SECTION 8 – UNIT OPERATION
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
8
TB3
TB1
TB2
TO PANEL 10M
TO FAN #2 (EXIS TING HARNESS)
TO MICROBOARD (P7)
251
250
252
250A
251A
252A
WHT
BLK
TB3
TB1
TB2
TO PANEL 10M
TO FAN #2 (EXIS TING HARNESS)
TO MICROBOARD (P7)
251
250
252
250A
251A
252A
WHT
BLK
TB3
TB1
TB2
TO PANEL 7M
TO FAN #1 (EXIS TING HARNESS)
TO MICROBOARD (P4)
151
150
152
150A
151A
152A
WHT
BLK
TB3
TB1
TB2
TB3
TB1
TB2
TO PANEL 7M
TO FAN #1 (EXIS TING HARNESS)
TO MICROBOARD (P4)
151
150
152
150A
151A
152A
WHT
BLK
FIGURE 58 -
INVERTER WIRING
LD11302
TABLE 28 -
YCAL0043-0066 VFD LOW AMBIENT OPTION – CONDENSER FAN CONTROL OPERATION
FAN STAGE
ON
OFF
CONTACTOR
MICROBOARD
FAN #
SYS 1
SYS 2
SYS 1
SYS 2
SYS 1
SYS 2
1:
VFD CONTROL
(1 FAN
VARIABLE
SPEED)
FAN SPEED
IS A FUNCTION
OF
DISCHARGE
PRESSURE.
WHEN THE
LIQUID LINE
SOLENOID IS
ENERGIZED,
SPEED
INCREASES
WITH PRESSURE
FAN WILL
TURN OFF OR
TURN VERY
SLOWLY WHEN
PRESSURE
DROPS BELOW
260 PSIG.
7M
10M
TB7-3
TB10-9
1
2
2:
1 FAN VFD
CONTROL
2ND FAN
FULL SPEED
UNDER
CONTACTOR
CONTROL
425 PSIG,
BOTH FANS
WILL BE
RUNNING FULL
SPEED
DISCHARGE
PRESSURE
< 260 PSIG
(PRESSURE IS
< FAN CONTROL
ON PRESSURE
OF
425 PSIG
MINUS FAN
DIFFERENTIAL
PRESSURE OF
125 PSIG = 300
PSIG)
7M
&
8M
10M
&
11M
TB7-3
AND
TB7-10
TB10-9
AND
TB10-
10
1
&
3
2
&
4
Summary of Contents for YCAL0019
Page 4: ...JOHNSON CONTROLS 4 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 69: ...69 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 71: ...71 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 229: ...229 JOHNSON CONTROLS SECTION 10 MAINTENANCE FORM 150 67 NM1 ISSUE DATE 4 28 2017 NOTES...