SECTION 5 - COMMISSIONING
JOHNSON CONTROLS
7
FORM 155.31-CL1
ISSUE DATE: 11/20/2017
EXHAUST GAS ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (2/2)
User:
Model: YHAU
MFG. No.:
User's machine code:
Running Data
Date:
Measured by
Specification
Standard
:
:
:
Exhaust
Gas
Inlet damper position
%
Damper indicator
Outlet damper position
%
Damper indicator
Bypass damper position
%
Control panel
Inlet temperature
°C
Thermometer
Outlet temperature
°C
Thermometer
Inlet pressure
Pressure Gauge
Outlet pressure
Pressure gauge
Pressure drop
DPG or Calculation
Waste Hot
Water
Inlet temperature
°C
Control panel
Outlet temperature
°C
Control panel
Inlet pressure
Pressure gauge
Outlet pressure
Pressure gauge
[11] Pressure drop
DPG or calculation [12]
[9] Flow rate
FM or calculation
[10]
Chilled/hot
Water
Inlet temperature
°C
Control panel
Outlet temperature
°C
Control panel
Inlet pressure
Pressure gauge
Outlet pressure
Pressure gauge
[3] Pressure drop
DPG or Calculation [4]
[1] Flow rate
FM or Calculation
[2]
Cooling
Water
Inlet temperature
°C
Control panel
20.0~32.0°C
Outlet temperature
°C
Control panel
20.0~37.5°C
Inlet pressure
Pressure gauge
Outlet pressure
Pressure gauge
[7] Pressure drop
DPG or Calculation
[8]
[5] Flow rate
FM or Calculation
[6]
Absorption
Cycle
XG pressure (Gauge)
MPa.G
Compound gauge
≤ -0.003 MPa
XG pressure (Sensor)
kPa.abs
Control panel
≤ 94.7 kPa
XG temperature
°C
Control panel
≤165°C
HT-HEX temperature
°C
Control panel
Absorber temperature
°C
Control panel
Refrigerant temperature
°C
Control panel
Liquid
Level
XG
Level gauge
LG
Level gauge
Absorber
Level gauge
Evaporator (Lower)
Level gauge
Evaporator (Upper)
Level gauge