Johnson Controls Ducted Systems
XA-15, XA-20 - Standard Drive With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat
(Field Installed Accessory Only)
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages Amps
-15
(15)
208-3-60 25
164
39
4.1
13.5
10
NONE
-
-
-
88
110
E18
13.5
1
37.5
134.8
150
E36
27
2
74.9
134.8
150
E54
40.6
2
112.7
170.2
175
E72
54.1
2
150.2
181.6
200
230-3-60 25
164
39
3.9
13
10
NONE
-
-
-
87.1
110
E18
18
1
43.3
141.2
150
E36
36
2
86.6
141.2
150
E54
54
2
129.9
158.7
175
E72
72
2
173.2
202
225
460-3-60 12.2
100
19
2.15
6.5
5
NONE
-
-
-
43.3
50
E18
18
1
21.7
70.3
80
E36
36
2
43.3
70.3
80
E54
54
2
65
79.3
90
E72
72
2
86.6
101
110
575-3-60
9
78
14
1.6
5.2
4
NONE
-
-
-
32.7
40
E18
18
1
17.3
54.3
60
E36
36
2
34.6
54.8
60
E54
54
2
52
63.5
70
E72
72
2
69.3
80.8
90
-20
(20)
208-3-60 34.3
239
52
3.4
20
20
NONE
-
-
-
120.8
150
E18
13.5
1
37.5
167.7
175
E36
27
2
74.9
167.7
175
E54
40.6
2
112.7
178.4
200
E72
54.1
2
150.2
214.4
225
230-3-60
3.4
19.4
20
NONE
-
-
-
120.2
150
E18
18
1
43.3
174.3
175
E36
36
2
86.6
174.3
175
E54
54
2
129.9
174.3
175
E72
72
2
173.2
228.5
250
460-3-60 17.9
125
28
1.8
9.7
20
NONE
-
-
-
62.2
80
E18
18
1
21.7
89.3
100
E36
36
2
43.3
89.3
100
E54
54
2
65
89.3
100
E72
72
2
86.6
116.3
125
575-3-60 12.8
80
20
1.4
7.8
20
NONE
-
-
-
46.2
50
E18
18
1
17.3
67.8
70
E36
36
2
34.6
67.8
70
E54
54
2
52
67.8
70
E72
72
2
69.3
89.5
90