background image

835966-UIM-E-0814

Johnson Controls Unitary Products

5

10.Release the refrigerant charge into the system in accordance with

the SYSTEM CHARGE procedures. Open the liquid line base valve
first and let pressures equalize. Then, open the suction line base
valve. When opening either valve, use an appropriate hex head
wrench and back seat the base valve by turning it counter clockwise
until it stops against the chamfered retaining wall, and then turn it
back 1/8 turn. If the service valve is a ball valve, use an adjustable
end wrench to turn valve stem one-quarter turn counterclockwise to
open. Do not overturn (or the valve stem may break or become dam-
aged).

11.To prevent leaks, replace base valve caps finger tight, and then

tighten the cap an additional 1/12 turn (1/2 hex flat).

12.Replace cap on service ports. Do not remove the flare caps from the

service ports except when necessary for servicing the system. 

13. See “System Charge” section for checking and recording system

charge.

SECTION IV: INDOOR EXPANSION DEVICE

THERMOSTATIC EXPANSION VALVE 

(

TXV) INSTAL-

LATIONS

Before accomplishing the following procedures, verify the proper TXV
kit to be installed on the coil distributor. Refer to supplied Tabular Data
Sheet for proper indoor coil match up and specific TXV kit. 

For installations requiring a TXV, the following are the basic steps for
installation. For detailed instructions, refer to the Installation Instructions
accompanying the TXV kit.

Install TXV kit as follows:

1. Relieve nitrogen holding charge from the indoor coil by depressing

the Schrader valve stem located in the end of the suction line. After
nitrogen holding charge is completely discharged, cut the spundown
copper to allow installation of the suction line.

2. Slide indoor coil out of cabinet far enough to gain access to equal-

izer fitting on the suction line.

3. Before the suction line from the outdoor unit is brazed to the indoor

coil suction line, remove and discard black plastic cap from equalizer
fitting on the indoor coil suction line.

4. Loosen and remove distributor cap seal.

5. Install the TXV to the distributor assembly by hand tightening, and

then turn fitting an additional 1/4 turn to seal. 

Do not overtighten fit-

tings.

6. Install the liquid line to the top of the TXV using the liquid line fitting

which is supplied with the indoor coil. Hand modify the liquid line to
align with casing opening. Hand tighten the liquid line on the TXV,
and tighten an additional 1/4 turn to seal.

7. Install the TXV liquid equalizer line onto the equalizer fitting of the

suction line. Hand tighten the 1/4” SAE nut to the equalizer fitting,
and tighten an additional 1/3 turn to seal.

8. Install the TXV bulb to the suction line near the equalizer line, using

the bulb clamp(s) furnished with the TXV assembly kit. Ensure the
bulb is making maximum contact. Refer to TXV kit installation
instructions for view of bulb location. 

a.

Install the bulb on the suction line near the equalizer line with
the bulb horizontal to the suction line. On a suction line under
7/8” Outside Diameter (O.D.), install the bulb on top of the
line. On a suction line 7/8” O.D. or larger, install the bulb at
about the 2 or 10 o'clock position.

b.

If bulb must be installed vertically to the suction line, position
the bulb at least 16 inches (40.6 cm) from any bend and on
the opposite side of the bend plane. Positioned the bulb with
the bulb tail at the top, so that the bulb acts as a reservoir.

c.

Use thermal insulation provided to protect the bulb from the

effect of the surrounding ambient temperature. Cover the
bulb completely to insulate from air-stream.

9. Leak test system after outdoor unit is connected.

10.Slide indoor coil back into cabinet.

Do not connect manifold gauges unless trouble is suspected. Approxi-
mately 3/4 ounce of refrigerant will be lost each time a standard manifold
gauge is connected.

In all cases, mount the TXV bulb after vapor line is brazed and has
had sufficient time to cool.

Dry nitrogen should always be supplied through the tubing while it is
being brazed, because the temperature required is high enough to
cause oxidation of the copper unless an inert atmosphere is provided.
The flow of dry nitrogen should continue until the joint has cooled.
Always use a pressure regulator and safety valve to insure that only
low pressure dry nitrogen is introduced into the tubing. Only a small
flow is necessary to displace air and prevent oxidation.

All connections to be brazed are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. Soft solder is NOT to be used.

NOTICE

Do not install TXV onto distributor assembly until field supplied liquid
line is brazed onto the indoor coil liquid line and cooled.

Do not use slip joint pliers. Damage and distortion of distributor can
prevent proper seal. Use appropriate sized adjustable end wrench.

The schrader valve core from the TXV kit MUST NOT be installed in
the equalizer fitting when the TXV kit is installed. Poor system perfor-
mance or system failure could result.

Do not install TXV equalizer line onto equalizer fitting nor the TVX
bulb onto the suction vapor line until field supplied suction line is
brazed onto the indoor coil suction line and cooled.

The TXV bulb is to be installed on the suction line near the equalizer
line, using the two bulb clamps furnished with the TXV assembly kit.
The bulb is to make maximum contact. The TXV installation instruc-
tion provide an illustration of proper bulb location.

NOTICE

NOTICE

NOTICE

Summary of Contents for YZF

Page 1: ...ns 2 R 410A Saturation Properties 7 Defrost Initiate Curves 21 SECTION I GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units a...

Page 2: ...ficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used a...

Page 3: ...to 15 feet See Application Data Part Number 247077 for installing tubing of longer lengths and elevation differences PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possi...

Page 4: ...izing 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the vapor service port connection After this...

Page 5: ...nstall the TXV bulb to the suction line near the equalizer line using the bulb clamp s furnished with the TXV assembly kit Ensure the bulb is making maximum contact Refer to TXV kit installation instr...

Page 6: ...ular data sheet 2 Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge for refrigerant piping using the tabular data sheet if line length is greater than 15 feet 4 6 m...

Page 7: ...igerant and compare it to the following table If the gauges are correct then measure the pressures using both the cooling and heating charts SECTION VII ELECTRICAL CONNECTIONS GENERAL INFORMATION GROU...

Page 8: ...unit to the indoor unit and thermostat 6 All field wiring to be in accordance with NEC and or local city codes 7 Mount the thermostat about 5 ft above the floor where it will be exposed to normal room...

Page 9: ...nline at www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM CONFIGU RATION Typical For proper system operation the indoor CFM must be set properly Refer to the Technical Gu...

Page 10: ...or Kit Optional S1 37309243000 Change FFuel jumper on the heat pump control to ON Jumper 2 must be set to O Jumper 3 must be set to GAS Jumper 1 must be set to HEAT PUMP Setup Step 50 Dual Fuel must b...

Page 11: ...n Set setup step 26 2nd Stage Deadband and step 29 Minutes Between 1st and 2nd to 0 Bonnet Sensor Kit Optional S1 37309243000 BS Bonnet Sensor BSG Bonnet Sensor W Auxiliary Heat Y2 Second Stage Compre...

Page 12: ...W1 First Stage Heat W2 Second Stage Heat Y1 First Stage Compressor O Reversing Valve Energized In Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise EAC 24 VAC out Electronic Air Cle...

Page 13: ...e Energized In Cool Y2 OUT Second Stage Compressor W2 OUT Second Stage Heat W1 OUT First Stage Heat R 24 Volt Hot Y1 Single Stage Compressor C 24 Volt Common HUM OUT 24 VAC out Humidifier EAC 24 VAC o...

Page 14: ...Sensor BSG Bonnet Sensor W Auxiliary Y2 Second Stage Compressor X L Malfunction Light O Reversing Valve Energized in Cool Y2 OUT Second Stage Compressor R 24 Volt Hot Y1 Single Stage Compressor C 24...

Page 15: ...BS Bonnet Sensor BSG Bonnet Sensor W Auxiliary Heat Y2 Second Stage Compressor X L Malfunction Light O Reversing Valve Energized In Cool Y2 OUT Second Stage Compressor W2 OUT Second Stage Heat W1 OUT...

Page 16: ...24 Volt Common Y First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR...

Page 17: ...Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Dehumidification Open on Humidity Rise VARIABLE SPEE...

Page 18: ...Heat COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunct...

Page 19: ...ge Compressor G Fan THERMOSTAT R 24 Volt Hot W3 Third Stage Heat C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FUR...

Page 20: ...econd Stage Compressor G Fan PP32U70124 THERMOSTAT E Emergency Heat R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR AUX Auxiliary Heat Thermostat Installer Setup 0170 System Type must be set to 12 3...

Page 21: ...uel furnace change FUEL jumper to ON position This setting MUST be set on the defrost board 4 Set low temperature cutout LTCO balance point BP switch point SP and Y2 Lock jumpers as desired These sett...

Page 22: ...peration and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessary to kee...

Page 23: ...THERMOPLASTIC OR ITS EQUIVALENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTOR...

Page 24: ...T WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING OPTIONAL WIRING FIELD...

Page 25: ...ENT WHERE POWER SUPPLY HAS ONE 1 230 VOLT CONDUCTOR AND ONE 1 NEUTRAL CONDUCTOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING OPTIONAL WIRING FIEL...

Page 26: ...835966 UIM E 0814 26 Johnson Controls Unitary Products NOTES...

Page 27: ...ltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plen...

Page 28: ...p Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board install...

Page 29: ...plain operation of system to equipment owner Explain the importance of regular filter replacement and equipment maintenance Owner Education Provide owner with the owner s manual Explain thermostat use...

Page 30: ...change without notice Published in U S A 835966 UIM E 0814 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 835966 UIM D 0614 York International Corp 5005 York Drive Norman OK 73...

Reviews: