COMPETENT PERSONS TROUBLE SHOOTING GUIDE
PROBLEM
POSSIBLE CAUSE
ACTION
No display on panel - Unit will not
operate
Main supply to unit off
Switch on main supply if safe to do so.
Emergency stop device off
Check if remote emergency stop device
is in the OFF position. Turn to ON
position if safe to do so.
No supply to -T1
Check fuses -F3 and -F6 and wiring to
-T1 and fuse -F1.
No 24 VAC supply to microprocessor
board.
Check wiring from -T1 to J14
microprocessor board.
No 24 VAC output from Transformer -T1. Change transformer -T1.
Short circuit in wiring to temperature
sensors or pressure transducers.
Unplug connections at microprocessor
board to isolate.
Defective microprocessor board or
display board.
Replace board after contacting Johnson
Controls Service.
FLOW SWITCH OPEN
displayed
No liquid flow through the liquid heat
exchanger.
Ensure that liquid pumps are running.
Valves are correctly set and flow is
established.
Flow switch contacts are not made.
Check that the flow switch is functional
and is installed according to the
manufactures instructions.
NOTE:
On some systems the pump
starter may be wired to the unit and
controlled to start by the unit.
Detective flow switch.
Replace flow switch.
UNIT FAULT: LOW AMBIENT TEMP
displayed in either mode or
HIGH AMBIENT TEMP
displayed in
heating mode
Ambient air temperature is lower than
the programmed operating limit or, in
heating mode, higher than the trip value.
(Refer to
Operating Manual (Form
150.68-O2.EN.GB
)
Use the OPER DATA key to display
the temperature and confirm that the
displayed value is correct. The warning
message should clear when the
ambient air temperature reaches the
programmed operating limit. Check that
the programmed settings are correct for
the options fitted to the unit.
Measured temperature is incorrect.
Check sensor calibration, location and
wiring.
UNIT FAULT: LOW LIQUID TEMP
displayed
Improperly adjusted leaving chilled liquid
temperature cut-out (glycol only).
Re-program the leaving chilled liquid
temperature cut-out.
Control panel setpoint/range values
improperly programmed.
Re-adjust setpoint/range.
Chilled liquid flow too low.
Increase chilled liquid flow.
Defective -BLCT sensor. (Check that the
sensor is properly installed in the bottom
of the well with a generous amount of
heat conductive compound).
Compare sensor against a reliable
temperature sensing device.
See the
Sensor Calibration Charts.
UNIT FAULT: 115 VAC
UNDERVOLTAGE
displayed
Poor mains supply voltage.
Check mains supply is stable and within
allowable limits.
Check for voltage dip on compressor
start.
Summary of Contents for YLPA 0115SE
Page 4: ...4 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 10: ...10 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 16: ...16 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 26: ...26 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 30: ...30 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 72: ...72 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 79: ...79 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 YLPA P I Diagram ...
Page 86: ...86 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 88: ...88 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...