background image

MODEL

POWER

SUPPLY

COMPRESSOR

(#1 and #2)*

OUTDOOR

FAN

MOTOR,

(#1 & #2)

FLA

EACH

SUPPLY

AIR

BLOWER

MOTOR,

FLA

TOTAL

UNIT

AMPACITY,

AMPS

MAXIMUM

FUSE

SIZE, 

1,2

AMPS

RLA

EACH

LRA

EACH

2HP

3HP

2HP

3HP

2HP

3HP

BHN090

208/230-3-60

460-3-60
575-3-60

14.1

7.1
5.8

130

64
52

2.3
1.3

1.3

4

7.5
3.4
2.7

-
-
-

43.8
22.0
18.4

-
-
-

50
25
20

-
-
-

BHN120

208/230-3-60

460-3-60
575-3-60

17.3/16.7

9.6
8.3

150

73
59

3.5
2.5

2.5

4

-
-
-

10.6

4.8
3.9

-
-
-

55.9
31.4
27.6

-
-
-

70
40
35

*

Dual numbers shown as “17.3/16.7" indicates compressor #1 / #2 respectively.

NOTES:  1. Dual element, time delay type.
               2. Maximum HACR breaker of the same AMP size is applicable, except 575 voltages.
               3. Motor voltage (460-1-60). Unit includes 575/460V transformer.

ELECTRICAL DATA

VOLTAGE

LIMITATIONS*

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

575-3-60

518

630

*

Utilization Range “A” in accordance with ARI Standard 110.

FIELD WIRING 

511.17-TG2Y 

Unitary Products Group

9

Summary of Contents for SUNLINE 2000 B1HN090

Page 1: ...unit and discard them If a bottom supply return is desired you simply remove the two bottom duct covers and discard them No panel cutting or swapping is required Convertible airflow design allows max...

Page 2: ...M PROTECTION Crankcase heaters and internal compressor protection are standard on all compressors Each unit has suction line freezestats low pressure switches high pressure switches and high temperatu...

Page 3: ...e refrigeration system including circulating fan heat BTU s per hour divided by the total electric input watts x 3 412 AFUE Annual Fuel Utilization Efficiency determined in accordance with DOE test pr...

Page 4: ...4 0 CHARGE REFRIGERANT 22 lbs oz SYSTEM NO 1 9 0 11 8 SYSTEM NO 2 9 0 13 8 NOTE Filter racks are adapted for 1 or 2 thick filters PHYSICAL DATA COMPONENT WEIGHTS BASIC COMPONENT MODEL BHN 090 120 Basi...

Page 5: ...W Sensible Capacity 1 MBH Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 3750 72 99 8 6 80 69 58 46...

Page 6: ...Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71...

Page 7: ...56 6 8 68 6 9 79 7 5 93 8 3 CFM RET AIR F CAP KW OUTDOOR AIR TEMPERATURE F 72 RH 10 0 10 20 30 40 50 60 3000 55 MBH KW 30 7 1 41 7 2 52 7 4 64 7 6 77 7 9 93 8 3 109 8 7 127 9 6 70 MBH KW 29 7 4 39 7...

Page 8: ...0 1 61 1 66 1 55 1 44 1 81 1 69 1 10 2 10 1 96 MODEL BHN090 BOTTOM DUCT APPLICATIONS BLOWER PERFORMANCE 7 1 2 10 TON SUPPLY AIR BLOWER SPEED RPM CFM 3000 3500 4000 4500 5000 ESP BHP KW ESP BHP KW ESP...

Page 9: ...16 7 9 6 8 3 150 73 59 3 5 2 5 2 54 10 6 4 8 3 9 55 9 31 4 27 6 70 40 35 Dual numbers shown as 17 3 16 7 indicates compressor 1 2 respectively NOTES 1 Dual element time delay type 2 Maximum HACR break...

Page 10: ...must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined spac...

Page 11: ...3 Replace the side duct covers DETAIL X SIDE SUPPLY AND RETURN AIR DUCT OPENINGS CENTER OF GRAVITY B A R O M E T R I C R E L I E F R A I N H O O D R E A R V I E W L H E N D V I E W 2 3 3 8 2 3 3 4 A...

Page 12: ...310 378 302 120 1 612 322 416 492 382 BHN UNIT 6 POINT LOADS LBS TOTAL A B C D E F 090 1 237 155 186 217 264 226 189 120 1 612 199 246 293 347 291 236 NOTE These weights are with economizer and 24kW e...

Page 13: ...the curb from the roof All electrical connections can be made inside the curb ROOF CURB BENEFITS UNIT AND CURB APPLICATION ROOF CURB DIMENSIONS BHN 7 1 2 10 TON Supply and Return Air including duct s...

Page 14: ...rainhood and filters The outdoor air dampers open when the indoor fan motor is energized Damper capable of providing 0 thru 100 of outdoor return air opening MANUAL OUTDOOR DAMPER Provides 0 thru 35 o...

Page 15: ...511 17 TG2Y Unitary Products Group 15...

Page 16: ...up P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1998 All Rights Reserved Code EBY EGY 511 17 TG2Y Superse...

Reviews: