background image

NOTE: The tubes must be inserted and held in a position

perpendicular to the air flow so that velocity pres-
sure does not affect the static pressure readings.

3. Using an inclined manometer, determine the pressure drop

across a dry indoor coil. Since the moisture on an indoor
coil may vary greatly, measuring the pressure drop across
a wet coil under field conditions would be inaccurate. To
assure a dry coil, the compressors should be de-energized
while the test is being run.

4. Knowing the pressure drop across a dry coil, the actual

airflow through the unit can be determined from the curve
in Figure 7.

WARNING: Failure to properly adjust the total system air quan-

tity can result in poor system performance.

After readings have been obtained, remove the tubes and
replace the dot plugs in the side panels. Eight millimeter (5/16")
dot plugs (P/N 029-13880) are available through normal parts
ordering procedures.

NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE

TAKING ANY TEST MEASUREMENTS TO ASSURE
A DRY INDOOR COIL.

0.6

0.4

8

11

14

17

20

23

26

DCE036

0.5

0.3

0.2

0.1

0.0

DCE048

DCE060,076

NOMINAL CFM (HUNDREDS)

PR

ESSUR

E

 D

R

OP

 (IWG

)

149

124

 99

 74

 50

 25

    0

NOMINAL M

3

/S

0.38

0.52

0.66

0.80

0.94

1.08

1.23

PR

ESSUR

E

 D

R

OP

 (P

A)

FIG. 7 - PRESSURE DROP ACROSS A DRY

EVAPORATOR COIL VS SUPPLY AIRFLOW

SECURE OWNER’S APPROVAL

When the system is functioning properly, secure the owner’s approval. Show him

the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust tem-
perature settings within the limitations of the system.

MAINTENANCE

NORMAL MAINTENANCE

WARNING: Prior to any of the following maintenance proce-

dures, shut off all power to the unit to prevent
personal injury.

FILTERS - Inspect once a month. Replace disposable or clean
permanent type as necessary. DO NOT replace permanent
type with disposable filters.

MOTORS - Indoor fan and outdoor fan motors are permanently
lubricated and require no maintenance.

OUTDOOR COIL - Dirt should not be allowed to accumulate
on the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep coil clean.
Use a brush, vacuum cleaner attachment, or other suitable
means. If water is used to clean coil, be sure power to the unit
is shut off prior to cleaning.

NOTE: Exercise care when cleaning the coil so that the coil

fins are not damaged.

Do not permit the outdoor air discharge to be obstructed by
overhanging structures or shrubs.

530.26-N1YI

14

Unitary Products Group

Summary of Contents for SUNLINE 2000 D3CE 036

Page 1: ...V Fixed Outdoor Air Damper Accessory 530 18 N1 6V Motorized Outdoor Air Damper Accy 530 18 N1 8V Coil Guard 530 18 N7 1V Electric Heater Accessory 530 18 N7 2V Fuse Block Accessory Renewal Parts Refer to Parts Manual for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Bo...

Page 2: ...3 2 Physical Data 4 3 Blower Perf 036 048 w Direct Drive 9 4 Blower Perf 060 076 w Belt Drive 10 5 Static Resistances 12 6 Motor and Drive Data Belt Drive 12 7 Electrical Data Basic Unit 12 8 Heat Anticipator Setting 13 9 Motor Pulley Adjustment 13 FIGURES No Description Page 1 Center of Gravity 3 2 Recommended Drain Piping 4 3 Economizer Rain Hood Assembly 5 4 Typical Field Wiring 6 5 Dimensions ...

Page 3: ...ur corners on top of the unit All screws that are removed when taking these brackets off must be replaced on the unit Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity CLEARANCES All units require certain clearances for proper operation and service Refer to Figure 5 for the clearances required for combustible construction servicing and proper unit operation WARNIN...

Page 4: ...uit fed directly from the meter panel and properly protected CAUTION When connecting electrical power and control wiring to the unit waterproof type connectors MUST BE USED so that water or moisture can not be drawn into the unit during normal opera tion The above waterproofing conditions will also apply when installing a field supplied discon nect switch Refer to Figure 4 for typical field wiring...

Page 5: ... hole E in hood flange and tighten Attach the two side plates to the unit panel by using two self drilling screws for each side plate at dimples D provided in the panel 6 Position fillpiece at bottom of hood between the two side plates but do not secure at this time Slotted openings MUST be downward for drainage After fillpiece is properly positioned note where contact is made with the unit panel ...

