background image

835966-UIM-E-0814

Johnson Controls Unitary Products

7

CHARGING IN HEATING MODE

If charging in heating mode, there are two methods for charging:
Weighing in the charge is the best method for ensuring the unit per-
forms as rated. However, if a device is installed in the line set that alters
the amount of refrigerant, such as a refrigerant flow meter, then the bet-
ter method for charging is to match the liquid pressure from the heating
charging chart (if available) or heating service data (available from
wwwupgnet.com). If no such device exists in the line set, then the
method is acceptable if weighing in the charge is not an option.

If servicing a unit for low heating performance and you find that you
have to add a significant amount of charge (ex: 20-30 ounces) in order
to match the published liquid pressures, the unit will NOT be over-
charged in cooling. Heat pumps are sensitive to charge in heating, but
not in cooling.

CHARGING WITH GAUGES

Do not charge a heat pump in cooling mode with gauges or charging
charts or any other method other than weighing in the charge. 

However for servicing a heat pump unit, the charging charts are an
acceptable troubleshooting method, but when the servicing is com-
pleted, the charge should be reclaimed and weighed in (to guarantee
optimal performance in heating mode). If servicing in heating mode, the
charge does not have to be reclaimed if the liquid pressures match the
published values.

Before measuring the pressures, use the method above to check the air
flow and then consult the table and match the liquid pressure to that air
flow. 

Before servicing a unit, confirm that your gauges are accurate by 
comparing the gauges against a calibrated pressure gauge that has 
been calibrated against a national standard. If a calibrated pressure 
gauge is not available, place a R-410A virgin refrigerant container in a 
conditioned space long enough to come to temperature equilibrium with 
the surroundings. Then measure the temperature of the air and the 
pressure of the refrigerant and compare it to the following table:

:

If the gauges are correct, then measure the pressures using both 
the cooling and heating charts.

SECTION VII: ELECTRICAL 

CONNECTIONS

GENERAL INFORMATION & GROUNDING

Check the electrical supply to be sure that it meets the values specified
on the unit nameplate and wiring label.

Power wiring, control (low voltage) wiring, disconnect switches and over
current protection must be supplied by the installer. Wire size should be
sized per NEC requirements.

The complete connection diagram and schematic wiring label is located
on the inside surface of the unit service access panel and this instruc-
tion.

FIELD CONNECTIONS POWER WIRING

1. Install the proper size weatherproof disconnect switch outdoors and

within sight of the unit.

2. Remove the screws at the bottom of the corner cover. Slide corner

cover down and remove from unit. See Figure 5.

3. Run power wiring from the disconnect switch to the unit.
4. Remove the service access panel to gain access to the unit wiring.

Route wires from disconnect through power wiring opening provided
and into the unit control box.

5. Install the proper size time-delay fuses or circuit breaker, and make

the power supply connections.

6. Energize the crankcase heater if equipped to save time by preheat-

ing the compressor oil while the remaining installation is completed.

Refrigerant charging should only be carried out by a qualified air con-
ditioning contractor.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

TABLE 2: 

R-410A Saturation Properties

Temp 

(°F)

Pressure 

(Psig)

Temp 

(°F)

Pressure 

(Psig)

Temp 

(°F)

Pressure 

(Psig)

40

119

75

218

110

365

45

130

80

236

115

391

50

143

85

255

120

418

55

156

90

274

125

447

60

170

95

295

130

477

65

185

100

317

70

201

105

341

All field wiring must USE COPPER CONDUCTORS ONLY and be in
accordance with Local, National Fire, Safety & Electrical Codes. This
unit must be grounded with a separate ground wire in accordance
with the above codes.

 FIGURE 5: 

Typical Field Wiring

Corner
Cover

Control
Wiring

Power
Wiring

Service
Access

Panel

Ambient
Temperature
Sensor

A0203-001

Summary of Contents for YZF

Page 1: ...ns 2 R 410A Saturation Properties 7 Defrost Initiate Curves 21 SECTION I GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units a...

Page 2: ...ficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used a...

Page 3: ...to 15 feet See Application Data Part Number 247077 for installing tubing of longer lengths and elevation differences PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possi...

Page 4: ...izing 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the vapor service port connection After this...

Page 5: ...nstall the TXV bulb to the suction line near the equalizer line using the bulb clamp s furnished with the TXV assembly kit Ensure the bulb is making maximum contact Refer to TXV kit installation instr...

Page 6: ...ular data sheet 2 Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge for refrigerant piping using the tabular data sheet if line length is greater than 15 feet 4 6 m...

Page 7: ...igerant and compare it to the following table If the gauges are correct then measure the pressures using both the cooling and heating charts SECTION VII ELECTRICAL CONNECTIONS GENERAL INFORMATION GROU...

Page 8: ...unit to the indoor unit and thermostat 6 All field wiring to be in accordance with NEC and or local city codes 7 Mount the thermostat about 5 ft above the floor where it will be exposed to normal room...

Page 9: ...nline at www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM CONFIGU RATION Typical For proper system operation the indoor CFM must be set properly Refer to the Technical Gu...

Page 10: ...or Kit Optional S1 37309243000 Change FFuel jumper on the heat pump control to ON Jumper 2 must be set to O Jumper 3 must be set to GAS Jumper 1 must be set to HEAT PUMP Setup Step 50 Dual Fuel must b...

Page 11: ...n Set setup step 26 2nd Stage Deadband and step 29 Minutes Between 1st and 2nd to 0 Bonnet Sensor Kit Optional S1 37309243000 BS Bonnet Sensor BSG Bonnet Sensor W Auxiliary Heat Y2 Second Stage Compre...

Page 12: ...W1 First Stage Heat W2 Second Stage Heat Y1 First Stage Compressor O Reversing Valve Energized In Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise EAC 24 VAC out Electronic Air Cle...

Page 13: ...e Energized In Cool Y2 OUT Second Stage Compressor W2 OUT Second Stage Heat W1 OUT First Stage Heat R 24 Volt Hot Y1 Single Stage Compressor C 24 Volt Common HUM OUT 24 VAC out Humidifier EAC 24 VAC o...

Page 14: ...Sensor BSG Bonnet Sensor W Auxiliary Y2 Second Stage Compressor X L Malfunction Light O Reversing Valve Energized in Cool Y2 OUT Second Stage Compressor R 24 Volt Hot Y1 Single Stage Compressor C 24...

Page 15: ...BS Bonnet Sensor BSG Bonnet Sensor W Auxiliary Heat Y2 Second Stage Compressor X L Malfunction Light O Reversing Valve Energized In Cool Y2 OUT Second Stage Compressor W2 OUT Second Stage Heat W1 OUT...

Page 16: ...24 Volt Common Y First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR...

Page 17: ...Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Dehumidification Open on Humidity Rise VARIABLE SPEE...

Page 18: ...Heat COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunct...

Page 19: ...ge Compressor G Fan THERMOSTAT R 24 Volt Hot W3 Third Stage Heat C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FUR...

Page 20: ...econd Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR AUX Auxiliary Heat Thermostat Installer Setup 0170 System Type must be set to 12 3...

Page 21: ...uel furnace change FUEL jumper to ON position This setting MUST be set on the defrost board 4 Set low temperature cutout LTCO balance point BP switch point SP and Y2 Lock jumpers as desired These sett...

Page 22: ...peration and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessary to kee...

Page 23: ...THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTOR...

Page 24: ...T WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING OPTIONAL WIRING FIELD...

Page 25: ...ENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING OPTIONAL WIRING FIEL...

Page 26: ...835966 UIM E 0814 26 Johnson Controls Unitary Products NOTES...

Page 27: ...ltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plen...

Page 28: ...p Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board install...

Page 29: ...plain operation of system to equipment owner Explain the importance of regular filter replacement and equipment maintenance Owner Education Provide owner with the owner s manual Explain thermostat use...

Page 30: ...change without notice Published in U S A 835966 UIM E 0814 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 835966 UIM D 0614 York International Corp 5005 York Drive Norman OK 73...

Reviews: