background image

Air On
Indoor

Coil

Temperature of Air on Outdoor Coil

85

°

F

95

°

F

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

 1

, MBH

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity 

1

, MBH

CFM

WB

°

F

Entering Dry Bulb, 

°

F

Entering Dry Bulb,

 °

F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

5000

72

159

11.0

118

103

88

73

58

-

-

151

11.8

115

100

85

70

55

-

-

67

142

10.8

138

123

108

93

78

63

48

135

11.6

135

122

107

92

77

62

47

62

133

10.5

133

133

131

116

101

86

71

125

11.3

125

125

125

110

95

80

65

57

136

10.4

136

136

136

121

106

91

76

131

11.2

131

131

131

116

101

86

72

4500

72

153

11.0

109

96

82

69

56

-

-

145

11.8

106

92

79

65

52

-

-

67

138

10.8

129

116

103

89

76

62

49

131

11.6

126

114

101

87

74

60

47

62

128

10.4

128

128

123

109

96

82

69

120

11.2

120

120

119

106

93

79

66

57

131

10.4

131

131

128

115

101

88

74

126

11.2

126

126

123

110

97

83

70

4000

72

146

10.9

101

89

77

65

53

-

-

140

11.7

96

85

73

61

49

-

-

67

134

10.7

121

109

97

85

73

61

50

128

11.5

118

106

94

82

70

58

46

62

123

10.4

123

123

115

103

91

79

67

115

11.2

115

115

115

103

91

79

67

57

126

10.4

126

126

120

108

96

84

72

121

11.2

121

121

115

104

92

80

68

3500

72

144

10.9

94

83

72

62

51

-

-

137

11.6

89

79

68

58

47

-

-

67

131

10.7

112

101

90

80

69

59

48

124

11.4

108

98

87

77

66

55

45

62

121

10.3

121

117

108

97

87

76

66

113

11.1

113

112

107

97

86

76

65

57

124

10.3

124

120

113

102

92

81

71

119

11.1

119

116

108

98

87

77

66

3000

72

142

10.8

86

77

68

59

49

-

-

135

11.5

82

73

64

54

45

-

-

67

127

10.6

102

93

84

74

65

56

47

121

11.3

99

90

80

71

62

53

43

62

120

10.3

120

110

101

92

83

73

64

111

11.0

111

110

100

91

82

73

63

57

122

10.2

122

115

106

97

87

78

69

117

11.0

117

110

101

92

83

73

64

COOLING CAPACITIES - 10 TON (BHN120)

Air On
Indoor

Coil

Temperature of Air on Outdoor Coil

105

°

F

115

°

F

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity

 1

, MBH

Total

Cap.

