background image

835966-UIM-E-0814

6

Johnson Controls Unitary Products

SECTION V:  EVACUATION

During this process, it is necessary to evacuate the system to 500
microns or less. If a leak is suspected, a dry nitrogen charge is used to
locate leak(s). After repairing any leaks, another leak test is to be per-
formed.

To verify that the system has no leaks, the system is held under a vac-
uum by closing the valve to the vacuum pump suction isolating the
pump. The micron gauge is observed for a few minutes. If the micron
gauge indicates a steady and continuous rise, it is an indication of a
leak. If the gauge shows a rise, then levels off after a few minutes and
remains fairly constant above 500 microns, it is an indication that the
system is leak free but still contains moisture and may require further
evacuation. Proper system evacuation requires the micron gauge to
indicate a vacuum holding below 500 microns for several minutes. 

SECTION VI: SYSTEM CHARGE

To ensure that your unit performs at the published levels, it is important
that the indoor airflow is determined and refrigerant charge added
accordingly.

MEASURE INDOOR AIR FLOW

To determine rated air flow for a specific match, consult the technical lit-
erature at www.upgnet.com. When attempting to match this air flow,
select the lowest possible speed tap, measure the actual flow, and
adjust as necessary. 

To measure actual air flow, it is not an acceptable method to just
check the jumper pin setting tables and to assume 0.5” static pres-

sure drop.

To determine indoor air flow, first measure the static pressure with a
manometer between the filter and blower. On a single-piece air handler,
take a second reading after the coil. On a furnace or modular air han-
dler, take the second reading after the heat exchanger, but before the
indoor coil. Add the negative return static to the positive supply static to
determine the system total static pressure. Treat the negative return
static as a positive pressure (even though it is a negative reading). If
there is static pressure on the blower (i.e. -.10) return, add it to a supply
static (.40) which equals a (.50) total system static pressure. Compare
this value to the table for the indoor unit's static pressure vs. CFM or to
a curve chart.

CHARGING THE UNIT

The factory charge in the outdoor unit includes enough charge for the
unit, 15 ft. (4.6 m) of refrigerant piping, and the smallest indoor coil/air
handler match-up. Some indoor coil/air handler matches may require
additional charge. 

See Tabular Data Sheet provided in unit Customer Booklet for charge
requirements. 

The “TOTAL SYSTEM CHARGE” must be permanently marked on the
unit data plate.

TOTAL SYSTEM CHARGE DETERMINED 

1. Determine outdoor unit charge from tabular data sheet.
2. Determine indoor coil adjustment from tabular data sheet.
3. Calculate the line charge for refrigerant piping using the tabular data

sheet if line length is greater than 15 feet (4.6 m).

4. Total system charge = item 1 + item 2 + item 3.
5. Permanently stamp or mark the unit data plate with the total amount

of refrigerant in the system.

CHARGING IN COOLING MODE

The unit includes cooling charging chart. All units include a subcooling 
charging chart for cooling. If a charging chart is not on the unit, then it 
can be obtained at www.upgnet.com.

Cooling charts should not be used to charge the unit. They are ref-
erence charts for servicing the unit. 

After the unit has been serviced, collect the charge and weigh it
back in according to the directions.

When charging a unit in cooling mode, the charge MUST be weighed in.
Charging by any other method, such as superheat, subcooling, cooling
charging charts, feeling the line set, etc is not acceptable. Most heat
pumps are sensitive to charge in heating, requiring more charge, so
charging by an unacceptable method will cause the unit to perform
poorly in heating mode. 

Refrigerant charging should only be carried out by a qualified air con-
ditioning contractor.

R-410A refrigerant cylinders are rose colored, and have a dip tube
which allows liquid to flow out of the cylinder in the Upright Posi-
tion.
 Always charge the system slowly with the tank in the upright
position.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Do not leave the system open to the atmosphere. Unit damage could
occur due to moisture being absorbed by the POE oil in the system.
This type of oil is highly susceptible to moisture absorption.

DO NOT attempt to pump “Total System Charge” into outdoor unit for
maintenance, service, etc. This may cause damage to the compres-
sor and/or other components. The outdoor unit only has enough vol-
ume for the factory charge, not the “Total System Charge”.

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR,
SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS
UNIT.

This method is for systems that only have interconnecting lines. If
any other objects that adjust the charge levels are placed between
the indoor and outdoor units (example: a refrigerant flow meter), then
before adding charge, the device must first be removed. Follow the
steps above. Run the system in both cooling and heating mode and
record the high side pressure in each mode. Then insert the device
and charge the system by matching the same high side pressure in
both heating and cooling as that value recorded without the device. It
is not acceptable to add a pre-determined charge amount listed by
the device manufacturer nor is it acceptable to use any other method.