Page 6: ...OMPRESSOR AND THE ECONOMIZER IF YOU WANT TO CONTROL THE ECONOMIZER ON A SECOND STAGE OF COOLING OR HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT USE THERMOSTAT 2TH04701024 OR 2TH04701524 WITH SUBBASE 2TB04700224 OR 2TB04700324 COOLING HEATING 24 VOLT THERMOSTAT 24 VOLT TRANSFORMER UNIT TERMINAL STRIP TB1 THERMOSTAT1 TERMINALS ADD JUMPER ADD JUMPER 4 2 3 4 NOT USED TO REMOTE SENSOR 2TH047...

Page 7: ...Knockouts in the bottom of the unit can be located by the slice in the insulation Do not remove the 2 knockout ring UTILITIES ENTRY DATA FILTER ACCESS ELECTRIC HEAT ACCESS B POWER WIRING ENTRY A B WIRING ENTRY See Detail B OUTDOOR COIL A CONTROL WIRING ENTRY 3 4 PVC FEMALE COND DRAIN See Detail A BOTTOM SUPPLY RETURN AIR OPENINGS SEE NOTE 829 325 8 445 171 2 292 111 2 200 77 8 171 63 4 206 81 8 21...

Page 8: ...tending into the supply air chamber The heaters are wired for a single point power supply Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper portion of the unit control box Fuses are supplied where required by the factory Some KW sizes require fuses and others do not Refer to the accessory instruction ...

Page 9: ...0 048 HI 0 94 960 0 91 936 0 88 910 0 85 880 0 81 845 MED 0 85 838 0 83 810 0 80 785 0 78 765 0 75 735 LOW 0 79 760 0 77 738 0 76 715 0 73 695 0 70 670 M3 S TABLE 3 SUPPLY AIR PERFORMANCE MODEL DCE MOTOR SPEED Available External Static Pressure Pa 174 198 223 248 m3 s Watts m3 s Watts m3 s Watts m3 s Watts 036 HI 0 67 725 0 64 700 0 60 680 0 56 655 MED 0 62 650 0 59 630 0 59 610 0 52 590 LOW 0 59 ...

Page 10: ...0 0 80 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 0 75 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 0 71 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL 25mm 1in FILTERS AND GAS FIRED HEAT EXCHANGERS MODEL DCG AIR FLOW M3 S Available External Static Pressure Pa 50 74 99 124 149 174 198 RPM Watts RPM Watts RPM Watts RPM Watts ...

Page 11: ...00 990 1350 1020 1400 1051 1430 1081 1490 1111 1600 2200 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325 2000 919 1025 950 1100 982 1130 1014 1160 1800 909 925 939 1005 968 1030 MODEL DCG AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 076 3200 3000 2800 2600 1193 1920 2400 1142 167...

Page 12: ...6 0 30 Electric Heaters1 5 15 KW 0 04 0 05 0 06 0 07 0 08 0 10 0 12 0 14 0 16 0 19 0 22 20 30 KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 Bottom Duct Connections1 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 0 19 0 22 Cooling Only2 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32 1 Deduct these resistance values from the available external static pressure shown in the Blower Pe...

Page 13: ...ncer 1S or contactor 2M maintains control of the evaporator blower c The thermostat cycles the electric heat to satisfy the heating requirements of the conditioned space CONTINUOUS BLOWER Continuous blower operation is possible by closing the R to G circuit on the thermostat HEAT ANTICIPATOR SETPOINTS It is important that the anticipator setpoint be correct Too high a setting results in longer hea...

Page 14: ... NOMINAL M3 S 0 38 0 52 0 66 0 80 0 94 1 08 1 23 PRESSURE DROP PA FIG 7 PRESSURE DROP ACROSS A DRY EVAPORATOR COIL VS SUPPLY AIRFLOW SECURE OWNER S APPROVAL When the system is functioning properly secure the owner s approval Show him the location of all disconnect switches and the thermostat Teach him how to start and stop the unit and how to adjust tem perature settings within the limitations of ...

Page 15: ...530 26 N1YI Unitary Products Group 15 ...

Page 16: ...P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1994 All Rights Reserved 530 26 N1YI ...

Reviews: