Johnson Controls Unitary Products

Hot Gas Bypass -

 Allows operation during low load 

conditions while avoiding coil frosting and damage to 
compressor. When suction pressure falls below valve 
setpoint, the valve modulates hot gas to the inlet of the 
evaporator.

HGBP is standard on all units with VAV, and optional with 
constant-volume units.

Control Options

Smart Equipment™ with Communication Option 
Control

 - The York® Smart Equipment™ with 

Communication Option Control is factory installed. It 
includes all the features of the Smart Equipment™ control 
with an additional gateway to BACnet MS/TP 
(programmable to Modbus or N2 protocols).

FDD (Fault Detection and Diagnostics) - Refrigerant 
side

 A factory installed control system option on the 

commercial equipment that constantly monitors 
refrigerant circuit pressures, refrigerant circuit 
temperatures, as well as the environmental temperatures 
and humidity via multiple sensor inputs.

• Provides a building owner, technician or contractor with 

the operational characteristics of the RTUs entire 
refrigerant circuit to ensure the unit is functioning at its 
specified performance level.

• Provides alarms if the unit is not functioning optimally.

• Remotely accessible via the Mobile Access Portal 

(MAP) gateway as well as scrolled on the UCB LCD 
screen.

Novar® BAS Control -

 The Novar® building automation 

system controller is factory installed. Includes supply air 
sensor, return air sensor, dirty filter indicator switch, and 
air proving switch.

CPC BAS Control - 

The Computer Process Controls 

Model 810-3060 ARTC Advanced Rooftop building 
automation system controller is factory installed. Includes 
supply air sensor, return air sensor, with optional dirty 
filter indicator switch and air proving switch.

Honeywell BAS Control - 

The Honeywell W7750C 

building automation system controller is factory installed. 
Includes air supply sensor, return air sensor, with optional 
dirty filter indicator switch, and air proving switch.

Verasys 

- Verasys provides a simple user experience 

with configurable self-recognizing controllers without the 
need for any additional tools. Verasys creates enhanced 
integration of HVACR equipment, zoning, and controls. 
Contractors are able to offer a complete bundled solution 
of equipment and controls to serve the light commercial 
market.

Field Installed Accessories

YORK

®

 offers several equipment accessories for field 

installation, for the Predator

®

 

line.

Down flow and End Return Economizers (with fresh air 
hood and barometric relief) -

 All units offer a variety of 

optional factory installed down flow economizers that are 
shipped, installed and wired with low leak dampers designed 

to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper, 
and the International Energy Conservation Code (IECC) 
certification requirements by achieving leakage rates of 3 
cfm/sq. ft. at 1" of static pressure. Each economizer goes 
through a rigorous 60,000 cycle test. Dry bulb, single 
enthalpy, and dual enthalpy (with field installed kit) can be 
selected. The economizer has spring return, fully modulating 
damper actuators and is capable of introducing up to 100% 
outdoor air. As the outdoor air intake dampers open, the 
return air dampers close. The changeover from mechanical 
refrigeration to economizer operation is regulated by the 
outdoor air dry bulb temperature or the outdoor air enthalpy 
input. The dual enthalpy kit provides a second input used to 
monitor the return air (field installed). The installer needs only 
to assemble the outdoor air hood, attach the enthalpy control 
the hood and mount the hood to the unit (Hood and control 
are provided).

Single or Dual Enthalpy Control, Accessories

 - These 

kits contain the required components to convert a dry bulb 
economizer to a single enthalpy and/or dual enthalpy 
economizer.

Barometric Relief Damper 

- Zero to 100% capacity 

barometric relief dampers for use with horizontal flow, or 
field installed economizers.

Power Exhaust 

- This accessory installs in the unit with a 

down flow or horizontal end return economizer. Power 
exhaust plugs into the connector in the unit bulkhead.

 

User must purchase the 1EH0408 barometric relief 
and hood kit when applying the product in a 
horizontal flow application. The power exhaust must 
be mounted in the horizontal end return ductwork.

Manual Outdoor Air Damper 

- Like the motorized outdoor 

air damper, each manual outdoor air damper includes a 
slide-in damper assembly with an outdoor air hood and 
filters. Customers have a choice of dampers with ranges of 
0% to 100% or 0% to 35% outdoor air entry.

Motorized Outdoor Air Damper 

- The motorized outdoor 

air damper includes a slide-in/plug-in damper assembly with 
an outdoor air hood and filters. The outdoor air dampers 
open to the preset position when the indoor fan motor is 
energized. The damper has a range of 0% to 100% outdoor 
air entry. Factory installed option or field installed accessory.

Smoke Detectors 

- The smoke detectors stop operation 

of the unit by interrupting power to the control board if 
smoke is detected within the air compartment.

CO

2

 Sensor

 

- Senses CO

2

 levels and automatically 

overrides the economizer when levels rise above the 
preset limits.

Dirty Filter Switch 

- This kit includes a differential 

pressure switch that energizes the fault light on the unit 
thermostat, indicating that there is an abnormally high 
pressure drop across the filters.

Coil Guard - 

Field installed decorative wire coil guard.

Hail Guard 

- This kit includes a sloped hood which installs 

over the outside condenser coil and prevents damage to 
the coil fins from hail strikes. Field installed accessory only.

Flue Exhaust Extension Kit 

- In locations with wind or 

weather conditions which may interfere with proper 
exhausting of furnace combustion products, this kit can be 

Summary of Contents for Predator ZF120

Page 1: ...way forklift access and overhead rigging Every unit is completely charged wired piped and tested at the factory to provide a quick and easy field installation Predator units in all tonnage sizes are c...

Page 2: ...essor Dual stage cooling for maximum comfort Second model nameplate inside hinged access panel Terminal block for hi voltage connection Smart Equipment control board w screw connector for T stat wirin...

Page 3: ...oil Guard CG STD Filter 5 2 Pleated Filter CG 6 4 Pleated Filter CG A Std Cabinet E SSD SST Drain Pan R Reverse Drain Pan A No Economizer B Economizer w Barometric RLF D Economizer w Power EXH H Motor...

Page 4: ...Filters MERV 7 BAS Ready Economizer 2 10 V D C Actuator without a Controller Shipping Bag York Commercial Comfort System YCCS Rtu Controller Hot Gas Bypass Standard on VAV Optional on CV Variable Air...

Page 5: ...shot openings No panel cutting is required Convertible airflow design allows maximum field flexibility and minimum inventory System Protection Suction line freezestats are supplied on all units to pro...

Page 6: ...ts are painted with a long lasting powder paint that stands up over the life of the unit The paint used has been proven by a 1000 hour salt spray test Full Perimeter Base Rails The permanently attache...

Page 7: ...inimum position will also be configurable to vary based on the supply fan VFD frequency output Aluminized Steel Gas Heat Exchanger For applications in non corrosive environments Stainless Steel Gas He...

Page 8: ...ion requirements by achieving leakage rates of 3 cfm sq ft at 1 of static pressure Each economizer goes through a rigorous 60 000 cycle test Dry bulb single enthalpy and dual enthalpy with field insta...

Page 9: ...ory Cooling units include an adapter panel for easy installation of the electric heaters Necessary hardware and connectors are included with the heaters All heaters are intended for single point power...

Page 10: ...inets 1RC0470 All Roof Curb 8 Height All Cabinets 1RC0471 All Roof Curb 14 Height All Cabinets 1RC0472 All Roof Curb Transition 7 5 T thru 12 5T Sunline to Predator 3 12T All Cabinets 1WC0412 All Wood...

Page 11: ...nflow All Cabinets 1FA0414 All Manual Outside Air Damper 0 100 Downflow All Cabinets 1EH0408 All Barometric Relief Kit for Power Exhaust Horizontal Application All Cabinets 2EC0401 All Single Enthalpy...

Page 12: ...d on two sides of the units for coil cleaning REFRIGERANT COMPONENTS Compressors a Shall be fully hermetic type direct drive internally protected with internal high pressure relief and over temperatur...

Page 13: ...the International Energy Conservation Code IECC certification requirements by achieving leakage rates of 3 cfm sq ft at 1 of static pressure Changeover from compressor to economizer operation shall b...

Page 14: ...d in the supply and or return air compartments OTHER PRE ENGINEERED ACCESSORIES AVAILABLE ROOF CURB 14 and 8 high full perimeter knockdown curb with hinged design for quick assembly BAROMETRIC RELIEF...

Page 15: ...0 120 180 180 240 180 240 Heat output K Btu 96 144 96 144 96 144 144 192 144 192 AFUE Steady state efficiency 80 80 80 80 80 80 80 80 80 80 No burners 4 6 4 6 4 6 6 8 6 8 No stages 23 23 23 23 23 23 2...

Page 16: ...VM50 1VM50 1VM50 1VM50 1VP56 Blower Sheave AK74 AK64 AK74 AK61 AK89 AK74 AK84 AK74 AK74 BK77 Belt A49 A49 A49 A49 A56 A54 A56 A54 A54 BX55 Motor HP each 1 1 2 2 1 1 2 3 2 3 2 3 3 5 RPM 1725 1725 1725...

Page 17: ...ZF 208 230 3 60 187 252 125 460 3 60 432 504 125 575 3 60 540 630 125 090 7 5 ZF 208 230 3 60 187 252 125 460 3 60 432 504 125 575 3 60 540 630 125 102 8 5 ZF 208 230 3 60 187 252 125 460 3 60 432 50...

Page 18: ...109 4 5 0 83 1 70 0 56 8 43 6 101 4 5 6 80 4 67 3 54 2 41 0 67 100 1 5 0 100 1 87 9 74 7 61 6 48 4 92 3 5 5 92 3 84 5 71 4 58 3 45 1 62 91 4 5 0 91 4 91 4 91 4 78 2 65 0 51 8 83 6 5 5 83 6 83 6 83 6...

Page 19: ...1 4 58 6 7 6 58 6 58 6 49 7 39 0 28 3 62 61 4 7 0 61 4 61 4 63 4 52 6 41 9 31 1 55 5 7 5 55 5 55 5 55 5 48 1 37 4 26 8 57 56 5 6 9 56 5 56 5 55 2 44 4 33 6 22 8 47 7 7 3 47 7 47 7 46 2 35 6 24 9 14 2...

Page 20: ...51 9 112 2 6 0 88 2 75 2 62 3 49 3 67 106 7 5 3 106 7 96 0 83 1 70 3 57 5 101 5 6 0 101 5 92 2 79 3 66 3 53 3 62 101 4 5 1 101 4 101 4 100 9 88 0 75 2 62 4 93 4 6 0 93 4 93 4 93 1 80 2 67 2 54 2 57 8...

Page 21: ...9 5 72 4 9 6 72 4 72 0 60 2 48 3 36 5 62 75 5 8 6 75 5 75 5 74 4 62 9 51 4 39 9 71 8 9 5 71 8 71 8 71 0 59 2 47 3 35 5 57 75 6 8 6 75 6 75 6 74 6 63 1 51 6 40 1 70 4 9 5 70 4 70 4 69 1 57 2 45 4 33 5...

Page 22: ...0 8 94 8 78 8 62 8 130 3 7 2 105 1 89 0 73 0 57 0 67 127 8 6 4 127 8 113 9 97 9 81 9 65 9 118 1 7 1 118 1 108 5 92 5 76 5 60 4 62 115 5 6 4 115 5 115 5 115 5 99 5 83 6 67 6 106 6 7 0 106 6 106 6 106 6...

Page 23: ...5 40 4 72 4 9 6 72 4 72 4 64 3 50 0 35 6 62 79 5 8 9 79 5 79 5 79 7 65 5 51 3 37 2 72 2 9 5 72 2 72 2 72 2 59 4 45 0 30 7 57 80 4 9 0 80 4 80 4 78 5 64 3 50 2 36 0 73 7 9 6 73 7 73 7 71 2 56 8 42 5 28...

Page 24: ...7 105 7 85 7 65 6 67 153 0 7 4 153 0 136 3 115 7 95 1 74 5 141 4 8 3 141 4 130 2 110 2 90 2 70 2 62 139 9 7 5 139 9 139 9 139 9 119 3 98 7 78 1 128 6 8 2 128 6 128 6 128 6 108 6 88 6 68 6 57 133 5 7 4...