NOTICE

Summary of Contents for YZF

Page 1: ...ns 2 R 410A Saturation Properties 7 Defrost Initiate Curves 21 SECTION I GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units a...

Page 2: ...ficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used a...

Page 3: ...to 15 feet See Application Data Part Number 247077 for installing tubing of longer lengths and elevation differences PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possi...

Page 4: ...izing 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the vapor service port connection After this...

Page 5: ...nstall the TXV bulb to the suction line near the equalizer line using the bulb clamp s furnished with the TXV assembly kit Ensure the bulb is making maximum contact Refer to TXV kit installation instr...

Page 6: ...ular data sheet 2 Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge for refrigerant piping using the tabular data sheet if line length is greater than 15 feet 4 6 m...

Page 7: ...igerant and compare it to the following table If the gauges are correct then measure the pressures using both the cooling and heating charts SECTION VII ELECTRICAL CONNECTIONS GENERAL INFORMATION GROU...

Page 8: ...unit to the indoor unit and thermostat 6 All field wiring to be in accordance with NEC and or local city codes 7 Mount the thermostat about 5 ft above the floor where it will be exposed to normal room...

Page 9: ...nline at www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM CONFIGU RATION Typical For proper system operation the indoor CFM must be set properly Refer to the Technical Gu...

Page 10: ...or Kit Optional S1 37309243000 Change FFuel jumper on the heat pump control to ON Jumper 2 must be set to O Jumper 3 must be set to GAS Jumper 1 must be set to HEAT PUMP Setup Step 50 Dual Fuel must b...

Page 11: ...n Set setup step 26 2nd Stage Deadband and step 29 Minutes Between 1st and 2nd to 0 Bonnet Sensor Kit Optional S1 37309243000 BS Bonnet Sensor BSG Bonnet Sensor W Auxiliary Heat Y2 Second Stage Compre...

Page 12: ...W1 First Stage Heat W2 Second Stage Heat Y1 First Stage Compressor O Reversing Valve Energized In Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise EAC 24 VAC out Electronic Air Cle...

Page 13: ...e Energized In Cool Y2 OUT Second Stage Compressor W2 OUT Second Stage Heat W1 OUT First Stage Heat R 24 Volt Hot Y1 Single Stage Compressor C 24 Volt Common HUM OUT 24 VAC out Humidifier EAC 24 VAC o...

Page 14: ...Sensor BSG Bonnet Sensor W Auxiliary Y2 Second Stage Compressor X L Malfunction Light O Reversing Valve Energized in Cool Y2 OUT Second Stage Compressor R 24 Volt Hot Y1 Single Stage Compressor C 24...

Page 15: ...BS Bonnet Sensor BSG Bonnet Sensor W Auxiliary Heat Y2 Second Stage Compressor X L Malfunction Light O Reversing Valve Energized In Cool Y2 OUT Second Stage Compressor W2 OUT Second Stage Heat W1 OUT...

Page 16: ...24 Volt Common Y First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR...

Page 17: ...Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Dehumidification Open on Humidity Rise VARIABLE SPEE...

Page 18: ...Heat COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunct...

Page 19: ...ge Compressor G Fan THERMOSTAT R 24 Volt Hot W3 Third Stage Heat C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FUR...

Page 20: ...econd Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR AUX Auxiliary Heat Thermostat Installer Setup 0170 System Type must be set to 12 3...

Page 21: ...uel furnace change FUEL jumper to ON position This setting MUST be set on the defrost board 4 Set low temperature cutout LTCO balance point BP switch point SP and Y2 Lock jumpers as desired These sett...

Page 22: ...peration and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessary to kee...

Page 23: ...THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTOR...

Page 24: ...T WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING OPTIONAL WIRING FIELD...

Page 25: ...ENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING OPTIONAL WIRING FIEL...

Page 26: ...835966 UIM E 0814 26 Johnson Controls Unitary Products NOTES...

Page 27: ...ltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plen...

Page 28: ...p Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board install...

Page 29: ...plain operation of system to equipment owner Explain the importance of regular filter replacement and equipment maintenance Owner Education Provide owner with the owner s manual Explain thermostat use...

Page 30: ...change without notice Published in U S A 835966 UIM E 0814 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 835966 UIM D 0614 York International Corp 5005 York Drive Norman OK 73...

Reviews: