@ 380/415 Volts - Side Duct Connections

TABLE 4 - SUPPLY AIR BLOWER PERFORMANCE 

MODEL

DCG

AIR FLOW

M

3

/S

Available External Static Pressure - Pa*

50

74

99

124

149

174

198

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

060

1.18

1059

1560

1077

1590

1095

1630

1114

1650

1134

1660

1158

1685

-

-

1.13

1032

1405

1054

1470

1074

1525

1094

1560

1116

1595

1140

1620

1167

1640

1.08

1005

1260

1024

1275

1049

1370

1069

1440

1090

1475

1116

1505

1142

1535

1.04

980

1160

1002

1170

1022

1190

1044

1250

1066

1350

1090

1410

1117

1440

0.99

930

1060

957

1070

983

1080

1010

1100

1039

1160

1064

1260

1092

1340

0.94

877

950

908

975

941

1000

976

1020

1009

1050

1040

1100

1070

1225

0.90

-

-

-

-

894

885

940

940

980

980

1014

1020

1047

1095

0.85

-

-

-

-

855

815

903

860

950

905

988

940

1022

970

0.80

-

-

-

-

-

-

884

815

925

850

964

880

1001

910

0.75

-

-

-

-

-

-

864

770

908

805

948

835

987

870

0.71

-

-

-

-

-

-

-

-

882

740

926

780

965

830

MODEL

DCG

AIR FLOW

M

3

/S

Available External Static Pressure - Pa*

223

248

273

298

322

347

372

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

060

1.18

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1.13

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1.08

1170

1580

-

-

-

-

-

-

-

-

-

-

-

-

1.04

1148

1480

1180

1530

-

-

-

-

-

-

-

-

-

-

0.99

1121

1385

1155

1425

-

-

-

-

-

-

-

-

-

-

0.94

1100

1285

1133

1340

1169

1385

-

-

-

-

-

-

-

-

0.90

1079

1180

1110

1240

1143

1280

1178

1330

-

-

-

-

-

-

0.85

1058

1060

1090

1135

1122

1190

1158

1240

-

-

-

-

-

-

0.80

1035

960

1071

1030

1103

1100

1134

1140

1164

1175

-

-

-

-

0.75

1020

900

1056

965

1088

1035

1118

1065

1145

1105

1170

1130

-

-

0.71

1004

860

1038

880

1070

925

1101

980

1130

1045

1158

1075

-

-

*

INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 25mm (1in. ) FILTERS, AND GAS-FIRED HEAT EXCHANGERS. 

MODEL

DCG

AIR FLOW

M

3

/S

Available External Static Pressure - Pa*

50

74

99

124

149

174

198

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

076

1.50

1150

2325

1182

2425

-

-

-

-

-

-

-

-

-

-

1.42

1100

2010

1129

2090

1157

2150

1185

2225

-

-

-

-

-

-

132

1045

1700

1074

1780

1102

1850

1131

1940

1160

2025

1190

2075

-

-

1.23

985

1425

1015

1475

1045

1540

1075

1630

1103

1715

1135

1760

1163

1825

1.13

930

1240

958

1300

990

1350

1020

1400

1051

1430

1081

1490

1111

1600

1.04

-

-

905

1070

933

1160

965

1210

997

1250

1028

1285

1060

1325

0.94

-

-

-

-

-

-

919

1025

950

1100

982

1130

1014

1160

0.85

-

-

-

-

-

-

-

-

909

925

939

1005

968

1030

MODEL

DCG

AIR FLOW

M

3

/S

Available External Static Pressure - Pa*

223

248

273

298

322

347

372

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

076

1.50

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1.42

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1.32

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1.23

1193

1920

-

-

-

-

-

-

-

-

-

-

-

-

1.13

1142

1675

1173

1730

-

-

-

-

-

-

-

-

-

-

1.04

1090

1380

1124

1450

1155

1550

1186

1640

-

-

-

-

-

-

0.94

1045

1175

1077

1200

1109

1275

1140

1360

1170

1460

-

-

-

-

0.85

998

1050

1028

1060

1058

1060

1087

1075

1118

1150

1148

1250

1176

1360

*

INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 25mm (1") FILTERS, AND GAS-FIRED HEAT EXCHANGERS. 

D*CE060 & 076 w/Belt-Drive Blower

M

3

/S

Continued on next page

530.26-N1YI

10

Unitary Products Group

Summary of Contents for SUNLINE 2000 D3CE 036

Page 1: ...V Fixed Outdoor Air Damper Accessory 530 18 N1 6V Motorized Outdoor Air Damper Accy 530 18 N1 8V Coil Guard 530 18 N7 1V Electric Heater Accessory 530 18 N7 2V Fuse Block Accessory Renewal Parts Refer to Parts Manual for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Bo...

Page 2: ...3 2 Physical Data 4 3 Blower Perf 036 048 w Direct Drive 9 4 Blower Perf 060 076 w Belt Drive 10 5 Static Resistances 12 6 Motor and Drive Data Belt Drive 12 7 Electrical Data Basic Unit 12 8 Heat Anticipator Setting 13 9 Motor Pulley Adjustment 13 FIGURES No Description Page 1 Center of Gravity 3 2 Recommended Drain Piping 4 3 Economizer Rain Hood Assembly 5 4 Typical Field Wiring 6 5 Dimensions ...

Page 3: ...ur corners on top of the unit All screws that are removed when taking these brackets off must be replaced on the unit Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity CLEARANCES All units require certain clearances for proper operation and service Refer to Figure 5 for the clearances required for combustible construction servicing and proper unit operation WARNIN...

Page 4: ...uit fed directly from the meter panel and properly protected CAUTION When connecting electrical power and control wiring to the unit waterproof type connectors MUST BE USED so that water or moisture can not be drawn into the unit during normal opera tion The above waterproofing conditions will also apply when installing a field supplied discon nect switch Refer to Figure 4 for typical field wiring...

Page 5: ... hole E in hood flange and tighten Attach the two side plates to the unit panel by using two self drilling screws for each side plate at dimples D provided in the panel 6 Position fillpiece at bottom of hood between the two side plates but do not secure at this time Slotted openings MUST be downward for drainage After fillpiece is properly positioned note where contact is made with the unit panel ...

Page 6: ...OMPRESSOR AND THE ECONOMIZER IF YOU WANT TO CONTROL THE ECONOMIZER ON A SECOND STAGE OF COOLING OR HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT USE THERMOSTAT 2TH04701024 OR 2TH04701524 WITH SUBBASE 2TB04700224 OR 2TB04700324 COOLING HEATING 24 VOLT THERMOSTAT 24 VOLT TRANSFORMER UNIT TERMINAL STRIP TB1 THERMOSTAT1 TERMINALS ADD JUMPER ADD JUMPER 4 2 3 4 NOT USED TO REMOTE SENSOR 2TH047...

Page 7: ...Knockouts in the bottom of the unit can be located by the slice in the insulation Do not remove the 2 knockout ring UTILITIES ENTRY DATA FILTER ACCESS ELECTRIC HEAT ACCESS B POWER WIRING ENTRY A B WIRING ENTRY See Detail B OUTDOOR COIL A CONTROL WIRING ENTRY 3 4 PVC FEMALE COND DRAIN See Detail A BOTTOM SUPPLY RETURN AIR OPENINGS SEE NOTE 829 325 8 445 171 2 292 111 2 200 77 8 171 63 4 206 81 8 21...

Page 8: ...tending into the supply air chamber The heaters are wired for a single point power supply Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper portion of the unit control box Fuses are supplied where required by the factory Some KW sizes require fuses and others do not Refer to the accessory instruction ...

Page 9: ...0 048 HI 0 94 960 0 91 936 0 88 910 0 85 880 0 81 845 MED 0 85 838 0 83 810 0 80 785 0 78 765 0 75 735 LOW 0 79 760 0 77 738 0 76 715 0 73 695 0 70 670 M3 S TABLE 3 SUPPLY AIR PERFORMANCE MODEL DCE MOTOR SPEED Available External Static Pressure Pa 174 198 223 248 m3 s Watts m3 s Watts m3 s Watts m3 s Watts 036 HI 0 67 725 0 64 700 0 60 680 0 56 655 MED 0 62 650 0 59 630 0 59 610 0 52 590 LOW 0 59 ...

Page 10: ...0 0 80 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 0 75 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 0 71 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL 25mm 1in FILTERS AND GAS FIRED HEAT EXCHANGERS MODEL DCG AIR FLOW M3 S Available External Static Pressure Pa 50 74 99 124 149 174 198 RPM Watts RPM Watts RPM Watts RPM Watts ...

Page 11: ...00 990 1350 1020 1400 1051 1430 1081 1490 1111 1600 2200 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325 2000 919 1025 950 1100 982 1130 1014 1160 1800 909 925 939 1005 968 1030 MODEL DCG AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 076 3200 3000 2800 2600 1193 1920 2400 1142 167...

Page 12: ...6 0 30 Electric Heaters1 5 15 KW 0 04 0 05 0 06 0 07 0 08 0 10 0 12 0 14 0 16 0 19 0 22 20 30 KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 Bottom Duct Connections1 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 0 19 0 22 Cooling Only2 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32 1 Deduct these resistance values from the available external static pressure shown in the Blower Pe...

Page 13: ...ncer 1S or contactor 2M maintains control of the evaporator blower c The thermostat cycles the electric heat to satisfy the heating requirements of the conditioned space CONTINUOUS BLOWER Continuous blower operation is possible by closing the R to G circuit on the thermostat HEAT ANTICIPATOR SETPOINTS It is important that the anticipator setpoint be correct Too high a setting results in longer hea...

Page 14: ... NOMINAL M3 S 0 38 0 52 0 66 0 80 0 94 1 08 1 23 PRESSURE DROP PA FIG 7 PRESSURE DROP ACROSS A DRY EVAPORATOR COIL VS SUPPLY AIRFLOW SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show him the location of all disconnect switches and the thermostat Teach him how to start and stop the unit and how to adjust tem perature settings within the limitations of ...

Page 15: ...530 26 N1YI Unitary Products Group 15 ...

Page 16: ...P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1994 All Rights Reserved 530 26 N1YI ...

Reviews: