YORK INTERNATIONAL
54
FORM 160.55-O1 (920)
HARMONIC FILTER DETAILS SCREEN
(STYLE D VSD AND VSD WITH PART NUMBER 371-03789-XXX
(503 HP 60 HZ; 410 HP 50 HZ
OVERVIEW
This screen displays more detailed information per-
taining to the IEEE-519 Harmonic Filter. Flash Memory
Card version C.MLM.02.04.xxx (and later) is required
for VSD part number 371-03789-xxx (503HP 60Hz;
419 HP 50Hz).
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls
is commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value. For the Variable Speed Drive
this is the data returned by the VSD Logic board.
Current Limit Setpoint
Displays the current limit value in use. This value could
come from a 0-20mA, 4-20mA, 0-10VDC or 2-10VDC
input in Analog Remote mode, PWM signal in Digital
Remote mode, MicroGateway interface in ISN mode
or a locally programmed value.
Pulldown Demand Time Left
Displays the time remaining in the programmed pull-
down period if the value is non-zero.
Operating Mode (Run / Stop)
Indicates whether the Harmonic Filter is operating.
VSD Model
Access Level Required
: SERVICE
Displays the horsepower for which the attached Har-
monic Filter is configured.
DC Bus Voltage
Displays the DC Bus voltage as measured by the Har-
monic Filter.
Supply Contactor (LED)
Indicates whether the output to the Supply Contactor
is energized.
Precharge Contactor (LED)
Indicates whether the output to the Precharge Contactor
is energized.
Phase Rotation
Displays the phase rotation detected by the Harmonic
Filter (A, B, C or C, B, A)
Total Supply kVA
Displays the total supply KiloVolt-Amps measured by
the Harmonic Filter.
00363VIP
FIG. 23