SECTION 5 – TECHNICAL DATA
It is possible that multiple sources of power can be supplying the unit power panel. To pre-
vent serious injury or death, the technician should verify that NO LETHAL VOLTAGES
are present inside the panel AFTER disconnecting power, PRIOR to working on equipment.
The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at
or below freezing temperatures, can result in damage to the evaporator and unit as a result
of the chilled liquid freezing.
ELECTRICAL DATA
TABLE 8 -
MICRO PANEL POWER SUPPLY
VOLTAGE RANGE
VOLTAGE CODE
UNIT POWER
MINIMUM
MAXIMUM
-17
200-3-60
180
220
-28
230-3-60
207
253
-40
380/415-3-60
342
440
-46
460-3-60
414
506
-50
380/415-3-50
342
440
-58
575-3-60
517
633
UNIT VOLTAGE
UNIT
VOLTAGE
CONTROL
POWER
MCA
NOTE A
OVER CURRENT PROTECTION,
SEE NOTE B
NF DISC SW
MINIMUM
MAXIMUM
MODELS W/O
CONTROL
TRANS
115-1-60/50
15A
10A
15A
30 A / 240V
MODELS W/
CONTROL
TRANS
-17
200-1-60
15A
10A
15A
30 A / 240V
-28
230-1-60
15A
10A
15A
30 A / 240V
-40
380-1-60
15A
10A
15A
30 A / 480V
-46
460-1-60
15A
10A
15A
30 A / 480V
-50
380/415-1-60
15A
10A
15A
30A / 415V
-58
575-1-60
15A
10A
15A
30 A / 600V
A. Minimum #14 AWG, 75 °C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
TABLE 9 -
VOLTAGE RANGE
Summary of Contents for YCAL0019
Page 4: ...JOHNSON CONTROLS 4 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 69: ...69 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 71: ...71 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 229: ...229 JOHNSON CONTROLS SECTION 10 MAINTENANCE FORM 150 67 NM1 ISSUE DATE 4 28 2017 NOTES...