5167798-YTG-J-0218
Johnson Controls Unitary Products
21
115°F
125°F
1875
77
87.5
8.8
31.3
27.3
20.4
-
-
-
78.2
9.7
23.0
21.8
14.9
-
-
-
72
80.7
8.8
47.5
40.5
33.5
26.6
-
-
73.2
9.8
42.9
36.0
29.1
22.2
-
-
67
73.8
8.9
63.7
53.7
46.7
39.7
32.8
-
68.3
9.9
61.8
50.3
43.4
36.5
29.6
-
62
70.1
8.8
70.1
67.8
55.6
48.7
41.7
34.7
67.5
9.8
67.5
64.1
51.2
44.3
37.4
30.5
2250
77
89.7
8.7
39.6
31.2
22.7
-
-
-
79.7
9.6
34.1
25.5
17.0
-
-
-
72 82.7
8.8
54.3
45.8
37.3
28.8
-
-
74.7
9.7
50.1
41.5
33.0
24.4
-
-
67 75.7
8.8
68.9
60.5
52.0
43.5
35.0
-
69.6
9.8
66.1
57.5
49.0
40.4
31.9
-
62 71.9
8.8
71.9
70.4
61.9
53.4
44.9
36.4
68.9
9.7
68.9
66.6
57.8
49.2
40.7
32.1
57 72.1
8.8
72.1
70.6
62.1
53.6
45.1
36.6
67.6
9.7
67.6
65.4
56.1
47.5
39.0
30.4
2625
77 92.0
8.7
48.0
35.0
25.0
-
-
-
81.3
9.5
45.2
29.3
19.1
-
-
-
72 84.7
8.7
61.1
51.1
41.1
31.1
-
-
76.2
9.6
57.2
47.0
36.8
26.6
-
-
67 77.5
8.7
74.2
67.2
57.2
47.2
37.2
-
71.0
9.7
70.4
64.8
54.6
44.4
34.2
-
62 73.7
8.7
73.7
72.9
68.1
58.1
48.1
38.1
70.3
9.6
70.3
69.2
64.4
54.2
44.0
33.8
57 73.8
8.7
73.8
73.1
68.4
58.4
48.4
38.4
69.0
9.6
69.0
67.9
62.6
52.4
42.2
32.0
3000
77 94.2
8.6
56.4
38.8
27.3
-
-
-
82.9
9.4
56.3
33.0
21.2
-
-
-
72 86.8
8.6
67.9
56.4
44.9
33.4
-
-
77.6
9.5
64.4
52.5
40.7
28.8
-
-
67 79.4
8.6
79.4
74.0
62.5
51.0
39.5
-
72.4
9.6
72.4
72.0
60.2
48.3
36.5
-
62 75.5
8.6
75.5
75.5
74.4
62.9
51.4
39.9
71.8
9.5
71.8
71.8
71.0
59.2
47.3
35.5
57 75.6
8.6
75.6
75.6
74.6
63.1
51.6
40.1
70.4
9.5
70.4
70.4
69.1
57.2
45.4
33.5
3375
72 87.7
8.6
72.0
59.8
47.5
35.3
-
-
78.2
9.5
67.8
55.4
43.0
30.7
-
-
67 80.2
8.6
80.2
77.5
66.2
54.0
41.7
-
72.9
9.6
72.9
72.9
63.7
51.3
39.0
-
62 76.2
8.6
76.2
76.2
75.7
63.5
51.2
39.0
72.3
9.5
72.3
72.3
71.9
59.6
47.2
34.8
57 76.4
8.6
76.4
76.4
75.9
63.7
51.5
39.2
70.9
9.5
70.9
70.9
70.2
57.9
45.5
33.1
3750
72 88.6
8.6
76.1
63.2
50.2
37.3
-
-
78.7
9.5
71.2
58.3
45.4
32.6
-
-
67 81.1
8.6
81.1
81.1
69.9
57.0
44.0
-
73.5
9.6
73.5
73.5
67.2
54.4
41.5
-
62 77.0
8.6
77.0
77.0
77.0
64.1
51.1
38.1
72.8
9.5
72.8
72.8
72.8
59.9
47.1
34.2
57 77.2
8.6
77.2
77.2
77.2
64.2
51.3
38.3
71.4
9.5
71.4
71.4
71.4
58.5
45.6
32.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65