10. EMS / BAS INTERFACE CARD KITS
FIG. 21 – EMS / BAS OPTION
10.1 EMS-PWM REMOTE TEMPERATURE RESET
EMS-PWM Remote Temperature Reset is a value that
resets the Chilled Liquid Setpoint based on a PWM in-
put (timed contact closure) to the microboard. This
PWM input would typically be supplied by an Energy
Management System.
A contact closure on the PWM Temp Reset input at
CTB 1 terminals 13 - 20, will reset the chilled liquid
setpoint based on the length of time the contacts re-
main closed. The maximum temperature reset is
achieved at a contact closure of 11 seconds. This is the
longest contact closure time allowed. One second is the
shortest time allowed and causes the Chilled Liquid
Setpoint to revert back to the Local programmed value.
The reset value is always added to the Chilled Liquid
Setpoint, meaning that this function never lowers the
Chilled Liquid Setpoint below the locally programmed
value, it can only reset to a higher value. The micro-
board must be refreshed between 30 seconds and 30
minutes. Any contact closure occurring sooner than 30
seconds will be ignored. If more than 30 minutes elapse
before the next contact closure, the setpoint will revert
back to the locally programmed value. The new chilled
liquid setpoint is calculated by the following equations:
setpoint = local chilled liquid se °reset
°reset = (Contact Closure - 1) x (*Max. Reset Value)
10
Example:
Local Chilled Liquid Setpoint = 45°F (7.22°C).
*Max Reset Value = 10°F (5.56°C)
Contact Closure Time = 6 Seconds.
(English)
(6 sec. - 1) (10°F/10) = 5°F Reset
So...the new chilled liquid setpoint = 45°F + 5°F= 50°F.
This can be viewed by pressing the Cooling Setpoints
key twice. The new value will be displayed as “REM SETP
= 50.0°F.”
(Metric)
(6 sec - 1) * (5.56°C/10) = 2.78°C
Reset Cooling Setpoint = 7.22°C + 2.78°C = 10.0°C
So...the new reset Cooling Setpoint = 7.22 °C + 2.78°C =
10°C. This can be viewed by pressing the Cooling Setpoints
key twice. The new value will be displayed as “REM SETP
= 10.0°C.”
10.2 BAS/EMS TEMPERATURE RESET OPTION
The Remote Reset Option allows the Control Center of
the unit to reset the chilled liquid setpoint using a 0 - 10
VDC input, a 4-20mA input, or a contact closure input.
The Remote Reset circuit board converts the signals
mentioned above into pulse width modulated (PWM)
signals which the microprocessor can understand. When-
ever a reset is called for, the change may be noted by
pressing the Cooling Setpoints key twice. The new value
will be displayed as “REM SETP = XXX°F”
* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” setpoint value described in the programming section under Cooling
Setpoints. Programmable values are from 2°F to 40°F (1.11°C to 22.22°C).
7
Summary of Contents for YCWS0313SC
Page 12: ...YORK INTERNATIONAL 12 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT...
Page 36: ...YORK INTERNATIONAL 36 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT Commissioning...
Page 86: ...YORK INTERNATIONAL 86 TYPICAL CONTROL PANEL WIRING Maintenance...
Page 87: ...FORM 201 24 NM2 87 YORK INTERNATIONAL TYPICAL CONTROL PANEL WIRING LD06957 8...
Page 103: ...FORM 201 24 NM2 103 YORK INTERNATIONAL NOTES 11...