background image

HEATING SYSTEM

The following sequence describes the operation of the gas heat
section.

CONTINUOUS BLOWER: With the room thermostat switch set
to “ON”, the supply air blower will operate continuously. The
normally closed contact “K5-1" provides 24 volt power to the
"3M" relay. The “3M-1” and "3M-2" power contacts close and
the blower motor operates.

INTERMITTENT BLOWER: With the room thermostat system
switch set to the “AUTO” or “HEAT” position and the fan switch
set to “AUTO”, the supply air blower will operate after the room
thermostat calls for heat and the time delay relay closes.

The “TH1" closes, the draft motor relay ”DMR" is energized.
The “DMR” power contact closes which energizes the line
voltage draft motor. As the speed of the draft motor reaches
approximately 2500 RPM, the centrifugal switch contact
located on the end of the draft motor shaft closes to power the
ignition control “IC”.

After 15 seconds, the "IC" will start the ignitor sparking and will
open the redundant valve located inside the main gas valve
“GV” to allow a flow of gas to only the carryover tube. See
Figure 11. Only after the pilot flame has been ignited and the
presence of pilot flame detected at the “IC” by a signal sent
back through the flame sensor is sparking terminated and the
main gas valve opened.

Gas flows into each of the main burners and is ignited from the
carryover tube flame.

If “IC” fails to detect a pilot flame, it will continue to try for a
maximum of 85 seconds to ignite the pilot tube. If the pilot flame
is not detected, then “IC” will soft lock out for 5 minutes. If the
pilot flame is not detected after 16 retries, then "IC" will hard
lock out the first stage furnace operation until 24V power is
removed from the module either at the unit or by resetting the
room thermostat.

At the same time power was supplied to the “DMR”, a parallel
circuit activates "TDR" which closes "TDR" after approximately
16 seconds and energizes "K5" which closes "K5-2" and starts
the blower by energizing "3M".

When "TH2" closes calling for second stage heating, it
energizes "W2" on the gas valve "GV" directly.

When the heating cycle is complete, “TH-1" opens
de-energizing the ”DMR" and “IC”, thus closing the redundant
and main gas valves. The blower motor continues to run
(approximately 15 seconds after the furnace is shut down) until
“TDR” opens de-energizing the “K5" and ”3M" relays.

SAFETY CONTROLS

The control circuit includes the following safety controls:

1. Limit Control (LS). This control is located inside the heat

exchanger compartment and is set to open at the
temperature indicated in Table 9. It resets automatically.
The limit switch operates when a high temperature
condition, caused by inadequate supply air flow occurs,
thus shutting down the ignition control and closing the main
gas valve and energizing the blower.

2. Centrifugal Switch (CS). If the draft motor should fail, the

centrifugal switch attached to the shaft of the motor
prevents the ignition control and gas valve from being
energized.

3. Redundant Gas Valve. This valve is an integral part of the

main gas valve and is located up stream of the main gas
valve. Should the main gas valve fail in the open position
the redundant valve serves as a back up and shuts off the
flow of gas.

4. Flame Sensor Rod. This sensor rod is located on the far

side of the carryover tube. If the ignition control does not
receive a signal from the flame sensor indicating that the
pilot flame has ignited properly, the main gas valve will not
open. If the flame sensor fails to detect the pilot flame during
operation of the main burners, a signal is sent to the ignition
control to close the main gas valve.

5. Rollout Switch. This switch is located in the burner

vestibule. In the event of a sustained main burner flame
rollout, it shuts off the ignition control and closes the main
gas valve.

HEAT ANTICIPATOR SETPOINTS

It is important that the anticipator setpoint be correct. Too high
of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter “ON” cycles
and may result in the lowering of the temperture within the
conditioned space.

PRE-START CHECK LIST

Complete the following checks before starting the unit.

1. Check the type of gas being supplied. Be sure that it is the

same as listed on the unit nameplate.

2. Make sure that the vent and combustion air hoods have

been properly installed.

Units

(Tons)

Capacity, MBH

Limit Control

Opens, 

°

F

Input

Output

7-1/2
7-1/2

10 & 12-1/2
10 & 12-1/2

163
204
204
245

130
163
163
198

180
170
170
170

TABLE 9 - LIMIT CONTROL SETTING

GAS
VALVE

GAS MAIN

MAIN VALVE

TO MAIN
BURNER

REDUNDANT
VALVE

TO PILOT BURNER

FIG. 11 - GAS VALVE PIPING

Gas Valve

Anticipator Setpoint

1st Stage

2nd Stage

Honeywell

VR8520

0.50 amp

0.24 amp

White-Rodgers

36C76

0.60 amp

0.10 amp

530.22-N4Y

12

Unitary Products Group

Summary of Contents for SUNLINE PLUS D1EG090

Page 1: ... Manual for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York Pa 17405 APPROVALS Design certified by U L as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 For installation on combustible material 4 For use with n...

Page 2: ...ES No Description Page 1 Unit Application Data 3 2 Gas Heat Application Data 5 3 Pipe Sizing 5 4 Physical Data 8 5 Supply Air Blower Performance 10 6 Accessory Static Resistances 11 7 Blower Motor and Drive Data 11 8 Electrical Data 11 9 Limit Control Setting 12 10 Blower Motor Pulley Adjustment 14 11 Gas Rate Cubic Feet Per Hour 15 FIGURES No Description Page 1 Center of Gravity 3 2 Barometric Re...

Page 3: ...S DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY Units may also be moved or lifted with a forklift Slotted openings in the base rails are provided for this purpose LENGTH OF FORKS MUST BE A MINIMUM OF 54 Remove the nesting brackets from the four corners on top of the unit All screws that are removed when taking these brackets off must be replaced on the unit CAUTION An adhesive back...

Page 4: ...s provided by the following removable panels Compressor compartment Burner compartment Two panels Blower compartment Main control box Filter compartment Refer to Figure 10 for location of these access panels CAUTION Make sure that all screws are replaced on the unit to maintain an air tight seal THERMOSTAT The room thermostat should be located on an inside wall approximately 56 above the floor whe...

Page 5: ...ode Z223 1 should be followed in all cases unless superseded by local codes or gas company requirements Refer to Table 3 The heating value of the gas may differ with locality The value should be checked with the local gas utility NOTE There may be a local gas utility requirement specifying a minimum diameter for gas piping All units require a 1 2 or 3 4 inch pipe connection at the gas valve GAS CO...

Page 6: ...per gas pressure depends on three main factors 1 The vaporization rate which depends on a the temperature of the liquid and b the wetted surface area of the container or containers 2 The proper pressure regulation Two stage regulation is recommended from the standpoint of both cost and effi ciency 3 The pressure drop in the lines between regulators and between the second stage regualtor and the ap...

Page 7: ... using 6 gasketed screws in each side plate 4 Secure the flange on the hood cover to the duct panel with 3 screws Use holes in the cover flange as a template and drill 3 holes 9 64 dia 26 drill into the duct panel 5 Insert two 2 1 filters into the center of the hood coming to rest in the center filter support at the back of the hood Press filters up against the filter guide angles on the side plat...

Page 8: ...OR COIL ROWS DEEP 4 3 4 FINS PER INCH 15 15 15 FACE AREA Sq Ft 7 8 10 9 13 4 OUTDOOR FAN Two Per Unit PROPELLER DIA in 24 ea 24 ea 24 ea FAN MOTOR HP 1 2 ea 1 2 ea 3 4 ea NOM CFM TOTAL 2900 ea 3600 ea 4400 ea CONDENSER COIL ROWS DEEP 3 2 3 FINS PER INCH 13 18 13 FACE AREA Sq Ft 16 7 24 0 29 3 AIR FILTERS SEE NOTE QUANTITY PER UNIT 12 X 24 X 2 2 QUANTITY PER UNIT 16 X 24 X 2 2 2 3 QUANTITY PER UNIT...

Page 9: ...CONDENSER COIL DETAIL X SIDE SUPPLY AND RETURN AIR OPENINGS CLEARANCES Front 24 Back 12 Less Economizer 36 With Economizer Left Side Filter Access 24 Less Economizer 54 With Economizer Right Side Cond Coil 24 Below Unit1 20 Above Unit2 72 with 36 maximum Horizontal Overhang For Condenser Air Discharge 1 Locate unit so that the vent air outlet hood is at least Three 3 feet above any forced air inle...

Page 10: ... 39 1 80 1 68 0 02 2 05 1 91 915 1 10 1 55 1 45 0 87 1 76 1 64 0 57 1 98 1 85 0 21 2 23 2 08 950 1 29 1 68 1 57 1 06 1 91 1 78 0 77 2 14 2 00 0 40 2 43 2 27 0 04 2 72 2 54 1000 1 47 1 83 1 71 1 26 2 07 1 93 0 97 2 33 2 17 0 63 2 62 2 45 0 29 2 91 2 72 1050 1 67 1 98 1 84 1 47 2 25 2 10 1 19 2 55 2 37 0 84 2 86 2 67 0 49 3 17 2 96 1090 1 86 2 12 1 97 1 66 2 41 2 24 1 40 2 72 2 54 1 04 3 06 2 86 MOD...

Page 11: ...loss of refrigerant charge If either one of the above safety controls opens that individual refrigerant system will be locked out The other refrigerant system will continue in operation unless it too is effected by the same fault The lock out of either system can be reset by opening the 24V circuit either at the room thermostat or at the unit disconnect OPERATION TABLE 6 ACCESSORY STATIC RESISTANC...

Page 12: ...nd 3M relays SAFETY CONTROLS The control circuit includes the following safety controls 1 Limit Control LS This control is located inside the heat exchanger compartment and is set to open at the temperature indicated in Table 9 It resets automatically The limit switch operates when a high temperature condition caused by inadequate supply air flow occurs thus shutting down the ignition control and ...

Page 13: ...r adjusting screw on the automatic gas valve Refer to Figure 12 Adjust as follows 1 Remove the cap on the regulator It s located next to the push on electrical terminals 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure turn the adjusting screw clockwise NOTE The correct manifold pressure for these furnaces is 4 1 IWG 0 3 PILOT CHECKOUT The pil...

Page 14: ...The tubes must be inserted and held in a position perpendicular to the air flow so that velocity pres sure will not affect the static pressure readings 3 Using an inclined manometer determine the pressure drop across a dry indoor coil Since the moisture on an indoor coil may vary greatly measuring the pressure drop across a wet coil under field conditions would be inaccurate To assure a dry coil t...

Page 15: ...al input is not within 5 of the furnace rating with allowance being made for the permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality contact your gas company for this information it varies widely from city to ...

Page 16: ... applied along top of the burner COMBUSTION AIR DISCHARGE Visually inspect discharge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain adequate combustion air discharge CLEANING FLUE PASSAGES AND HEATING ELEMENTS With proper combustion adjustment the heating element of a gas fired furnace will seldom need cleaning If the element shou...

Page 17: ...position a The draft motor has inherent protection If the motor shell is hot to the touch wait for the internal overload to reset b If the motor shell is cold with the room thermostat calling for heat check for line voltage at the motor s Mate N Lok connector attached to the evaporator partition If line voltage is present replace the draft motor c If line voltage is not present check for line volt...

Page 18: ...he pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level with respect to one another 9 Main burners light but exhibit erratic flame characteristics a Adjust air shutters as described in BURNER AIR SHUTTERADJUSTMENT b Check the main burner orifices for obstruction and alignment Removal p...

Page 19: ...530 22 N4Y Unitary Products Group 19 ...

Page 20: ...e SBY 530 22 N4Y Unitary Products Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rights Reserved ...

Reviews: