background image

835966-UIM-E-0814

2

Johnson Controls Unitary Products

INSPECTION

As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information.

Requirements For Installing/Servicing R-410A Equipment

Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle POE oils, and the higher pressures
of R-410A.

Manifold sets should be 800 PSIG high side and 250 PSIG low
side with 550 PSIG low side restart.

All hoses must have a 700 PSIG service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.

An R-22 TXV (thermostatic expansion valve) must not be used.

A liquid-line filter drier is required on every unit.

LIMITATIONS

The unit should be installed in accordance with all National, State and
Local Safety Codes and the limitations listed below:

1. Limitations for the indoor unit, coil and appropriate accessories must

also be observed.

2. The outdoor unit must not be installed with any duct work in the air

stream. The outdoor fan is the propeller type and is not designed to
operate against any additional external static pressure.

3. The maximum and minimum conditions for operation must be

observed to assure a system that will give maximum performance
with minimum service. Refer to the dry bulb (DB) and wet bulb (WB)
temperature limitations in Table 1.

.

4. The 2 stage units are not designed to operate with a low ambient kit.

The 2 stage models which can not operate with a low ambient kit
include YZF060, HC6B060, HL6B060, all YZH, all HC8B, and all
HL8B. Do not modify the control system of these models to operate
with any kind of low ambient kit.

5. The maximum allowable line length for this product is 75 feet.

SECTION III: UNIT INSTALLATION

LOCATION

Before starting the installation, the suitability of the locations for both the
indoor and outdoor units need to be checked. All required limitations
and clearances must be observed. The outdoor unit must have suffi-
cient clearance for air entrance to the condenser coil, for air discharge,
and for service access as shown in Figure 1.

If the unit is to be installed on a hot sun exposed roof or a paved
ground area that is seasonally hot, the unit should be raised sufficiently
above the roof or ground to avoid taking the accumulated layer of hot
air into the outdoor unit.

Provide adequate structural support.

ADD-ON REPLACEMENT/RETROFIT

When this unit is being used as a replacement for an R-22 unit, it is
required that the outdoor unit, indoor coil, and metering device all be
replaced. The following steps should be performed in order to insure
proper system operation and performance. Line-set change out is also
recommended. 

1. Change-out of the indoor coil to an approved R-410A coil/ condens-

ing unit combination with the appropriate metering device.

2. Change-out of the line-set when replacing an R-22 unit with an

R410-A unit is highly recommended to reduce cross-contamination
of oils and refrigerants. 

3. If change-out of the line set is not practical, then the following pre-

cautions should be taken.

Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.

Determine if there are any low spots in the line set which might
cause oil traps. 

Flush the line set with a commercially available flush kit to
remove as much of the existing oil and contaminants as possi-
ble. 

Install a suction line filter-drier to trap any remaining contami-
nants, and remove it after 50 hours of operation. 

4. If the outdoor unit is being replaced due to a compressor burnout,

then installation of a 100% activated alumina suction-line filter drier
in the suction-line is required, in addition to the factory installed liq-
uid-line drier. Operate the system for 10 hours. Monitor the suction
drier pressure drop. If the pressure drop exceeds 3 psig, replace
both the suction-line and liquid-line driers. After a total of 10 hours
run time where the suction-line pressure drop has not exceeded 3
psig, replace the liquid line drier, and remove the suction-line drier.
During the contamination removal procedure, never leave a suction
line drier in the system longer than 50 hours of run time.

TABLE 1: 

Maximum / Minimum Operating Limit Conditions   

AIR TEMPERATURE AT 

OUTDOOR COIL, °F

AIR TEMPERATURE AT 

INDOOR COIL, °F

Min.

Max.

Min.

Max.

DB

Cool

DB 

Heat

DB

Cool

DB 

Heat

WB 

Cool

DB 

Heat

WB 

Cool

DB 

Heat

50

-10

115

75

57

50

1

1.

72

80

1. Operation below this temperature is permissible for a short period 
    of time, during morning warm-up.

For multiple unit installations, units must be spaced a minimum of 24
inches apart. (Coil face to coil face.)

NOTICE

 FIGURE 1: 

Typical Installation with Required Clearances

THERMOSTAT

NEC CLASS 1

WIRING

TO INDOOR
BLOWER

NEC CLASS 2
WIRING

TO COIL

WEATHERPROOF

DISCONNECT

SWITCH

24” SERVICE

ACCESS

CLEARANCE

NOTE:

ALL OUTDOOR WIRING MUST BE WEATHERPROOF

SEAL OPENINGS WITH
PERMAGUM OR EQUIVALENT

60” OVERHEAD
CLEARANCE

10” CLEARANCE
AROUND PERIMETER

A0216-001

Summary of Contents for YZF

Page 1: ...ns 2 R 410A Saturation Properties 7 Defrost Initiate Curves 21 SECTION I GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units a...

