5167798-YTG-J-0218
Johnson Controls Unitary Products
19
115°F
125°F
1625
77
75.2
7.3
29.2
26.1
18.9
-
-
-
68.0
7.9
28.3
22.9
16.6
-
-
-
72
67.9
7.1
43.8
36.6
29.3
22.1
-
-
60.9
7.7
41.0
33.9
26.8
19.6
-
-
67
60.5
7.0
58.4
47.1
39.8
32.6
25.4
-
53.8
7.5
53.8
44.1
36.9
29.8
22.7
-
62
56.1
6.8
56.1
56.1
47.7
40.5
33.3
26.0
50.9
7.3
50.9
50.9
43.7
36.6
29.4
22.3
1950
77
77.6
7.3
37.8
29.4
20.9
-
-
-
70.1
7.9
37.5
26.8
18.5
-
-
-
72
70.0
7.2
49.4
41.0
32.6
24.2
-
-
62.7
7.7
46.5
38.1
29.8
21.5
-
-
67
62.4
7.0
61.0
52.6
44.2
35.8
27.4
-
55.4
7.5
55.4
49.5
41.2
32.9
24.5
-
62
57.8
6.9
57.8
57.8
52.9
44.5
36.1
27.7
52.4
7.4
52.4
52.4
48.7
40.4
32.1
23.8
57
53.2
6.8
53.2
53.2
46.1
37.7
29.2
20.8
45.1
7.2
45.1
45.1
38.3
29.9
21.6
13.3
2275
77
80.0
7.4
46.3
32.6
23.0
-
-
-
72.1
8.0
46.8
30.8
20.4
-
-
-
72
72.2
7.2
55.0
45.4
35.8
26.2
-
-
64.6
7.8
51.9
42.4
32.9
23.4
-
-
67
64.3
7.0
63.6
58.2
48.6
39.0
29.4
-
57.0
7.6
57.0
54.9
45.4
35.9
26.4
-
62
59.6
6.9
59.6
59.6
58.2
48.6
39.0
29.4
53.9
7.4
53.9
53.9
53.8
44.3
34.8
25.3
57
54.8
6.8
54.8
54.8
50.6
41.0
31.4
21.8
46.4
7.2
46.4
46.4
42.2
32.7
23.2
13.7
2600
77
82.3
7.4
54.9
35.9
25.1
-
-
-
74.2
8.0
56.0
34.7
22.3
-
-
-
72
74.3
7.2
60.6
49.8
39.0
28.2
-
-
66.4
7.8
57.3
46.7
36.0
25.3
-
-
67
66.2
7.1
66.2
63.7
52.9
42.1
31.4
-
58.6
7.6
58.6
58.6
49.7
39.0
28.3
-
62
61.4
7.0
61.4
61.4
63.4
52.6
41.9
31.1
55.5
7.5
55.5
55.5
55.5
48.1
37.4
26.8
57
56.5
6.9
56.5
56.5
55.2
44.4
33.6
22.8
47.7
7.3
47.7
47.7
46.2
35.6
24.9
14.2
2925
72
75.5
7.3
65.8
53.9
42.0
30.1
-
-
67.4
7.8
62.5
50.7
38.9
27.0
-
-
67
67.3
7.1
67.3
66.1
57.0
45.1
33.2
-
59.5
7.6
59.5
59.5
53.6
41.8
30.0
-
62
62.4
7.0
62.4
62.4
63.4
51.5
39.7
27.8
56.3
7.5
56.3
56.3
56.3
46.2
34.4
22.6
57
57.4
6.9
57.4
57.4
56.8
44.9
33.0
21.1
48.4
7.3
48.4
48.4
47.7
35.9
24.1
12.3
3250
72
76.8
7.3
71.0
58.0
45.0
32.0
-
-
68.5
7.9
67.6
54.7
41.7
28.8
-
-
67
68.4
7.1
68.4
68.4
61.1
48.1
35.1
-
60.5
7.7
60.5
60.5
57.6
44.6
31.7
-
62
63.4
7.0
63.4
63.4
63.4
50.4
37.5
24.5
57.2
7.5
57.2
57.2
57.2
44.3
31.3
18.4
57
58.4
6.9
58.4
58.4
58.4
45.4
32.4
19.4
49.1
7.4
49.1
49.1
49.1
36.2
23.3
10.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZF078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65