BACnet and Modbus Communications
Chiller data that can be read and modified using spe-
cific BACnet or Modbus Register Addresses; and the
data associated with the addresses, is outlined below:
Analog Write Points
This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1025 + AV #.
Binary Write Points
This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1537 + BV #.
Analog Read Only Points
This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 513 + AI #.
Binary Monitor Only Points
This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 1281 + BI #.
See Table 4 on page 59 for complete list of BACnet
and Modbus registers.
The latest data map information is listed
on the Johnson Controls Equipment In-
tegration website.
Communications Data Map Notes
For information on Data Maps see
1.
IPU II based units are configured for Native BAC
-
net MS/TP and Modbus RTU communications.
Microgateway or E-Link not required for these
two communication protocols.
2. BACnet Object Types:
0 = Analog In
1 = Analog Out
2 = Analog Value
3 = Binary In
4 = Binary Output
5 = Binary Value
8 = Device
15 = Alarm Notifica-
tion (0
through
127
are reserved ASHRAE
Objects).
3.
WC= Inches of water
column
CFM = Cubic Feet per
Minute
FPM = Feet per Minute
PSI = Lbs per square
inch
Pa = Pascals
kPa = Kilopascals
PPM = Part per Mil-
lion
kJ/kg = Kilojoules per
Kilogram.
4.
Water Cooled Scroll units use the same firmware
as Air Cooled Scroll units, ignoring Fan Control.
Summary of Contents for YLPA 0115SE
Page 4: ...4 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 10: ...10 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 16: ...16 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 26: ...26 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 30: ...30 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 72: ...72 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 79: ...79 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 YLPA P I Diagram ...
Page 86: ...86 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Page 88: ...88 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...