5167798-YTG-J-0218
8
Johnson Controls Unitary Products
•
Hot Gas Bypass -
Allows operation during low load
conditions while avoiding coil frosting and damage to
compressor. When suction pressure falls below valve
setpoint, the valve modulates hot gas to the inlet of the
evaporator.
HGBP is standard on all units with VAV, and optional with
constant-volume units.
Control Options
•
Smart Equipment™ with Communication Option
Control
- The York® Smart Equipment™ with
Communication Option Control is factory installed. It
includes all the features of the Smart Equipment™ control
with an additional gateway to BACnet MS/TP
(programmable to Modbus or N2 protocols).
•
FDD (Fault Detection and Diagnostics) - Refrigerant
side
A factory installed control system option on the
commercial equipment that constantly monitors
refrigerant circuit pressures, refrigerant circuit
temperatures, as well as the environmental temperatures
and humidity via multiple sensor inputs.
• Provides a building owner, technician or contractor with
the operational characteristics of the RTUs entire
refrigerant circuit to ensure the unit is functioning at its
specified performance level.
• Provides alarms if the unit is not functioning optimally.
• Remotely accessible via the Mobile Access Portal
(MAP) gateway as well as scrolled on the UCB LCD
screen.
•
Novar® BAS Control -
The Novar® building automation
system controller is factory installed. Includes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
•
CPC BAS Control -
The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, with optional dirty
filter indicator switch and air proving switch.
•
Honeywell BAS Control -
The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, with optional
dirty filter indicator switch, and air proving switch.
•
Verasys
- Verasys provides a simple user experience
with configurable self-recognizing controllers without the
need for any additional tools. Verasys creates enhanced
integration of HVACR equipment, zoning, and controls.
Contractors are able to offer a complete bundled solution
of equipment and controls to serve the light commercial
market.
Field Installed Accessories
YORK
®
offers several equipment accessories for field
installation, for the Predator
®
line.
•
Down flow and End Return Economizers (with fresh air
hood and barometric relief) -
All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers designed
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper,
and the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/sq. ft. at 1" of static pressure. Each economizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to 100%
outdoor air. As the outdoor air intake dampers open, the
return air dampers close. The changeover from mechanical
refrigeration to economizer operation is regulated by the
outdoor air dry bulb temperature or the outdoor air enthalpy
input. The dual enthalpy kit provides a second input used to
monitor the return air (field installed). The installer needs only
to assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and control
are provided).
•
Single or Dual Enthalpy Control, Accessories
- These
kits contain the required components to convert a dry bulb
economizer to a single enthalpy and/or dual enthalpy
economizer.
•
Barometric Relief Damper
- Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed economizers.
•
Power Exhaust
- This accessory installs in the unit with a
down flow or horizontal end return economizer. Power
exhaust plugs into the connector in the unit bulkhead.
User must purchase the 1EH0408 barometric relief
and hood kit when applying the product in a
horizontal flow application. The power exhaust must
be mounted in the horizontal end return ductwork.
•
Manual Outdoor Air Damper
- Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
•
Motorized Outdoor Air Damper
- The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
•
Smoke Detectors
- The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
•
CO
2
Sensor
- Senses CO
2
levels and automatically
overrides the economizer when levels rise above the
preset limits.
•
Dirty Filter Switch
- This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
•
Coil Guard -
Field installed decorative wire coil guard.
•
Hail Guard
- This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
•
Flue Exhaust Extension Kit
- In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be