RATINGS

MODEL

COOLING

CAPACITY

(SEE NOTE 1)

80/67-95

°

F

SOUND
RATING

(SEE NOTE 2)

(bels)

HEAT PUMP

HTG. CAPACITY

@ 47

°

(SEE NOTE 1)

GAS HEAT CAPACITY 

(SEE NOTE 3)

INPUT

(MBH)

OUTPUT

(MBH)

AFUE

(%)

S.S.E.

(%)

S.E.

(%)

TEMP.

RISE

(

°

F)

GAS

LINE SIZE

(in. OD)

MBH

EER

MBH

COP

B1HN090N130
B1HN090N165

87.0

9.0

8.6

89.0

3.0

163
204

130
163

79.0
80.0

80.0
80.0

72.9
74.9

30 - 60
30 - 60

3/4
3/4

B1HN120N165
B1HN120N200

118.0

9.0

8.8

116.0

3.0

204
245

163
198

80.0
79.5

80.0
81.0

73.5
76.4

30 - 60
30 - 60

3/4
3/4

NOTE:  1. Ratings are in accordance with ARI Standard 240.
             2. Sound Ratings are in accordance with ARI Standard 270.
             3.  All units are two-stage gas heating. First stage is 70% of total.

EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (Btuh) divided by the power input in watts at any
            given set of rating conditions, expressed in Btuh per watt (Btuh/watt).
COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat
            (BTU’s per hour) divided by the total electric input (watts) x 3.412.
AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.
S.S.E. = Steady State Efficiency. (Percent Output).

208/230,460 VOLT

MODELS ONLY

208/230,575 VOLT

MODELS ONLY

Unit

Size

CFM

ESP

Blower

Sound Power (db 10

-12 

Watts)

Octave Band Centerline Frequency (Hz)

SWL

db(A)

db(A)

@

10 Ft*

IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

090
120

3,000
4,000

0.80
0.80

1,145

960

1.85
2.20

92
94

92
94

82
84

75
77

77
79

70
72

65
67

60
62

82
84

49
51

*At a distance of 10 ft.from the blower.
NOTE: These values have been derived using a model of sound propagation, measuring the indoor ambient sound levels ten feet from the source. The dBA values provided are for reference
only. Calculation of dBA values cover matters of system design and application. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other
form than sound power level ratings.

INDOOR SOUND POWER RATINGS

511.17-TG2Y 

Unitary Products Group

3

Summary of Contents for SUNLINE 2000 B1HN090

Page 1: ...unit and discard them If a bottom supply return is desired you simply remove the two bottom duct covers and discard them No panel cutting or swapping is required Convertible airflow design allows max...

Page 2: ...M PROTECTION Crankcase heaters and internal compressor protection are standard on all compressors Each unit has suction line freezestats low pressure switches high pressure switches and high temperatu...

Page 3: ...e refrigeration system including circulating fan heat BTU s per hour divided by the total electric input watts x 3 412 AFUE Annual Fuel Utilization Efficiency determined in accordance with DOE test pr...

Page 4: ...4 0 CHARGE REFRIGERANT 22 lbs oz SYSTEM NO 1 9 0 11 8 SYSTEM NO 2 9 0 13 8 NOTE Filter racks are adapted for 1 or 2 thick filters PHYSICAL DATA COMPONENT WEIGHTS BASIC COMPONENT MODEL BHN 090 120 Basi...

Page 5: ...W Sensible Capacity 1 MBH Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 3750 72 99 8 6 80 69 58 46...

Page 6: ...Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71...

Page 7: ...56 6 8 68 6 9 79 7 5 93 8 3 CFM RET AIR F CAP KW OUTDOOR AIR TEMPERATURE F 72 RH 10 0 10 20 30 40 50 60 3000 55 MBH KW 30 7 1 41 7 2 52 7 4 64 7 6 77 7 9 93 8 3 109 8 7 127 9 6 70 MBH KW 29 7 4 39 7...

Page 8: ...0 1 61 1 66 1 55 1 44 1 81 1 69 1 10 2 10 1 96 MODEL BHN090 BOTTOM DUCT APPLICATIONS BLOWER PERFORMANCE 7 1 2 10 TON SUPPLY AIR BLOWER SPEED RPM CFM 3000 3500 4000 4500 5000 ESP BHP KW ESP BHP KW ESP...

Page 9: ...16 7 9 6 8 3 150 73 59 3 5 2 5 2 54 10 6 4 8 3 9 55 9 31 4 27 6 70 40 35 Dual numbers shown as 17 3 16 7 indicates compressor 1 2 respectively NOTES 1 Dual element time delay type 2 Maximum HACR break...

Page 10: ...must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined spac...

Page 11: ...3 Replace the side duct covers DETAIL X SIDE SUPPLY AND RETURN AIR DUCT OPENINGS CENTER OF GRAVITY B A R O M E T R I C R E L I E F R A I N H O O D R E A R V I E W L H E N D V I E W 2 3 3 8 2 3 3 4 A...

Page 12: ...310 378 302 120 1 612 322 416 492 382 BHN UNIT 6 POINT LOADS LBS TOTAL A B C D E F 090 1 237 155 186 217 264 226 189 120 1 612 199 246 293 347 291 236 NOTE These weights are with economizer and 24kW e...

Page 13: ...the curb from the roof All electrical connections can be made inside the curb ROOF CURB BENEFITS UNIT AND CURB APPLICATION ROOF CURB DIMENSIONS BHN 7 1 2 10 TON Supply and Return Air including duct s...

Page 14: ...rainhood and filters The outdoor air dampers open when the indoor fan motor is energized Damper capable of providing 0 thru 100 of outdoor return air opening MANUAL OUTDOOR DAMPER Provides 0 thru 35 o...

Page 15: ...511 17 TG2Y Unitary Products Group 15...

Page 16: ...up P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1998 All Rights Reserved Code EBY EGY 511 17 TG2Y Superse...

Reviews: