background image

DISCONNECT SWITCH BRACKET
FOR UNITS WITH BELT-DRIVE BLOWER

A special bracket for mounting a field-supplied disconnect
switch is provided in each unit ordered with an optional
belt-drive supply air blower. The bracket is shipped inside the
blower compartment taped to the top of the blower housing.

Install the bracket on the left hand side of the unit as shown in
Figure 5. Several existing screws at the top of the unit and one
screw approximately midway down from the top will be used
for mounting the bracket. Screws should be loosened only -
NOT REMOVED. Matching holes in the bracket have
elongated keyways allowing easy installation. Re-tighten
screws after bracket is in place to ensure panels will remain
leak tight.

FIG. 4 - TYPICAL FIELD WIRING

CONTROL WIRING

24 VOLT

TRANSFORMER

UNIT TERMINAL

STRIP TB1

THERMOSTAT

1

TERMINALS

1

 24 VOLT THERMOSTAT 2TH08701024. IF THE UNIT HAS AN ECONOMIZER,

  REMOVE JUMPER J1 FROM TERMINALS 8 AND 10 ON THE RELAY BOARD
  TO PREVENT SIMULTANEOUS OPERATION OF THE COMPRESSOR AND
  THE ECONOMIZER. IF YOU WANT TO CONTROL THE ECONOMIZER ON A
  SECOND STAGE OF COOLING, USE THERMOSTAT 2TH04701224.

COOLING ONLY (24 VOLT THERMOSTAT)

THERMOSTAT

1

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

ADD
JUMPER

1

 24 VOLT THERMOSTAT 2TH07701024. IF THE UNIT HAS AN ECONOMIZER,

  REMOVE JUMPER J1 FROM TERMINALS 8 AND 10 ON THE RELAY BOARD
  TO PREVENT SIMULTANEOUS OPERATION OF THE COMPRESSOR AND
  THE ECONOMIZER. IF YOU WANT TO CONTROL THE ECONOMIZER ON A
  SECOND STAGE OF COOLING OR HAVE AN ELECTRIC HEAT ACCESSORY
  WITH TWO STAGES OF HEAT, USE THERMOSTAT 2TH04701024 OR
  2TH04701524 (WITH SUBBASE 2TB04700224 OR 2TB04700324).

COOLING / HEATING (24 VOLT THERMOSTAT)

24 VOLT

TRANSFORMER

UNIT TERMINAL

STRIP TB1

THERMOSTAT

1

TERMINALS

ADD
JUMPER

ADD
JUMPER

4

2

3

4

NOT
USED

TO REMOTE SENSOR
2TH04702224 IF USED

1

 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE)

   TO CONTROL ECONOMIZER ON SECOND STAGE OF COOLING, REMOVE JUMPER
   J1 FROM TERMINALS 8 AND 10 ON THE RELAY BOARD.

2

 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.

3

 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE

   ELECTRIC HEATER.

4

 REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR

   P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
  OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
  THERMOSTAT SWITCHES TO THE SET-BACK POSITION.

COOLING / HEATING (ELECTRONIC THERMOSTAT)

24 VOLT

TRANSFORMER

THERMOSTAT

1

TERMINALS

ADD
JUMPER

UNIT TERMINAL

STRIP TB1

1

 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).

  IF THIS UNIT HAS AN ECONOMIZER, REMOVE JUMPER J1 FROM TERMINALS 8 AND
  10 ON THE RELAY BOARD TO PREVENT SIMULTANEOUS OPERATION OF THE
  COMPRESSOR AND THE ECONOMIZER. IF YOU WANT TO CONTROL THE
  ECONOMIZER ON A SECOND STAGE OF COOLING, USE THERMOSTAT 2ET04700224.

COOLING / HEATING (ELECTRONIC THERMOSTAT)

THREE
PHASE
POWER
SUPPLY

FIELD-SUPPLIED

DISCONNECT

GROUND LUG

CONTACTOR

NEUTRAL

TERMINAL

BLOCK

POWER WIRING

530.26-N1YI

6

Unitary Products Group

Summary of Contents for SUNLINE 2000 D3CE 036

Page 1: ...V Fixed Outdoor Air Damper Accessory 530 18 N1 6V Motorized Outdoor Air Damper Accy 530 18 N1 8V Coil Guard 530 18 N7 1V Electric Heater Accessory 530 18 N7 2V Fuse Block Accessory Renewal Parts Refer to Parts Manual for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Bo...

Page 2: ...3 2 Physical Data 4 3 Blower Perf 036 048 w Direct Drive 9 4 Blower Perf 060 076 w Belt Drive 10 5 Static Resistances 12 6 Motor and Drive Data Belt Drive 12 7 Electrical Data Basic Unit 12 8 Heat Anticipator Setting 13 9 Motor Pulley Adjustment 13 FIGURES No Description Page 1 Center of Gravity 3 2 Recommended Drain Piping 4 3 Economizer Rain Hood Assembly 5 4 Typical Field Wiring 6 5 Dimensions ...

Page 3: ...ur corners on top of the unit All screws that are removed when taking these brackets off must be replaced on the unit Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity CLEARANCES All units require certain clearances for proper operation and service Refer to Figure 5 for the clearances required for combustible construction servicing and proper unit operation WARNIN...

Page 4: ...uit fed directly from the meter panel and properly protected CAUTION When connecting electrical power and control wiring to the unit waterproof type connectors MUST BE USED so that water or moisture can not be drawn into the unit during normal opera tion The above waterproofing conditions will also apply when installing a field supplied discon nect switch Refer to Figure 4 for typical field wiring...

Page 5: ... hole E in hood flange and tighten Attach the two side plates to the unit panel by using two self drilling screws for each side plate at dimples D provided in the panel 6 Position fillpiece at bottom of hood between the two side plates but do not secure at this time Slotted openings MUST be downward for drainage After fillpiece is properly positioned note where contact is made with the unit panel ...

Page 6: ...OMPRESSOR AND THE ECONOMIZER IF YOU WANT TO CONTROL THE ECONOMIZER ON A SECOND STAGE OF COOLING OR HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT USE THERMOSTAT 2TH04701024 OR 2TH04701524 WITH SUBBASE 2TB04700224 OR 2TB04700324 COOLING HEATING 24 VOLT THERMOSTAT 24 VOLT TRANSFORMER UNIT TERMINAL STRIP TB1 THERMOSTAT1 TERMINALS ADD JUMPER ADD JUMPER 4 2 3 4 NOT USED TO REMOTE SENSOR 2TH047...

Page 7: ...Knockouts in the bottom of the unit can be located by the slice in the insulation Do not remove the 2 knockout ring UTILITIES ENTRY DATA FILTER ACCESS ELECTRIC HEAT ACCESS B POWER WIRING ENTRY A B WIRING ENTRY See Detail B OUTDOOR COIL A CONTROL WIRING ENTRY 3 4 PVC FEMALE COND DRAIN See Detail A BOTTOM SUPPLY RETURN AIR OPENINGS SEE NOTE 829 325 8 445 171 2 292 111 2 200 77 8 171 63 4 206 81 8 21...

Page 8: ...tending into the supply air chamber The heaters are wired for a single point power supply Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper portion of the unit control box Fuses are supplied where required by the factory Some KW sizes require fuses and others do not Refer to the accessory instruction ...

Page 9: ...0 048 HI 0 94 960 0 91 936 0 88 910 0 85 880 0 81 845 MED 0 85 838 0 83 810 0 80 785 0 78 765 0 75 735 LOW 0 79 760 0 77 738 0 76 715 0 73 695 0 70 670 M3 S TABLE 3 SUPPLY AIR PERFORMANCE MODEL DCE MOTOR SPEED Available External Static Pressure Pa 174 198 223 248 m3 s Watts m3 s Watts m3 s Watts m3 s Watts 036 HI 0 67 725 0 64 700 0 60 680 0 56 655 MED 0 62 650 0 59 630 0 59 610 0 52 590 LOW 0 59 ...

Page 10: ...0 0 80 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 0 75 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 0 71 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL 25mm 1in FILTERS AND GAS FIRED HEAT EXCHANGERS MODEL DCG AIR FLOW M3 S Available External Static Pressure Pa 50 74 99 124 149 174 198 RPM Watts RPM Watts RPM Watts RPM Watts ...

Page 11: ...00 990 1350 1020 1400 1051 1430 1081 1490 1111 1600 2200 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325 2000 919 1025 950 1100 982 1130 1014 1160 1800 909 925 939 1005 968 1030 MODEL DCG AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 076 3200 3000 2800 2600 1193 1920 2400 1142 167...

Page 12: ...6 0 30 Electric Heaters1 5 15 KW 0 04 0 05 0 06 0 07 0 08 0 10 0 12 0 14 0 16 0 19 0 22 20 30 KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 Bottom Duct Connections1 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 0 19 0 22 Cooling Only2 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32 1 Deduct these resistance values from the available external static pressure shown in the Blower Pe...

Page 13: ...ncer 1S or contactor 2M maintains control of the evaporator blower c The thermostat cycles the electric heat to satisfy the heating requirements of the conditioned space CONTINUOUS BLOWER Continuous blower operation is possible by closing the R to G circuit on the thermostat HEAT ANTICIPATOR SETPOINTS It is important that the anticipator setpoint be correct Too high a setting results in longer hea...

Page 14: ... NOMINAL M3 S 0 38 0 52 0 66 0 80 0 94 1 08 1 23 PRESSURE DROP PA FIG 7 PRESSURE DROP ACROSS A DRY EVAPORATOR COIL VS SUPPLY AIRFLOW SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show him the location of all disconnect switches and the thermostat Teach him how to start and stop the unit and how to adjust tem perature settings within the limitations of ...

Page 15: ...530 26 N1YI Unitary Products Group 15 ...

Page 16: ...P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1994 All Rights Reserved 530 26 N1YI ...

Reviews: