YORK INTERNATIONAL
60
FORM 160.55-O1 (920)
SETUP SCREEN
OVERVIEW
This screen is the top level of the general configuration
parameters. It allows programming of the time and
date, along with specifications as to how the time will
be displayed (12 or 24 hour format). In addition, the
chiller configuration, as determined by the state of the
Microboard Program Jumpers and Program Switches
is displayed. A qualified Service Technician establishes
this configuration per the desired operation. This screen
also serves as a gateway to more subscreens for defining
general system parameters
DISPLAY ONLY
031-01730-000 Microboard
Chilled Liquid Pump Operation:
Displays
Standard
or
Enhanced
Motor Type:
Displays
Fixed Speed
or
Variable Speed
Refrigerant Selection:
Displays
R-11
or
R123
Anti-Recycle:
Displays
Disabled
or
Enabled
Power Failure Restart:
Displays
Manual
or
Automatic
Liquid Type:
Displays
Water
or
Brine
Coastdown:
Displays
Standard
(150 seconds) or
Enhanced
(15
minutes – Steam Turbine applications)
Pre-Run:
Displays
Standard
(30 seconds) or
Extended
(180
seconds)
Power Line Frequency (VSD only):
Displays
60 Hz
or
50 Hz
031-02430-000 Microboard
Refrigerant Selection
Displays R11 or R123
Liquid Type
Displays Water or Brine
LD09562
FIG. 26
OptiView Control Center