Page 25: ...3 65 7 49 2 90 0 11 4 90 0 90 0 77 2 60 7 44 2 62 91 7 10 4 91 7 91 7 99 5 82 9 66 4 49 8 80 6 11 1 80 6 80 6 80 6 77 4 61 0 44 5 57 95 1 10 5 95 1 95 1 94 7 78 2 61 6 45 1 86 9 11 2 86 9 86 9 85 7 69...

Page 26: ...0 4 9 8 181 6 160 4 140 4 120 5 100 5 179 9 10 9 175 5 155 4 135 3 115 1 95 0 62 172 2 9 7 172 2 172 2 172 2 152 2 132 2 112 3 162 8 10 8 162 8 162 8 162 8 142 7 122 5 102 4 57 167 2 9 7 167 2 167 2 1...

Page 27: ...1 0 126 8 16 2 126 8 117 7 100 8 83 8 66 8 62 128 9 14 6 128 9 128 9 130 1 112 9 95 7 78 4 119 9 16 0 119 9 119 9 119 9 107 0 90 0 73 1 57 126 9 14 6 126 9 126 9 130 6 113 4 96 2 79 0 117 9 16 0 117 9...

Page 28: ...982 1 06 1038 1 21 1092 1 35 1147 1 48 1203 1 61 1259 1 73 1317 1 87 2400 835 0 66 897 0 87 956 1 06 1013 1 22 1069 1 37 1124 1 51 1178 1 64 1234 1 77 1290 1 90 1348 2 03 2600 869 0 84 931 1 05 990 1...

Page 29: ...Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave settin...

Page 30: ...49 1286 1 65 1365 1 81 1447 1 98 1532 2 18 2400 878 0 78 953 1 00 1027 1 19 1100 1 36 1174 1 52 1250 1 67 1327 1 82 1405 1 98 1487 2 16 1572 2 36 2600 923 0 98 997 1 20 1071 1 39 1145 1 56 1219 1 72...

Page 31: ...2 5 Ton Bottom Duct Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See R...

Page 32: ...0 08 0 09 0 11 2300 0 01 0 11 0 12 0 07 0 08 0 09 0 10 0 13 2500 0 02 0 13 0 14 0 08 0 09 0 10 0 11 0 14 2700 0 03 0 16 0 15 0 09 0 10 0 12 0 13 0 16 2900 0 04 0 18 0 16 0 10 0 11 0 13 0 14 0 18 3100...

Page 33: ...1 95 BHP exceeds the maximum continuous BHP rating of the 1 5 HP motor The 2 HP motor is required 6 1268 RPM is within the range of the 2 HP drives 7 Using the 2 HP motor and drive 5 turns open will...

Page 34: ...0 880 0 848 0 816 0 787 0 757 0 729 0 701 70 1 000 0 964 0 930 0 896 0 864 0 832 0 801 0 772 0 743 0 715 0 688 80 0 982 0 947 0 913 0 880 0 848 0 817 0 787 0 758 0 730 0 702 0 676 90 0 964 0 929 0 89...

Page 35: ...50 12 5 ZF 208 230 3 60 3750 3750 3750 4000 460 3 60 3750 3750 3750 3750 600 3 60 3750 3750 3750 3750 Indoor Blower Specifications Size Tons Model Motor Motor Sheave Blower Sheave Belt HP RPM Eff SF F...

Page 36: ...onstitutes an exception to any specification or guarantee requiring a dBA value of sound data in any other form than sound power level ratings Octave Band Centerline Frequency Hz RPM BHP 63 125 250 50...

Page 37: ...40 5 46 50 50 E09 6 8 1 18 9 40 5 46 50 50 E18 13 5 2 37 5 53 4 60 3 60 70 E24 18 2 50 69 75 9 70 80 E36 25 5 2 70 8 95 101 9 100 110 230 13 8 83 1 22 2 1 5 2 5 5 None 40 5 46 50 50 E09 9 1 21 7 40 5...

Page 38: ...0 100 E24 18 2 50 74 5 81 4 90 100 E36 25 5 2 70 8 100 5 107 4 110 110 E54 40 6 2 112 7 152 9 159 8 175 175 230 23 1 160 36 3 03 9 6 5 5 None 73 7 79 2 90 100 E18 18 2 43 3 73 7 79 2 90 100 E24 24 2 5...

Page 39: ...9 50 4 50 60 E09 6 8 1 18 9 44 9 50 4 50 60 E18 13 5 2 37 5 58 9 65 8 60 70 E24 18 2 50 74 5 81 4 80 90 E36 25 5 2 70 8 100 5 107 4 110 110 230 13 8 83 1 22 2 1 9 6 5 5 None 44 9 50 4 50 60 E09 9 1 21...

Page 40: ...00 100 E24 18 2 50 80 86 9 100 100 E36 25 5 2 70 8 106 112 9 110 125 E54 40 6 2 112 7 158 4 165 3 175 175 230 23 1 160 36 3 03 14 5 5 None 78 1 83 6 100 100 E18 18 2 43 3 78 1 83 6 100 100 E24 24 2 57...

Page 41: ...09 6 8 1 18 9 50 5 56 60 60 E18 13 5 2 37 5 65 9 72 8 70 80 E24 18 2 50 81 5 88 4 90 90 E36 25 5 2 70 8 107 5 114 4 110 125 230 13 8 83 1 22 2 1 5 2 5 5 20 None 50 5 56 60 60 E09 9 1 21 7 50 5 56 60 6...

Page 42: ...89 2 100 110 E24 18 2 50 87 93 9 100 110 E36 25 5 2 70 8 113 119 9 125 125 E54 40 6 2 112 7 165 4 172 3 175 175 230 23 1 160 36 3 03 9 6 5 5 20 None 83 7 89 2 100 110 E18 18 2 43 3 83 7 89 2 100 110...

Page 43: ...0 70 E09 6 8 1 18 9 54 9 60 4 60 70 E18 13 5 2 37 5 71 4 78 3 80 80 E24 18 2 50 87 93 9 90 100 E36 25 5 2 70 8 113 119 9 125 125 230 13 8 83 1 22 2 1 9 6 5 5 20 None 54 9 60 4 60 70 E09 9 1 21 7 54 9...

Page 44: ...6 110 110 E24 18 2 50 92 5 99 4 110 110 E36 25 5 2 70 8 118 5 125 4 125 150 E54 40 6 2 112 7 170 9 177 8 175 200 230 23 1 160 36 3 03 14 5 5 20 None 88 1 93 6 110 110 E18 18 2 43 3 88 1 93 6 110 110 E...

Page 45: ...5167798 YTG J 0218 Johnson Controls Unitary Products 45 Typical Wiring Diagrams ZF078 150 Typical Wiring Diagrams Typical ZF078 120 Cooling Unit with Gas Heat 208 230 Volt Wiring Diagram...

Page 46: ...5167798 YTG J 0218 46 Johnson Controls Unitary Products Typical ZF078 120 Cooling Unit with Gas Heat 208 230 Volt Unit Options...

Page 47: ...5167798 YTG J 0218 Johnson Controls Unitary Products 47 Typical ZF078 120 Cooling Unit with Gas Heat 460 575 Volt Wiring Diagram...

Page 48: ...5167798 YTG J 0218 48 Johnson Controls Unitary Products Typical ZF078 120 Cooling Unit with Gas Heat 460 575 Volt Unit Options...

Page 49: ...5167798 YTG J 0218 Johnson Controls Unitary Products 49 Typical ZF078 120 Cooling Unit with without Electric Heat Wiring Diagram...

Page 50: ...5167798 YTG J 0218 50 Johnson Controls Unitary Products Typical ZF78 120 Cooling Unit with without Electric Heat Unit Options...

Page 51: ...5167798 YTG J 0218 Johnson Controls Unitary Products 51 Typical ZF150 Cooling Unit with Gas Heat 208 230 Volt Wiring Diagram...

Page 52: ...5167798 YTG J 0218 52 Johnson Controls Unitary Products Typical ZF150 Cooling Unit with Gas Heat 208 230 Volt Unit Options...

Page 53: ...5167798 YTG J 0218 Johnson Controls Unitary Products 53 Typical ZF150 Cooling Unit with Gas Heat 460 575 Volt Wiring Diagram...

Page 54: ...5167798 YTG J 0218 54 Johnson Controls Unitary Products Typical ZF150 Cooling Unit with Gas Heat 460 575 Volt Unit Options...

Page 55: ...5167798 YTG J 0218 Johnson Controls Unitary Products 55 Typical ZF150 Cooling Unit with without Electric Heat Wiring Diagram...

Page 56: ...5167798 YTG J 0218 56 Johnson Controls Unitary Products Typical ZF150 Cooling Unit with without Electric Heat Unit Options...

Page 57: ...5167798 YTG J 0218 Johnson Controls Unitary Products 57 BAS Controls Typical Wiring Diagrams Typical SURVEYOR BAS Control Wiring Diagram...

Page 58: ...5167798 YTG J 0218 58 Johnson Controls Unitary Products Typical CPC BAS Control Wiring Diagram...

Page 59: ...5167798 YTG J 0218 Johnson Controls Unitary Products 59 Typical HONEYWELL BAS Control Wiring Diagram...

Page 60: ...5167798 YTG J 0218 60 Johnson Controls Unitary Products Typical NOVAR BAS Control Wiring Diagram...

Page 61: ...4 Point Load Location lbs 6 Point Load Location lbs Shipping Operating X Y A B C D A B C D E F 078 6 5 ZF 865 860 38 24 200 149 218 292 140 114 95 138 167 205 090 7 5 ZF 885 860 38 24 205 153 223 299...

Page 62: ...ght given is for the maximum heater size available 54KW 49 49 Gas Heat2 2 Weight given is for the maximum number of tube heat exchangers available 8 tube 110 110 Variable Frequency Drive3 3 Weight inc...

Page 63: ...OR GAS INLET B 29 95 30 11 14 92 58 09 14 92 14 92 45 64 4X 24 38 ZF078 150 Unit Physical Dimensions Unit Model Number Dimension in A B C D E F 078 42 89 22 1 8 18 3 16 15 3 16 6 3 16 090 42 89 22 1 8...

Page 64: ...tructure or shrubs should not obscure condenser air discharge outlet 72 Right 12 Front 36 Left 36 Rear 36 Bottom2 2 Units may be installed on combustible floors made from wood or class A B or C roof c...

Page 65: ...t Opening TOP VIEW Bottom condensate drain Bottom gas supply entry FRONT RETURN AIR SUPPLY AIR RIGHT LEFT 20 1 8 19 1 8 17 1 8 6 13 16 6 13 16 32 11 16 14 1 2 16 3 8 18 1 16 25 9 16 12 5 16 27 1 2 24...

Page 66: ...it Electrical Entry ZF078 120 Unit Side Duct Openings Disconnect Swith Cover Power Entry 2 1 2 Control Entry 7 8 Power Entry 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry 7 8 FRONT Dot...

Page 67: ...it Left Duct Opening ZF Side Duct Dimensions Unit Model Number Dimension in A B C D 078 27 3 4 12 1 16 27 1 2 16 090 27 3 4 12 1 16 27 1 2 16 102 28 1 4 18 1 16 28 1 4 18 1 4 120 28 1 4 18 1 16 28 1 4...

Page 68: ...ions ZF078 150 Roof Curb ZF078 150 Transition Roof Curb 8 or 14 50 1 2 30 20 20 80 5 8 6 2 TYP INSULATED DECK UNDER COMPRESSOR SECTION INSULATED DECK UNDER CONDENSER SECTION FRONT RIGHT SUPPLY RETURN...

Page 69: ...nomizer without barometric relief 2EE047069241 Downflow End Return Horizontal or ERV 42 Economizer 42 tall cabinet 2EE047074242 50 Economizer 50 tall cabinet 2EE047076242 1 Barometric relief must be o...

Page 70: ...n 5005 York Drive Norman OK 73069 Economizer End Return W Power Exhaust Field Installed Horizontal Economizer W Power Exhaust Fresh Air Hood Field Installed Duct Work Power Exhaust Barometric Relief D...

Reviews: