FIG. 3 - TYPICAL FIELD WIRING
NEUTRAL
3-PHASE 4 WIRE
NEUTRAL CONNECTION ON
NEUTRAL TERMINAL BLOCK
SIZE POWER WIRING,
DISCONNECT SWITCH, AND
FUSING PER ELECTRICAL DATA
TABLE
Unit
Size
(MBH)
Compressor
Condenser Fan Motor
Total
Unit
Ampacity
(Amps)
Max.
Fuse
Size
1
(Amps)
Power
Supply
RLA
LRA
Power
Supply
HP (kW)
Each
Qty.
FLA
Each
090
380/415-3-50
17.3
111
220/240-1-50
3/4 (.56)
1
2.9
22.3
30
120
380/415-3-50
19.6
118
220/240-1-50
1/2 (.37)
2
2.1
26.2
35
1
Dual element.
2
Based on three, 60
°
C insulated copper conductors in steel conduit.
TABLE 3 - ELECTRICAL DATA