1

MBH

Power

Input

2

KW

Sensible Capacity 

1

, MBH

CFM

WB

°

F

Entering Dry Bulb, 

°

F

Entering Dry Bulb,

 °

F

86

83

80

77

74

71

68

86

83

80

77

74

71

68

5000

72

138

12.5

109

94

79

64

50

-

-

124

13.2

104

89

74

59

44

-

-

67

121

12.3

121

115

102

87

72

57

42

108

12.9

108

108

97

82

67

52

37

62

112

11.9

112

112

112

97

82

67

52

99

12.6

99

99

99

84

69

54

39

57

118

11.9

118

118

118

103

89

74

59

105

12.5

105

105

105

91

76

61

46

4500

72

132

12.5

101

87

74

60

47

-

-

119

13.1

96

82

69

55

42

-

-

67

118

12.2

115

108

96

82

69

56

42

104

12.9

104

102

91

78

64

51

37

62

107

11.9

107

107

106

93

80

66

53

94

12.5

94

94

93

80

67

53

40

57

114

11.8

114

114

111

98

84

71

57

101

12.4

101

101

99

85

72

58

45

4000

72

126

12.4

92

80

68

56

44

-

-

113

13.1

87

75

63

51

39

-

-

67

114

12.2

109

102

90

78

66

54

42

101

12.8

101

97

85

73

61

49

38

62

103

11.8

103

103

102

90

78

66

54

90

12.5

90

90

89

77

65

53

41

57

109

11.8

109

109

104

92

80

68

56

96

12.3

96

96

92

80

68

56

44

3500

72

124

12.3

85

74

63

53

42

-

-

111

13.0

80

69

59

48

38

-

-

67

111

12.1

102

93

83

72

61

51

40

98

12.7

95

89

78

68

57

46

36

62

101

11.7

101

100

95

84

74

63

53

88

12.4

88

87

82

72

61

51

40

57

107

11.7

107

104

97

86

76

65

54

95

12.2

95

92

85

75

64

53

43

3000

72

122

12.2

77

68

59

50

40

-

-

109

12.9

73

63

54

45

36

-

-

67

108

12.0

94

85

76

66

57

48

39

95

12.6

90

80

71

62

53

43

34

62

99

11.6

99

97

88

79

70

60

51

87

12.3

87

85

76

67

57

48

39

57

105

11.6

105

99

90

81

71

62

53

93

12.1

93

88

79

69

60

51

42

1

These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the 

   motor heat, and  deduct this heat from the gross capacity of the unit.

2

These ratings include the compressor and the outdoor fan motors but not the supply air blower motor.

ALL SENSIBLE CAPACITY

NOMINAL RATING

511.17-TG2Y 

6

Unitary Products Group

Summary of Contents for SUNLINE 2000 B1HN090

Page 1: ...unit and discard them If a bottom supply return is desired you simply remove the two bottom duct covers and discard them No panel cutting or swapping is required Convertible airflow design allows max...

Page 2: ...M PROTECTION Crankcase heaters and internal compressor protection are standard on all compressors Each unit has suction line freezestats low pressure switches high pressure switches and high temperatu...

Page 3: ...e refrigeration system including circulating fan heat BTU s per hour divided by the total electric input watts x 3 412 AFUE Annual Fuel Utilization Efficiency determined in accordance with DOE test pr...

Page 4: ...4 0 CHARGE REFRIGERANT 22 lbs oz SYSTEM NO 1 9 0 11 8 SYSTEM NO 2 9 0 13 8 NOTE Filter racks are adapted for 1 or 2 thick filters PHYSICAL DATA COMPONENT WEIGHTS BASIC COMPONENT MODEL BHN 090 120 Basi...

Page 5: ...W Sensible Capacity 1 MBH Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 3750 72 99 8 6 80 69 58 46...

Page 6: ...Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71...

Page 7: ...56 6 8 68 6 9 79 7 5 93 8 3 CFM RET AIR F CAP KW OUTDOOR AIR TEMPERATURE F 72 RH 10 0 10 20 30 40 50 60 3000 55 MBH KW 30 7 1 41 7 2 52 7 4 64 7 6 77 7 9 93 8 3 109 8 7 127 9 6 70 MBH KW 29 7 4 39 7...

Page 8: ...0 1 61 1 66 1 55 1 44 1 81 1 69 1 10 2 10 1 96 MODEL BHN090 BOTTOM DUCT APPLICATIONS BLOWER PERFORMANCE 7 1 2 10 TON SUPPLY AIR BLOWER SPEED RPM CFM 3000 3500 4000 4500 5000 ESP BHP KW ESP BHP KW ESP...

Page 9: ...16 7 9 6 8 3 150 73 59 3 5 2 5 2 54 10 6 4 8 3 9 55 9 31 4 27 6 70 40 35 Dual numbers shown as 17 3 16 7 indicates compressor 1 2 respectively NOTES 1 Dual element time delay type 2 Maximum HACR break...

Page 10: ...must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined spac...

Page 11: ...3 Replace the side duct covers DETAIL X SIDE SUPPLY AND RETURN AIR DUCT OPENINGS CENTER OF GRAVITY B A R O M E T R I C R E L I E F R A I N H O O D R E A R V I E W L H E N D V I E W 2 3 3 8 2 3 3 4 A...

Page 12: ...310 378 302 120 1 612 322 416 492 382 BHN UNIT 6 POINT LOADS LBS TOTAL A B C D E F 090 1 237 155 186 217 264 226 189 120 1 612 199 246 293 347 291 236 NOTE These weights are with economizer and 24kW e...

Page 13: ...the curb from the roof All electrical connections can be made inside the curb ROOF CURB BENEFITS UNIT AND CURB APPLICATION ROOF CURB DIMENSIONS BHN 7 1 2 10 TON Supply and Return Air including duct s...

Page 14: ...rainhood and filters The outdoor air dampers open when the indoor fan motor is energized Damper capable of providing 0 thru 100 of outdoor return air opening MANUAL OUTDOOR DAMPER Provides 0 thru 35 o...

Page 15: ...511 17 TG2Y Unitary Products Group 15...