2
86.6
99.1
110
575-3-60 8.7
62
13.5
1.5
8.2
0.0
None
-
-
-
51.2
60
E18
18.0
1
17.3
51.2
60
E36
36.0
2
34.6
53.6
60
E54
54.0
2
52.0
62.2
70
E72
72.0
2
69.3
79.5
90
ZJ300 - Low Static Drive With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
300
(25)
208-3-60 23.0
160
31.5
3.7
20.0
10.0
None
-
-
-
142.6
150
E18
13.5
1
37.5
142.6
150
E36
27.0
2
74.9
142.6
150
E54
40.6
2
112.7
178.4
200
E72
54.1
2
150.2
187.7
200
230-3-60 23.0
160
31.5
3.7
20.0
10.0
None
-
-
-
142.6
150
E18
18.0
1
43.3
142.6
150
E36
36.0
2
86.6
145.8
150
E54
54.0
2
129.9
167.4
175
E72
72.0
2
173.2
210.7
225
460-3-60 12.2
87
17.1
1.9
10.0
5.0
None
-
-
-
74.5
80
E18
18.0
1
21.7
74.5
80
E36
36.0
2
43.3
74.5
80
E54
54.0
2
65.0
83.7
90
E72
72.0
2
86.6
105.4
110
575-3-60 8.7
62
13.5
1.5
8.2
4.0
None
-
-
-
55.2
60
E18
18.0
1
17.3
55.2
60
E36
36.0
2
34.6
58.6
60
E54
54.0
2
52.0
67.2
70
E72
72.0
2
69.3
84.5
90