YORK SETPOINT CHANGE LOG
CHILLER ID 163
© 1997 – 2000 YORK INTERNATIONAL CORPORATION
Mon 09 Oct 2000 3:33:47 PM
Log Entry 1 Evaporator - Leaving Chilled Local Setpoint
---------------------------------------------------------------------------
Date
= 05 Oct 2001
Time
= 4:23:49 PM
Access Level
= Service
User Id
= 4268
Old Value
= 46.5 ~F
New Value
= 48.0 ~F
Log Entry 2 Condenser - High Pressure Warning Threshold
---------------------------------------------------------------------------
Date
= 05 Oct 2001
Time
= 1:36:12 PM
Access Level
= Service
User Id
= 4268
Old Value
= 162.5 Psig
New Value
= 225.0 Psig
Log Entry 3 Condenser - Drop Leg
---------------------------------------------------------------------------
Date
= 05 Oct 2001
Time
= 1:36:02 PM
Access Level
= Service
User Id
= 4268
Old Value
= Disabled
New Value
= Enabled
Log Entry 4 Evaporator - Refrigerant
---------------------------------------------------------------------------
Date
= 05 Oct 2001
Time
= 1:35:48 PM
Access Level
= Service
User Id
= 4268
Old Value
= Disabled
New Value
= Enabled
FIG. 49
– SAMPLE PRINTOUT (SECURITY LOG)
[Skip the following section if Motor Type is not VSD]
Variable Speed Drive
--------------------------------------------------------------------------
Motor Run
= Off
% Full Load Amps
= 0 %
Pre-Rotation Vanes Position
= 0 %
Full Load Amps
= 402 A
Precharge Relay Output
= Off
Trigger SCR Output
= Off
Water Pump Output
= Off
KW Hours
= 14528 KWH
Input Power
= 150 KW
Output Frequency
= 0 Hz
Output Voltage
= 800 V
DC Bus Voltage
= 600 V
DC Inverter Link Current
= 300 A
Phase A Output Current
= 0 A
Phase B Output Current
= 0 A
Phase C Output Current
= 0 A
Internal Ambient Temperature
= 88 ~F
Converter Heatsink Temperature
= 102 ~F
Phase A Heatsink Temperature
= 93 ~F
Phase B Heatsink Temperature
= 99 ~F
Phase C Heatsink Temperature
= 97 ~F
[Skip the following section if Motor Type is not VSD,
or
Filter is not
present]
Harmonic Filter Data
--------------------------------------------------------------------------
Precharge Contactor
= Off
Supply Contactor
= Off
Operating Mode
= Stopped
Phase Rotation
= ABC
Total Supply KVA
= 148 KVA
Total Power Factor
= 0.97
DC Bus Voltage
= 608 V
Heatsink Temperature
= 102 ~F
Voltage Peak N-L1
= 200 V
Voltage Peak N-L2
= 200 V
Voltage Peak N-L3
= 200 V
L1-L2 RMS Voltage
= 215 V
L2-L3 RMS Voltage
= 215 V
L3-L1 RMS Voltage
= 215 V
L1 RMS Filter Current
= 150 A
L2 RMS Filter Current
= 150 A
L3 RMS Filter Current
= 150 A
L1 RMS Supply Current
= 152 A
L2 RMS Supply Current
= 152 A
L3 RMS Supply Current
= 152 A
L1 Voltage Total Harmonic Distortion
= 1.5 %
L2 Voltage Total Harmonic Distortion
= 1.2 %
L3 Voltage Total Harmonic Distortion
= 1.1 %
L1 Supply Current Total Demand Distortion = 2.6 %
L2 Supply Current Total Demand Distortion = 2.3 %