Page 2: ...ficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used a...

Page 3: ...to 15 feet See Application Data Part Number 247077 for installing tubing of longer lengths and elevation differences PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possi...

Page 4: ...izing 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the vapor service port connection After this...

Page 5: ...nstall the TXV bulb to the suction line near the equalizer line using the bulb clamp s furnished with the TXV assembly kit Ensure the bulb is making maximum contact Refer to TXV kit installation instr...

Page 6: ...ular data sheet 2 Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge for refrigerant piping using the tabular data sheet if line length is greater than 15 feet 4 6 m...

Page 7: ...igerant and compare it to the following table If the gauges are correct then measure the pressures using both the cooling and heating charts SECTION VII ELECTRICAL CONNECTIONS GENERAL INFORMATION GROU...

Page 8: ...unit to the indoor unit and thermostat 6 All field wiring to be in accordance with NEC and or local city codes 7 Mount the thermostat about 5 ft above the floor where it will be exposed to normal room...

Page 9: ...nline at www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM CONFIGU RATION Typical For proper system operation the indoor CFM must be set properly Refer to the Technical Gu...

Page 10: ...or Kit Optional S1 37309243000 Change FFuel jumper on the heat pump control to ON Jumper 2 must be set to O Jumper 3 must be set to GAS Jumper 1 must be set to HEAT PUMP Setup Step 50 Dual Fuel must b...

Page 11: ...n Set setup step 26 2nd Stage Deadband and step 29 Minutes Between 1st and 2nd to 0 Bonnet Sensor Kit Optional S1 37309243000 BS Bonnet Sensor BSG Bonnet Sensor W Auxiliary Heat Y2 Second Stage Compre...

Page 12: ...W1 First Stage Heat W2 Second Stage Heat Y1 First Stage Compressor O Reversing Valve Energized In Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise EAC 24 VAC out Electronic Air Cle...

Page 13: ...e Energized In Cool Y2 OUT Second Stage Compressor W2 OUT Second Stage Heat W1 OUT First Stage Heat R 24 Volt Hot Y1 Single Stage Compressor C 24 Volt Common HUM OUT 24 VAC out Humidifier EAC 24 VAC o...

Page 14: ...Sensor BSG Bonnet Sensor W Auxiliary Y2 Second Stage Compressor X L Malfunction Light O Reversing Valve Energized in Cool Y2 OUT Second Stage Compressor R 24 Volt Hot Y1 Single Stage Compressor C 24...

Page 15: ...BS Bonnet Sensor BSG Bonnet Sensor W Auxiliary Heat Y2 Second Stage Compressor X L Malfunction Light O Reversing Valve Energized In Cool Y2 OUT Second Stage Compressor W2 OUT Second Stage Heat W1 OUT...

Page 16: ...24 Volt Common Y First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR...

Page 17: ...Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Dehumidification Open on Humidity Rise VARIABLE SPEE...

Page 18: ...Heat COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunct...

Page 19: ...ge Compressor G Fan THERMOSTAT R 24 Volt Hot W3 Third Stage Heat C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FUR...

Page 20: ...econd Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR AUX Auxiliary Heat Thermostat Installer Setup 0170 System Type must be set to 12 3...

Page 21: ...uel furnace change FUEL jumper to ON position This setting MUST be set on the defrost board 4 Set low temperature cutout LTCO balance point BP switch point SP and Y2 Lock jumpers as desired These sett...

Page 22: ...peration and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessary to kee...

Page 23: ...THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTOR...

Page 24: ...T WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING OPTIONAL WIRING FIELD...

Page 25: ...ENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING OPTIONAL WIRING FIEL...

Page 26: ...835966 UIM E 0814 26 Johnson Controls Unitary Products NOTES...

Page 27: ...ltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plen...

Page 28: ...p Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board install...

Page 29: ...plain operation of system to equipment owner Explain the importance of regular filter replacement and equipment maintenance Owner Education Provide owner with the owner s manual Explain thermostat use...

Page 30: ...change without notice Published in U S A 835966 UIM E 0814 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 835966 UIM D 0614 York International Corp 5005 York Drive Norman OK 73...

Reviews: