YORK INTERNATIONAL
22
FORM 160.55-O1 (920)
CONDENSER SCREEN
OVERVIEW
This screen displays a cutaway view of the chiller
condenser. All setpoints relating to the condenser side
of the chiller are maintained on this screen. Animation
indicates condenser liquid flow. This screen also serves
as a gateway to controlling the Refrigerant Level.
DISPLAY ONLY
Leaving Condenser Liquid Temperature
Displays the water temperature as it leaves the condenser.
Return Condenser Liquid Temperature
Displays the water temperature as it enters the con-
denser.
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Condenser Saturation Temperature
Displays the saturation temperature in the condenser.
Small Temperature Difference
Displays the difference between the Condenser Refrig
-
erant temperature and the Leaving Condenser Liquid
temperature. The Condenser Refrigerant temperature
will be represented by the Condenser Saturation tem-
perature.
Drop Leg Refrigerant Temperature
Displays the temperature of the refrigerant in the drop
leg between the condenser and evaporator shells, if the
sensor is present.
Sub-Cooling Temperature
Displays the difference between the Condenser Refrig
-
erant temperature and the Drop Leg Refrigerant tem-
perature. The Condenser Refrigerant temperature will
be represented by the Condenser Saturation temperature.
If the Drop Leg sensor is not present, this temperature
is not displayed.
High Pressure Switch (Open / Closed)
Displays the present position of the high pressure switch.
This will indicate whether a High Pressure fault is pres-
ent.
Condenser Liquid Flow Switch
Indicates whether flow is present in the condenser.
Condenser Liquid Pump (Run / Stop)
Indicates whether Condenser liquid pump is operat-
ing.
Refrigerant Level Position
Displays the present position of the refrigerant level if
this function is enabled.
00350VIP0
FIG. 7
OptiView Control Center