JOHNSON CONTROLS
56
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
SECTION 5 – TECHNICAL DATA
Single-Point Field Supplied Power Wiring (See Figure 12)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused
Disconnect Switch (optional) or Circuit Breaker (optional)).
ELECTRICAL DATA (ENGLISH)
YCAL0019_ – YCAL0066_ (CON’T.)
(Without Pump)
TABLE 7 –
ELECTRICAL DATA (ENGLISH) (CONT.)
MODEL
YCAL
VOLT
60 Hz MCA
1
MIN N/F
DISC
MDSW
2
D.E. FUSE CKT. BKR.
5
FIELD WIRING LUGS
6
TERMINAL BLOCK (std)
FIELD WIRING LUGS
6
NF DISC. SWITCH (opt)
FIELD WIRING LUGS
6
CIRCUIT BREAKER (opt)
MIN. MAX
4
MIN. MAX LUGS/
PHASE LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
0056
200 268 400 300 300 300 300
1
6 AWG – 350 kcmil 2
*(2) 3/0 – 250 kcmil
2
*(2) 3/0 – 250 kcmil
230 267 400 300 300 300 300
1
6 AWG – 350 kcmil 2
*(2) 3/0 – 250 kcmil
2
*(2) 3/0 – 250 kcmil
380 171 200 200 200 200 200
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
460 130 150 150 150 150 150
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
575 112 150 125 125 125 125
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
0066
200 324 400 350 400 350 400
1
4 AWG – 500 kcmil 1 250 kcmil – 500 kcmil
1
250 kcmil – 500 kcmil
230 301 400 350 350 350 350
1
4 AWG – 500 kcmil 1 250 kcmil – 500 kcmil
1
250 kcmil – 500 kcmil
380 175 200 200 200 200 200
1
6 AWG – 350 kcmil 1
6 AWG – 350 kcmil
1
6 AWG – 350MCM
460 143 200 175 175 175 175
1
6 AWG – 350 kcmil 1
6 AWG – 350 kcmil
1
6 AWG – 350MCM
575 115 150 125 125 125 125
1
6 AWG – 350 kcmil 1
6 AWG – 350 kcmil
1
6 AWG – 350MCM
* Panels will have (3) 250 KEMIL lug kit shipped loose to accommodate larger wire size if needed.
Summary of Contents for YCAL0019
Page 4: ...JOHNSON CONTROLS 4 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 69: ...69 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 71: ...71 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 229: ...229 JOHNSON CONTROLS SECTION 10 MAINTENANCE FORM 150 67 NM1 ISSUE DATE 4 28 2017 NOTES...