JOHNSON CONTROLS
130
FORM 155.33-ICOM2.EN.GB
ISSUE DATE: 12/4/2017
SECTION 8 – TROUBLESHOOTING
FIGURE 45 -
TROUBLESHOOTING SEQUENCE FLOW CHART
Chiller-heater
operating
Alarm buzzer
ON
Dilution starts
Failure lamp lit
No
Yes
No
Yes
EG input stops
Temperature control with
HW three-way valve stops
Solution pumps and
refrigerant pump stop
Chilled / hot water and
cooling water pump
stop
Minimum dilution
time passed?
Air conditional machine
and cooling tower stop
HEX temp.
≤
dilution completion
temp?
No
Failure alarm?
No
Yes
Yes
Failure without
dilution? (see note)
NOTE:
See
mation on when the chiller-heater stops without the
dilution cycle being run.
Press BUZZER STOP
Button
External output signal
failure lamp lights.